# UPS for data centres in the Middle East: heat, dust and generators

For a data centre in the Gulf, the UPS has to live with hot rooms, fine dust and long hours on generators. AEC's online double-conversion UPS from 1 kVA to 1.2 MVA are rated up to 40 °C, with batteries best kept at 20–25 °C, and AEC Power LLC in Dubai serves the region with the Lainate EMEA office.

Rated temperatures [Contact us](https://www.aecups.com/en/contacts/?msg=Middle%20East%20data%20centre#form)

Heat

## Operating temperature of each range

As each range's AEC user manual or the EMEA 2026 catalogue gives it. Above 40 °C no range has a published figure or derating: ask AEC.

**AEC UPS and battery ranges: rated operating temperature and its source**

| Range | Operating temperature | Source |
| --- | --- | --- |
| [IST3](https://www.aecups.com/en/products/ist3/) | −5 to 40 °C, best 20–25 °C | AEC IST3 user manual p.6 §1.2 |
| [IST3-J](https://www.aecups.com/en/products/ist3-j/) IST3J-1K–IST3J-3K | −5 to 40 °C, best 20 °C | AEC IST3-J 1–3 user manual p.22 §3.1, p.24 |
| [IST3-J](https://www.aecups.com/en/products/ist3-j/) IST3J-6K, IST3J-10K | −5 to 40 °C, best 20–25 °C | AEC IST3-J 6–10 user manual p.6 §1.3 |
| [IST8](https://www.aecups.com/en/products/ist8/) | 0 to 40 °C | EMEA 2026 catalogue p.38, 44: lithium 0–60 °C, best 0–40 °C |
| [IST9](https://www.aecups.com/en/products/ist9/) | −5 to 40 °C | EMEA 2026 catalogue p.64 |
| [IST7 10–40](https://www.aecups.com/en/products/ist7-10-40/) | −5 to 40 °C, best 20–25 °C | AEC IST7 10–40 user manual p.6 §1.3 |
| [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/) | −5 to 40 °C, best 20–30 °C | AEC IST7 60–200 user manual p.34–35 §3.2.2 |
| [IST6-120](https://www.aecups.com/en/products/ist6-120/) | −5 to 40 °C | IST6 30–120 user manual |
| [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/) | 0 to 40 °C | IST6 200–500 AEC user manual |
| [IST6 400–1200](https://www.aecups.com/en/products/ist6-400-1200/) | 0 to 40 °C | IST6 400–1200 AEC user manual |
| [L6 Lithium](https://www.aecups.com/en/products/l6-lithium/) | 0 to 40 °C, best 20–30 °C | L6 user manual App. A; EMEA 2026 catalogue p.177 |
| [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/) BB4 | 0 to 40 °C, best 25 °C | BB4 user manual (2025) §2.1, §3.3 |
| [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/) BB5–BB8 | 0 to 40 °C, best 20–25 °C | AEC BB5–BB8 user manuals §3.3 |

Design

## What changes in a hot, dusty site

**Cooling is part of the UPS.** Every kW the UPS loses is a kW of heat the room must remove: at 96% efficiency a 100 kW load gives about 4.2 kW of heat. The modular [IST6 400–1200](https://www.aecups.com/en/products/ist6-400-1200/) reaches 98.1% with PLUS modules, which cuts that heat by more than half. Each model page gives its heat at full load and the air it needs.

**50 or 60 Hz.** Saudi Arabia's grid runs at 60 Hz, most of the Gulf at 50 Hz. The [IST9](https://www.aecups.com/en/products/ist9/), [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/) and IST6 ranges are rated for 50 / 60 Hz, each datasheet with its window; the IST7-T is a 50 Hz design. Say which grid the site has when you ask for a UPS.

**Batteries first.** VRLA life halves for about every 8 °C above 25 °C (OZ Power data). Keep the batteries in the coolest room, or choose [L6 lithium cabinets](https://www.aecups.com/en/products/l6-lithium/) (LiFePO4), rated 0 to 40 °C.

**Generators.** In double conversion the output does not follow the generator's voltage and frequency while it starts and settles. Input THDi ≤ 3% ([IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)) or ≤ 1.5% ([IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)) keeps the generator's rating close to the load.

**Redundancy.** Up to eight IST6 200–500 or 400–1200, or IST7 60–200, in parallel, and an extra power module for N+1 in the modular ranges, so one module can be serviced with the load on.

AEC Power LLC · Dubai

## The AEC Group company for the Middle East.

Dubai · UTC+4 · 08–18 local. Requests go through the EMEA office in Lainate (Milan), which answers within one working day.

[Contact the EMEA office](https://www.aecups.com/en/contacts/#form)

Questions

## Questions people ask

#### Which ambient temperature do AEC UPS run at?

Every AEC UPS range is rated for operation up to 40 °C, from −5 or 0 °C depending on the range, as its user manual or the EMEA 2026 catalogue gives it; the table lists each range with its source. None publishes operation above 40 °C: for a hotter room, ask AEC before you size.

#### What does heat do to the batteries?

It shortens their life: VRLA battery life halves for about every 8 °C above 25 °C (OZ Power data: about 43% of design life at 35 °C). AEC's battery cabinets are rated 0 to 40 °C, best at 20–25 °C (BB5–BB8) or 25 °C (BB4), and the L6 lithium cabinets 0 to 40 °C, so the battery room is where cooling pays first.

#### How do I plan for dust?

Put the UPS in a closed, cooled electrical room with filtered air, keep the clearances its manual gives for the air paths, and add filter checks to the maintenance plan. The ranges' datasheets give no dust rating: ask AEC about a filtered enclosure for the site.

#### Do AEC UPS run on a generator?

Yes: online double conversion rebuilds the output from DC, so the load sees a stable voltage and frequency while the generator starts and settles. A low input THDi makes the generator easier to size: ≤ 3% on the IST7 60–200, with input power factor ≥ 0.99, and ≤ 1.5% on the IST6 200–500.

#### Is there an AEC office in the Middle East?

Yes: AEC Power LLC in Dubai is the AEC Group company for the Middle East, working 08–18 local time (UTC+4). Requests go through the EMEA office in Lainate, which answers within one working day and involves the Dubai team.

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.

[Contact us](https://www.aecups.com/en/contacts/#form) [+39 02 9415 8991](tel:+390294158991)

More about AEC: [About AEC](https://www.aecups.com/en/about/) [Company](https://www.aecups.com/en/company/) [Why AEC](https://www.aecups.com/en/why-aec/) [Warranty](https://www.aecups.com/en/warranty/) [UPS in 3D](https://www.aecups.com/en/3d/) [Applications](https://www.aecups.com/en/applications/) [Example designs](https://www.aecups.com/en/example-designs/) [AEC EMEA](https://www.aecups.com/en/aec-emea/) [AEC in brief](https://www.aecups.com/en/aec-in-brief/)