# kVA vs kW: power factor and UPS sizing explained

kVA measures the apparent power a UPS can carry (volts × amps), while kW measures the active power that actually does work in your equipment. The two are linked by the power factor, kW = kVA × PF: a 10 kVA UPS rated at 0.9 gives 9 kW, while AEC's IST3 and IST7 give as many kW as kVA.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

Check both ratings against your load.

**In brief**

- **kVA** is apparent power: voltage × current, whatever the current does.
- **kW** is active power: the part converted into work and heat.
- **Power factor (PF)** = kW ÷ kVA, a number between 0 and 1.
- A UPS has two limits, kVA and kW. Your load must stay within both, with a margin.
- Many modern online UPS have an output PF of 1 (kVA = kW); others are rated at 0.9 or 0.8.

## Apparent, active and reactive power in plain words

Alternating current (AC) does not always push energy into a load in step with the voltage. Motors, transformers and electronic power supplies draw current that is partly out of step, or distorted. That changes what the supply has to carry compared with what the load actually uses.

**Apparent power (S)** is simply voltage × current, measured in volt-amperes (VA) or kilovolt-amperes (kVA). It is what cables, breakers and the UPS inverter must be able to carry, because they feel the full current.

**Active power (P)**, in watts (W) or kilowatts (kW), is the part that does useful work: it runs the processor, turns the fan, heats the room. Your electricity meter records it.

**Reactive power (Q)**, in volt-amperes reactive (var or kvar), is energy that flows back and forth between the supply and the magnetic or electric fields in the load. It does no work, but the current that carries it still flows through every wire.

The common analogy is a glass of beer. The whole glass is kVA, the beer is kW and the foam is reactive power. It helps, with one caveat: the parts do not simply add up. For a sinusoidal load the relationship is a right-angled triangle, S² = P² + Q². A load of 9 kW and 4.36 kvar gives 10 kVA, not 13.36 kVA.

## What is power factor?

The **power factor (PF)** is the ratio of active power to apparent power: PF = kW ÷ kVA. It is always between 0 and 1. A PF of 1 means every volt-ampere is a useful watt, as with a heater. A PF of 0.7 means you carry 1 kVA of current to get 0.7 kW of work.

For pure sine waves the PF equals cos φ, the cosine of the angle between voltage and current. With non-linear loads, such as the switched-mode power supplies in IT equipment, the current is also distorted by harmonics. The true PF then includes that distortion too, so it can be lower than cos φ alone suggests.

Two different power factors matter for a UPS:

- **Load power factor:** how your equipment draws current. You cannot change it, but you need to know or estimate it.
- **UPS output power factor:** a design rating. It tells you how many kW the UPS can deliver for each kVA of its rating.

UPS data sheets also show an *input* power factor, often ≥ 0.99 on online units with a PFC (power factor correction) rectifier. That describes how the UPS loads the mains or a generator, not what it can deliver to your equipment.

## UPS output power factor: 0.8, 0.9 or 1.0

A UPS is rated in kVA and in kW. The output power factor links the two: kW rating = kVA rating × output PF. Older designs were often rated at 0.8. Many current online UPS are rated at 0.9 or 1.0.

This matters because the kW limit is often the one you hit first. A 10 kVA UPS at output PF 0.9 gives you 10 kVA but only 9 kW. A 10 kVA UPS at PF 1 gives you 10 kVA and 10 kW. On paper both are "10 kVA", yet the second one carries 1 kW more of real load.

The power a UPS can deliver to a given load is the lower of two figures: its kW rating, and its kVA rating × the load PF. With a 10 kVA / 9 kW UPS and a load at PF 0.95, the kVA limit allows 9.5 kW, but the kW limit stops you at 9 kW. With a load at PF 0.8, the kVA limit allows only 8 kW.

## kVA to kW conversion table

The table shows the kW available at three output power factors. It is pure arithmetic: kW = kVA × PF. The last two columns give the full-load current, single-phase at 230 V (I = VA ÷ 230) and three-phase at 400 V (I = VA ÷ (√3 × 400)).

**kVA to kW and amps at common power factors**

| kVA | kW at PF 0.8 | kW at PF 0.9 | kW at PF 1.0 | Amps, 230 V single-phase | Amps per phase, 400 V three-phase |
| --- | --- | --- | --- | --- | --- |
| 1 | 0.8 | 0.9 | 1 | 4.3 | 1.4 |
| 3 | 2.4 | 2.7 | 3 | 13.0 | 4.3 |
| 6 | 4.8 | 5.4 | 6 | 26.1 | 8.7 |
| 10 | 8 | 9 | 10 | 43.5 | 14.4 |
| 20 | 16 | 18 | 20 | 87.0 | 28.9 |
| 40 | 32 | 36 | 40 | 173.9 | 57.7 |
| 100 | 80 | 90 | 100 | 434.8 | 144.3 |

Above about 10–20 kVA, UPS are normally three-phase, so the single-phase currents for 20, 40 and 100 kVA are shown only for comparison.

## How to convert kW, kVA and amps: worked examples

### Single-phase, 230 V: P = V × I × PF

A rack draws 12 A at 230 V and its power supplies have a PF of 0.9.

1. Apparent power: S = 230 V × 12 A = 2,760 VA = 2.76 kVA.
2. Active power: P = 2,760 VA × 0.9 = 2,484 W ≈ 2.5 kW.

### Three-phase, 400 V: P = √3 × V × I × PF

A small server room draws 30 A per phase on a 400 V three-phase supply, with a PF of 0.95. V is the line-to-line voltage and √3 ≈ 1.732.

1. Apparent power: S = 1.732 × 400 V × 30 A = 20,784 VA ≈ 20.8 kVA.
2. Active power: P = 20,784 VA × 0.95 = 19,745 W ≈ 19.7 kW.

### From kW back to kVA and amps

You know the load is 3 kW at PF 0.9, single-phase 230 V.

1. kVA = kW ÷ PF = 3 ÷ 0.9 = 3.33 kVA.
2. Current: I = P ÷ (V × PF) = 3,000 ÷ (230 × 0.9) = 14.5 A.

For three-phase, use I = P ÷ (√3 × V × PF). A 20 kW load at PF 0.9 and 400 V draws 20,000 ÷ (1.732 × 400 × 0.9) = 32.1 A per phase.

## What size UPS for 3 kW?

"What size UPS for 3 kW?" is a common question, and the honest answer is: usually more than a 3 kVA unit. Work through both limits.

1. **Load in kW:** 3 kW.
2. **Load in kVA:** at a load PF of 0.9, 3 ÷ 0.9 = 3.33 kVA.
3. **Add the margin:** keeping the load within about 80% of the rating, as in our [UPS sizing guide](https://www.aecups.com/en/blog/ups-sizing/), you need at least 3 ÷ 0.8 = 3.75 kW and 3.33 ÷ 0.8 = 4.17 kVA.
4. **Check candidates against both:**
  - 3 kVA / 2.7 kW (output PF 0.9): too small on both counts.
  - 3 kVA / 3 kW (output PF 1): the kW rating equals the load with no margin, and 3 kVA is below the 3.33 kVA the load draws. Too small.
  - 6 kVA / 5.4 kW (output PF 0.9): 5.4 kW ≥ 3.75 kW and 6 kVA ≥ 4.17 kVA. Suitable, with room to grow.

If "3 kW" is the rating of your home supply rather than a measured load, it is the maximum your meter allows, not what the UPS has to protect. In most homes you back up only some circuits, such as the boiler controls, router and a few sockets, and the real load is often far lower. Measure it, or see our guide to [choosing a UPS for the home](https://www.aecups.com/en/blog/ups-for-home/).

## Inrush, non-linear loads and crest factor

Steady-state kW and kVA are not the whole story. Three effects can push a UPS past its limits even when the averages look fine.

**Inrush current** is the short surge when equipment switches on, as capacitors charge or motors start. It can be several times the normal current for a few milliseconds or longer. A UPS handles it through its overload capacity: the inverter carries, say, 150% for a set time, and beyond that transfers the load to the bypass. Laser printers, motors, pumps and compressors are typical culprits.

**Non-linear loads** draw current in short pulses instead of a smooth sine wave. Most IT power supplies, LED drivers and variable-speed drives behave like this. The pulses create harmonic currents, which add to the kVA without adding kW and can distort the output voltage.

**Crest factor** is the ratio between the peak current and the RMS (effective) current. A clean sine wave has a crest factor of about 1.41. Equipment without PFC can draw current with a crest factor of around 3, which is why [IEC 62040-3](https://webstore.iec.ch/en/publication/60140), the UPS performance standard, uses a reference non-linear load with a crest factor of 3 for testing. The UPS must deliver those peaks without the voltage collapsing; online double-conversion units are designed to.

## Common mistakes

- **Comparing watts with kVA.** A 3 kW load on a "3 kVA" UPS at output PF 0.9 is already 11% overloaded on the kW limit.
- **Checking only one limit.** On a PF 1 UPS the kVA limit can bind first when the load PF is below 1.
- **Confusing input and output power factor.** An input PF of ≥ 0.99 says nothing about the kW the UPS delivers.
- **Using nameplate maximums as the load.** Power supply ratings are worst-case figures; measured loads are usually lower. Measure where you can.
- **Ignoring derating.** Some output PF ratings apply only below a stated temperature, or with a given battery configuration. Read the notes on the data sheet.
- **Forgetting inrush and growth.** Sizing to 100% leaves no room for start-up peaks or the next server.
- **Confusing power and runtime.** kVA and kW decide the UPS; the backup time decides the battery. See our [backup time calculator](https://www.aecups.com/en/tools/backup-time/).

### Checklist to avoid them

1. List the loads and find kW (or V and A) for each, ideally measured.
2. Estimate the load PF; if unknown, a cautious 0.7 avoids undersizing.
3. Work out total kW and total kVA.
4. Divide both by 0.8 for a margin of about 20%.
5. Read the UPS kVA and kW ratings, and the output PF, with any temperature conditions.
6. Check that both UPS ratings exceed both figures from step 4.
7. Check overload capacity against known inrush loads.
8. Confirm phases and voltage: single-phase 230 V or three-phase 400 V.

## Output power factor across AEC UPS ranges

Figures below are from the AEC data sheets. Always check the full technical data of the model you choose.

**Stated output power factor of AEC UPS ranges**

| Range | Size | Output power factor | Example rating |
| --- | --- | --- | --- |
| [IST3](https://www.aecups.com/en/products/ist3/) | 1–10 kVA single-phase | 1 (kVA = kW) | 3000 VA / 3000 W · 10000 VA / 10000 W |
| [IST3-J](https://www.aecups.com/en/products/ist3-j/) | 1–10 kVA single-phase | 1 (kVA = kW) | 6000 VA / 6000 W |
| [IST8](https://www.aecups.com/en/products/ist8/) | 1–3 kVA single-phase, lithium | 1 | 3000 VA / 3000 W |
| [IST9](https://www.aecups.com/en/products/ist9/) | 10–40 kVA | 1.0 | 40 kVA / 40 kW |
| [IST7 10–40 kVA](https://www.aecups.com/en/products/ist7-10-40/) | 10–40 kVA | 1 (settable 0.9) | 20 kVA / 20 kW |
| [IST7 60–200 kVA](https://www.aecups.com/en/products/ist7-60-200/) | 60–200 kVA | 1 (settable 0.9) | 120 kVA / 120 kW |
| [IST7-T](https://www.aecups.com/en/products/ist7-t/) | 100–200 kVA | 0.9 (from the kVA / kW ratings) | 100 kVA / 90 kW · 200 kVA / 180 kW |
| [IST6-120](https://www.aecups.com/en/products/ist6-120/) | 30–120 kVA modular | 1 | 30 kVA / 30 kW per module |
| [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/) | 200–500 kVA modular | settable 0.8–1.0 (default 1.0) | 50 kVA / 50 kW per module |
| [IST6 400–1200](https://www.aecups.com/en/products/ist6-400-1200/) | 400–1200 kVA modular | settable 0.8–1.0 (default 1.0) | 100 kVA / 100 kW per module |

So for a 3 kW load, the [IST3](https://www.aecups.com/en/products/ist3/) 6 kVA model at 6,000 W leaves a comfortable margin, while the 3 kVA model does not. The IST3 3 kVA and the [IST8](https://www.aecups.com/en/products/ist8/) 3 kVA both deliver 3,000 W, which, keeping the load within the usual 80% and with a load PF of 0.9, suits loads up to about 2.2 kW (2.4 kVA × 0.9).

On the three-phase side, the [IST9](https://www.aecups.com/en/products/ist9/) and IST7 deliver their full kVA rating as kW, so a 40 kVA unit carries 40 kW. The [IST7-T](https://www.aecups.com/en/products/ist7-t/) with isolation transformer is rated at 0.9, so its 100 kVA model delivers 90 kW. On the IST6 and IST7 ranges, the inverter's overload times are also stated for different load power factors. At PF 0.8 the IST6 transfers to bypass above 105%, so check the data sheet when the load PF is low. For inrush, the static bypass of the IST7 60–200 kVA handles up to 300% for 100 ms.

To compare models quickly, try the [UPS finder](https://www.aecups.com/en/tools/ups-finder/). For a mixed or large load, [send us your load list](https://www.aecups.com/en/contacts/#form) and AEC will check both the kVA and kW limits for you.

Questions

## Questions people ask

#### What is the difference between kVA and kW?

kVA is apparent power, voltage multiplied by current. kW is active power, the part that does useful work. They are linked by the power factor: kW = kVA × PF, so kW is never higher than kVA.

#### How do I convert kVA to kW?

Multiply the kVA by the power factor. At PF 0.8, 10 kVA is 8 kW; at PF 0.9 it is 9 kW; at PF 1 it is 10 kW. To go from kW to kVA, divide by the power factor instead.

#### What is the power factor of a UPS?

The output power factor of a UPS tells you how many kW it can deliver per kVA of rating. Common values are 0.8, 0.9 and 1.0. A UPS with output PF 1 delivers its full kVA rating as kW.

#### What size UPS do I need for 3 kW?

A 5 or 6 kVA UPS: a 3 kVA unit is too small. At a load PF of 0.9, 3 kW is 3.33 kVA; keeping the load within 80% of the rating means at least 3.75 kW and 4.17 kVA.

#### Is a 10 kVA UPS the same as 10 kW?

Only if its output power factor is 1. At output PF 0.9 a 10 kVA UPS delivers 9 kW, and at 0.8 it delivers 8 kW. Read both the kVA and kW ratings on the data sheet.

#### What is crest factor in a UPS?

Crest factor is the ratio between peak current and RMS current. A pure sine wave has about 1.41, while IT power supplies without power factor correction can reach around 3. The UPS must supply these peaks without its output voltage collapsing.

Products

## Products in this guide

[All products](https://www.aecups.com/en/products/)

### IST3

VRLA

1–10 kVA

Online UPS, double conversion, tower, 1–10 kVA

Details

### IST8

Lithium

1–3 kVA

Online UPS, lithium, rack / tower, 1–3 kVA

Details

### IST9

VRLA

10–40 kVA

Online UPS, rack / tower, 10–40 kVA

Details

### IST7-T

VRLA

100–200 kVA

Online UPS with isolation transformer, 100–200 kVA

Details

Blog

## Keep reading

[All articles](https://www.aecups.com/en/blog/)

[**UPS sizing: how to work out the power you need** How to size a UPS: list the loads, convert watts to VA, keep 20% headroom in both VA and W, then pick the battery. Two worked examples and a checklist.](https://www.aecups.com/en/blog/ups-sizing/) [**UPS for blackouts and storms: what to know** A UPS keeps equipment running through a blackout and filters storm sags and surges. What to check, how long it lasts and which AEC ranges fit.](https://www.aecups.com/en/blog/ups-for-blackouts/) [**Online UPS vs line-interactive vs offline: UPS types** The three UPS types compared: offline, line-interactive and online double conversion, with transfer time, VFI/VI/VFD classes and ECO mode.](https://www.aecups.com/en/blog/ups-types-online-line-interactive-offline/)