# Isolation transformer UPS: when you need one

An isolation transformer UPS has a transformer that separates the load electrically from the mains, so there is no direct conductive path between input and output. That isolation creates a new neutral at the output, blocks some disturbances and lets the installer choose a local earthing arrangement.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

It is worth the extra weight and space on industrial sites, harsh supplies and loads that need galvanic isolation; for most IT rooms a transformerless UPS is enough.

**In brief**

- Galvanic isolation means the output is coupled to the input only magnetically, through the transformer, not by copper.
- The transformer secondary is a new source with its own neutral, often called a separately derived system.
- Transformer-based UPS systems are heavier and larger; transformerless designs are lighter, smaller and usually more efficient.
- Check the bypass: if the bypass feeds the load directly, isolation applies only while the load is on the inverter.
- Choose isolation for a reason (earthing, neutral, harsh supply, voltage), not by habit.

## What an isolation transformer UPS is

A UPS with an **isolation transformer** includes a transformer whose primary and secondary windings are separate. Energy passes from one winding to the other through the magnetic field in the iron core, so there is no metallic connection between the two sides. This is **galvanic isolation**.

In an online double-conversion UPS the transformer usually sits at the output, after the inverter. The rectifier turns the mains into DC, the inverter rebuilds clean AC, and the transformer delivers it to the load. Some designs place it at the input instead, or add one on the bypass line.

A **transformerless UPS** has no such transformer in the power path. Its inverter produces the output voltage directly, using fast semiconductor switching. Most modern UPS systems up to large ratings are built this way. Our guide to [what a UPS is](https://www.aecups.com/en/blog/what-is-a-ups/) explains the basic blocks if you need them.

## Galvanic isolation and the new neutral

The secondary winding of the transformer is a new voltage source. Its star point gives a **new neutral**, which is not connected to the input neutral. In installation terms, the output becomes a **separately derived system**: a source whose neutral and earthing you define at the transformer.

This has practical effects:

- **Neutral-earth voltage.** On long or loaded supplies, the incoming neutral can sit a few volts above earth. Bonding the new neutral to earth near the load brings the neutral-earth voltage close to zero, which some electronics and measuring equipment need.
- **Earthing arrangement.** A different earthing system can be set for the downstream circuits, following IEC 60364 and local rules. The transformer makes this possible; the design and verification remain the job of the installation designer.
- **No neutral needed at the rectifier input.** Because the transformer secondary creates the output neutral, the rectifier can be fed with three phases and no neutral, while the output still provides one for single-phase loads. The bypass, which bypasses the transformer, still needs the incoming neutral.
- **Harmonic containment.** In a delta-star (Δ/Y) transformer, the triplen harmonic currents (3rd, 9th and so on) drawn by single-phase loads on the star side circulate in the delta winding. They do not flow in the lines on the delta side, which here is the inverter. Only the zero-sequence part is blocked, and the circulating current still heats the transformer.

An isolation transformer does not stop every disturbance. It attenuates common-mode noise and blocks DC paths, but it passes the voltage the inverter produces. In a double-conversion UPS that voltage is already clean, so the transformer's main role is isolation and neutral, not filtering.

## When you need a transformer UPS

Choose a transformer-based design when one of these applies:

- **Industrial sites** with motors, drives and welding loads that produce noise, unbalance and earth currents. Our guide to [UPS for industry](https://www.aecups.com/en/blog/ups-for-industry/) covers these loads in more detail.
- **Harsh or weak supplies**, such as remote sites, mines, railways or plants at the end of long lines, where neutral quality is poor.
- **A stable neutral-earth reference** for instruments, control systems and some laboratory equipment.
- **A different earthing system downstream**, defined by the installation designer for that part of the site.
- **Medical locations**, where special earthing and isolation rules apply. Here the UPS is one part of a system that the designer must assess against IEC 60364-7-710 and national rules; see our guide on [UPS for hospitals](https://www.aecups.com/en/blog/ups-for-hospitals/).
- **A voltage change** between supply and load. A transformer can adapt one voltage to another; check that the UPS you choose offers the ratio you need.

If none of these applies, as in many offices and data centres with a good TN-S supply, a transformerless UPS normally does the job with less weight and lower losses.

## Transformer-based vs transformerless UPS

The comparison below is general. Exact figures differ by design, so check each datasheet.

**Transformer based UPS vs transformerless: general comparison**

| Aspect | Transformer-based UPS | Transformerless UPS |
| --- | --- | --- |
| Galvanic isolation | Yes, between input and output (on the inverter path) | No, unless an external transformer is added |
| Output neutral | New neutral from the transformer secondary | Neutral passed through from the input |
| Weight and footprint | Higher: copper windings and iron core | Lower |
| Efficiency | Lower, because the transformer adds its own losses | Usually higher |
| Unbalanced and non-linear loads | Handles them well; triplen currents circulate in the delta winding, not in the inverter | Depends on inverter design |
| Short-circuit and inductive loads | Generally withstands them | Depends on design and on inverter current limits |
| Typical use | Industry, harsh grids, isolation and earthing needs | IT rooms, data centres, offices |

Modular UPS systems are usually transformerless, because a transformer does not split well into hot-swap modules. Where a modular system needs isolation, a separate output transformer is added. See our guide to [modular UPS](https://www.aecups.com/en/blog/modular-ups/) for how those systems scale.

## Weight, space and efficiency trade-offs

A transformer is mostly copper and electrical steel, so it adds significant mass and volume. Plan the floor loading, the access route and the lifting method early, especially for upper floors.

The transformer also has losses: **no-load losses** in the core, present whenever it is energised, and **load losses** in the windings, which grow with current. These become heat. They lower the efficiency of the UPS compared with an equivalent transformerless unit and add to the cooling load; see our guide to [UPS efficiency and ECO mode](https://www.aecups.com/en/blog/ups-efficiency-eco-mode/) for how to turn efficiency into kW of losses.

Two points work in favour of a built-in transformer. First, an output transformer matched to the inverter avoids the magnetising inrush that an external transformer causes when it is switched on, which can otherwise overload the inverter or trip the UPS to bypass. Second, one product is easier to install and service than a UPS plus a separate transformer cabinet.

## Sizing an isolation transformer UPS: worked example

A packaging line needs isolation for its PLCs, drives and instruments. The measured load is 70 kW at a power factor of 0.9, on a 400 V three-phase supply.

1. Apparent power: kVA = kW / PF = 70 / 0.9 = 77.8 kVA.
2. Line current: I = P / (√3 × V × PF) = 70,000 / (1.732 × 400 × 0.9) = 112 A.
3. Headroom: to keep the UPS at about 80% load (a common rule of thumb), the rating must be at least 70 / 0.8 = 87.5 kW and 77.8 / 0.8 = 97.2 kVA.
4. Choice: an 80 kVA / 72 kW unit is too small. A 100 kVA / 90 kW unit gives 70 / 90 = 78% load in kW and 77.8 / 100 = 78% in kVA.
5. Check the phases: list single-phase loads by phase. A UPS that accepts 100% unbalanced load copes with an uneven split, but the most loaded phase must still stay within its share of the rating.
6. Battery: size the runtime separately, as in our [UPS backup time guide](https://www.aecups.com/en/blog/ups-backup-time/).

The same steps apply to any UPS; our [UPS sizing guide](https://www.aecups.com/en/blog/ups-sizing/) covers inrush and growth in more depth.

## AEC IST7-T: isolation transformer as standard

The [AEC IST7-T](https://www.aecups.com/en/products/ist7-t/) is a three-phase online double-conversion UPS from 100 to 200 kVA, with an output isolation transformer built into every model. Figures from the datasheet:

- **Models:** 20, 40, 60, 80, 100, 120 and 200 kVA, rated at 18, 36, 54, 72, 90, 108 and 180 kW (output power factor 0.9).
- **Power path:** input EMI filter and contactor, three-phase PFC rectifier, DC bus, three-phase inverter, Δ/Y transformer, output static switch. The battery connects to the DC bus through a bidirectional converter. Bypass and maintenance bypass are outside the inverter path.
- **Input:** 380 / 400 / 415 V, ±25% range with full load from −20% to +25%. The rectifier input is three wires plus PE, with no neutral; the bypass input is three phases plus N and PE. Input power factor ≥ 0.99, THDi below 5%.
- **Output:** 220 / 230 / 240 V phase-to-neutral, THDv below 1% on linear load, 50 Hz ±0.2% in battery mode. 0 ms transfer from mains to battery and 1 ms from inverter to bypass.
- **Loads:** 100% three-phase unbalanced load and full kVA output at 100% non-linear load, with improved short-circuit and inductive-load capability.
- **Size and weight:** 600 × 800 × 2000 mm cabinets for 20-80 kVA and 1000 × 800 × 2000 mm for 100-200 kVA (W × D × H); from 345 kg (20 kVA) to 1,280 kg (200 kVA).
- **Standards and environment:** CE marking, EN / [IEC 62040-1](https://webstore.iec.ch/en/publication/80573) and 62040-2 (category C3); −5 to 40 °C operation; IP20, or IP21 with the optional top cover.

The IST7-T also offers ECO mode, in which the load runs on the bypass and therefore without the transformer's isolation. For larger modular systems, the [IST6 200–500 kVA](https://www.aecups.com/en/products/ist6-200-500/) and [IST6 400–1200 kVA](https://www.aecups.com/en/products/ist6-400-1200/) ranges offer an optional output isolation transformer of the same capacity.

## Checklist for an isolation transformer UPS

1. Write down why you need isolation: neutral, earthing, harsh supply, voltage change or a specific load requirement.
2. Agree the earthing arrangement downstream of the UPS with the installation designer.
3. Check how the bypass and maintenance bypass are fed, and whether the load needs isolation in those modes too.
4. Size the UPS in both kW and kVA with about 20% headroom, and check the load per phase.
5. Confirm floor loading, door widths and lifting for the cabinet weight.
6. Include transformer losses in the heat load of the room.
7. Decide whether ECO mode is acceptable, given that it bypasses the isolation.

## Common mistakes

- **Assuming isolation in every mode.** On bypass or maintenance bypass the load may be fed straight from the mains. If isolation must be permanent, plan a bypass transformer or a different arrangement.
- **Forgetting the neutral-earth bond.** A new neutral needs to be bonded to earth according to the chosen earthing system; left floating, it does not give the reference you expect.
- **Adding an external transformer without checking inrush.** Switching on a large transformer downstream of a UPS can overload the inverter.
- **Choosing a transformer "to be safe".** Without a real need, you pay in weight, space and losses.
- **Treating the UPS as medical certification.** Isolation helps, but compliance of a medical location depends on the whole installation.

Not sure whether your site needs galvanic isolation? [Describe your supply and loads to us](https://www.aecups.com/en/contacts/#form), or use the [UPS finder](https://www.aecups.com/en/tools/ups-finder/) to compare three-phase ranges.

Questions

## Questions people ask

#### What is an isolation transformer UPS?

It is a UPS with a transformer in the power path that separates the output electrically from the input. Energy crosses the transformer magnetically, so there is no direct copper connection between mains and load. The transformer secondary provides a new neutral at the output.

#### What is the difference between a transformer based UPS and a transformerless UPS?

A transformer-based UPS has an isolation transformer, usually at the output, giving galvanic isolation and a new neutral. A transformerless UPS produces the output directly from the inverter, so it is lighter, smaller and usually more efficient. The transformer-based design suits industrial sites, harsh supplies and specific earthing needs.

#### Does a UPS need an isolation transformer?

Not always. Most IT rooms and offices on a good supply work well with a transformerless UPS. An isolation transformer is worth it when you need a new neutral, a different earthing system downstream, protection from a poor supply or a voltage change.

#### Does an isolation transformer UPS give isolation on bypass?

Only if the bypass is also routed through a transformer. In many designs, including those where the transformer sits on the inverter output, the bypass feeds the load from the mains directly. In that case isolation applies while the load is on the inverter.

#### Is a transformer UPS less efficient?

Yes, generally, because the transformer adds core losses whenever it is energised and winding losses that grow with load. The difference depends on the design and the load level. The extra losses also become heat that the room cooling must remove.

#### Can an isolation transformer UPS be used in hospitals?

Yes, as part of a hospital installation, where isolation and special earthing rules often apply. Compliance depends on the whole system, assessed by the designer against IEC 60364-7-710 and national rules, not on the UPS alone. Ask for the full requirements before choosing equipment.

Products

## Products in this guide

[All products](https://www.aecups.com/en/products/)

### IST7-T

VRLA

100–200 kVA

Online UPS with isolation transformer, 100–200 kVA

Details

### IST6 200–500

VRLA

200–500 kVA

Modular online UPS, double conversion, 200–500 kVA

Details

### IST6 400–1200

VRLA

400–1200 kVA

Modular online UPS, double conversion, 400–1200 kVA

Details

Blog

## Keep reading

[All articles](https://www.aecups.com/en/blog/)

[**Three-phase UPS: configurations, sizing and installation** A three-phase UPS protects 400 V loads from about 10 kVA up. 3/3 against 3/1, phase balancing, sizing from measured currents, and installation.](https://www.aecups.com/en/blog/three-phase-ups/) [**UPS vs generator: how they differ and work together** A UPS gives instant power, a generator long runtime after a start delay. How to combine them, size the generator and avoid common mistakes.](https://www.aecups.com/en/blog/ups-and-generator/) [**UPS datasheet explained: every line, with examples** How to read a UPS datasheet: UPS specifications explained section by section, from input and battery to efficiency, using a real AEC datasheet.](https://www.aecups.com/en/blog/how-to-read-a-ups-datasheet/)