# Three-phase UPS: configurations, sizing and installation

A three-phase UPS is an uninterruptible power supply that takes its input from a three-phase 400 V supply and keeps critical loads running through mains failures and disturbances. It is the usual choice from about 10-20 kVA upwards: server rooms, data centres, hospitals, factories and whole buildings.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

A three-phase uninterruptible power supply can feed three-phase loads (3/3) or deliver a single-phase output from a three-phase input (3/1).

**In brief**

- **3/3** feeds a three-phase board or three-phase machines; **3/1** feeds single-phase loads with no phase balancing downstream.
- Three-phase power is **√3 × V × I × PF**, but with single-phase loads the busiest phase sets the size, not the total.
- The neutral matters: unbalance and IT loads can push large currents through it.
- Transformerless units are smaller and usually more efficient; isolation-transformer units add galvanic isolation for harsh sites.
- Parallel and modular systems add capacity and N+1 redundancy as the load grows.

## What is a three-phase UPS?

A three-phase supply carries three alternating voltages, 120° apart. In Europe you measure 230 V between any phase and neutral, and 400 V between two phases. It moves far more power through a cable of a given size than a single phase can.

A three-phase UPS connects to that supply. Most units sold today are **online double-conversion** UPS, class VFI under [IEC 62040-3](https://webstore.iec.ch/en/publication/60140). The rectifier turns the incoming AC into DC, the batteries sit on that DC link, and the inverter rebuilds a clean, stable AC output. When the mains fails, the inverter keeps running from the batteries with no break.

A **static bypass**, an electronic switch, can transfer the load straight to the mains if the UPS is overloaded or develops a fault. If you are still choosing between supply types, our guide to [single-phase vs three-phase UPS](https://www.aecups.com/en/blog/single-vs-three-phase-ups/) covers the basics. This article goes deeper into how a three-phase UPS system is configured, sized and installed.

## Three-phase UPS configurations: 3/3 or 3/1?

The two numbers describe the input and the output. The first is the number of phases in, the second the number of phases out.

- **3/3 (three-phase in, three-phase out):** the UPS rebuilds all three phases. Use it for a three-phase distribution board, motors, pumps, lifts, medical imaging, industrial machines, or many single-phase circuits spread across three phases.
- **3/1 (three-phase in, single-phase out):** the UPS draws a balanced load from the three-phase mains and delivers one single-phase output. Use it when every protected load is single-phase, such as racks of servers, network equipment or a security control room. You no longer need to balance loads downstream.

There is a catch with 3/1. All the output current flows on one phase conductor and the neutral. A 20 kVA output at 230 V carries about 87 A (20,000 ÷ 230), so output cables, breakers and distribution must be sized for that current.

**When each configuration fits**

| Point | 3/3 | 3/1 |
| --- | --- | --- |
| Typical loads | Three-phase machines, distribution boards, mixed loads | Single-phase IT, telecom, security systems |
| Phase balancing | Needed for single-phase loads downstream | Not needed at the output |
| Output current | Shared across three phases | All on one phase and the neutral |
| Output cabling | Smaller conductors per phase | Larger conductors for the full current |

## 400 V systems, phase balancing and the neutral

In a 3/3 system the UPS rating is shared across the three phases. A 30 kVA three-phase UPS gives roughly 10 kVA per phase. If one phase carries 12 kVA of single-phase load, that phase is overloaded, even though the total is well under 30 kVA.

**Phase balancing** means spreading single-phase circuits so each phase carries a similar load. Recheck it whenever equipment is added or moved. Some UPS designs accept 100% unbalanced load: one phase can be fully loaded while another is empty. That gives flexibility, but each phase still has its own limit.

The **neutral** is the return conductor shared by the three phases. With a balanced linear load its current is close to zero. With unbalance, it carries the difference. With single-phase IT loads, which draw non-linear current, third-harmonic currents add up in the neutral instead of cancelling. Neutral current can then approach or exceed the phase current, so size the neutral at least as large as the phase conductors and follow IEC 60364 and local rules.

## How to calculate the power of a three-phase UPS

For a balanced three-phase load, the formulas are:

- **Apparent power (VA) = √3 × line voltage × current**
- **Active power (W) = √3 × line voltage × current × power factor (PF)**

Apparent power, in kVA, is what the cables and the UPS must carry. Active power, in kW, is the real work done. The power factor is the ratio between them, between 0 and 1. A UPS rated at output power factor 1 delivers as many kW as kVA.

### Worked example from measured currents

An electrician clamps the feeder of a server room at 400 V during peak hours and reads **L1 = 42 A, L2 = 38 A, L3 = 35 A**. The IT loads have a power factor of about 0.9.

1. **Average current:** (42 + 38 + 35) ÷ 3 = 38.3 A.
2. **Total apparent power:** √3 × 400 × 38.3 ≈ 1.732 × 400 × 38.3 ≈ 26,500 VA, or 26.5 kVA.
3. **Active power:** 26.5 kVA × 0.9 ≈ 23.9 kW.
4. **Busiest phase:** 230 V × 42 A ≈ 9.7 kVA.
5. **Add a margin** of about 20-25% for growth and inrush: 26.5 × 1.25 ≈ 33 kVA total, and 9.7 × 1.25 ≈ 12.1 kVA on L1.
6. **Check per phase:** a 30 kVA UPS gives about 10 kVA per phase. That covers today's L1 but not the margin. A 40 kVA UPS gives about 13.3 kVA per phase and covers both the total and the busiest phase.

The alternative is to rebalance. Moving about 4 A of load from L1 to L3 brings every phase close to 38 A. The busiest phase plus margin then falls to about 11 kVA, still just over the 10 kVA per phase of a 30 kVA unit, so 40 kVA remains the safer choice. At output power factor 1, a 40 kVA UPS also delivers 40 kW, well above the 23.9 kW needed. For a step-by-step method from a device list, see our [UPS sizing guide](https://www.aecups.com/en/blog/ups-sizing/).

## Typical three-phase ratings and what fits where

Whether a site needs three-phase at all is the subject of our guide to [single-phase vs three-phase UPS](https://www.aecups.com/en/blog/single-vs-three-phase-ups/). Once it does, three-phase UPS fall into broad, overlapping bands.

- **10-40 kVA:** small server rooms, offices, retail, labs and machine control. Compact tower or rack units, often with 3/1 as an option.
- **60-200 kVA:** data rooms, hospital departments, industrial lines and building services. Floor-standing cabinets, often paralleled.
- **200 kVA and above:** data centres and large critical buildings. Usually modular systems that grow in power modules and run in parallel into the MW range.

## Design options: transformer, parallel and modular

### Transformerless or isolation transformer?

A **transformerless** UPS uses power electronics only. An **isolation-transformer** UPS adds a transformer at the output. The transformer gives **galvanic isolation**: there is no direct metallic path between input and output.

**Transformerless vs isolation-transformer three-phase UPS**

| Point | Transformerless | With isolation transformer |
| --- | --- | --- |
| Size and weight | Smaller and lighter | Larger and heavier |
| Efficiency | Generally higher | Somewhat lower, because of transformer losses |
| Galvanic isolation | No | Yes, between input and output |
| Neutral and earthing | Neutral passes through from the input | Can provide a locally derived neutral |
| Best fit | Offices, IT rooms, data centres | Industrial sites, harsh grids, loads that need isolation |

### Parallel and modular three-phase UPS systems

Two or more UPS in **parallel** share the load on a common output. Paralleling serves two purposes. **Capacity:** units add up to a larger total. **Redundancy:** with N+1, one unit more than the load needs, any single unit can fail or be serviced while the rest carry the load.

A **modular UPS** puts the parallel system inside one cabinet. Hot-swappable power modules slide in as the load grows and can be replaced without switching off the load. See our guide to [modular UPS systems](https://www.aecups.com/en/blog/modular-ups/) to decide whether this suits your site.

## Installation checklist for a three-phase UPS

1. **Input protection:** size the input breaker for the maximum input current, including battery recharge. Where the UPS has separate rectifier and bypass inputs, protect each one, and check selectivity with downstream breakers.
2. **Phase rotation:** confirm the phase sequence on the rectifier and bypass inputs before start-up.
3. **Cabling:** size phases and neutral for the real current, with a full-size or larger neutral for IT loads. On 3/1, size the output for the whole single-phase current.
4. **Maintenance bypass:** fit an external maintenance bypass so the UPS can be isolated for service while the load stays powered from the mains.
5. **Ventilation:** respect the operating temperature range and the clearances in the manual, and remove the heat the UPS gives off.
6. **Batteries:** plan the battery cabinet, its DC protection and its cabling. VRLA batteries last longest at 20-25 °C; heat shortens their life a lot.
7. **EMC and site:** many three-phase UPS are EMC category C3 under [IEC 62040-2](https://webstore.iec.ch/en/publication/33696), meant for commercial and industrial sites, not residential ones without extra measures.
8. **Monitoring:** connect SNMP, Modbus or dry contacts to your building or network management, and test the emergency power off (EPO).

## Common mistakes

- **Sizing on the total only.** A 30 kVA UPS with 12 kVA on one phase is overloaded. Always check the busiest phase.
- **Undersizing the neutral.** Harmonic currents from IT loads can make the neutral the hottest conductor.
- **Forgetting the 3/1 output current.** The single-phase output carries about three times the current of each input phase.
- **Mixing up kVA and kW.** A UPS rated 0.9 power factor delivers 90 kW per 100 kVA. Compare kW with kW.
- **Counting parallel units as redundant** when the load needs all of them. N+1 needs one spare unit's worth of capacity.
- **Ignoring heat.** A hot UPS room shortens battery life and can derate the UPS.

## How AEC's three-phase UPS ranges fit

AEC's [three-phase UPS range](https://www.aecups.com/en/products/three-phase-ups/) runs from 10 kVA to the megawatt range. All the ranges below are online double conversion.

- **[IST9](https://www.aecups.com/en/products/ist9/), 10-40 kVA:** a 19-inch, 3U unit for rack or tower. It runs 3/3 or 3/1, and 1/1 up to 20 kVA. Output power factor 1, up to 96% efficiency and 99% in ECO mode.
- **[IST7 10-40 kVA](https://www.aecups.com/en/products/ist7-10-40/):** one model for 3/3, 3/1 or, on 10-20 kVA, 1/1. Output power factor 1 (settable to 0.9), up to 96% efficiency, a full-power input window of 176-280 V phase, and up to 4 units in parallel with the optional kit. Battery voltage is set on site.
- **[IST7 60-200 kVA](https://www.aecups.com/en/products/ist7-60-200/):** three-phase 400 V in two cabinet sizes, 60-120 kVA and 160-200 kVA. Up to 96.5% efficiency, input THDi ≤ 3%, 100% unbalanced load, and up to 8 units in parallel for 1.6 MW with N+X redundancy. Selected models are upgraded on site from the touch screen.
- **[IST7-T](https://www.aecups.com/en/products/ist7-t/), 100–200 kVA:** a built-in output isolation transformer on every model, an input range of ±25%, 0 ms transfer from mains to battery and 100% unbalanced load. Its kW rating is 90% of the kVA rating, for example 100 kVA / 90 kW.
- **[All-in-One](https://www.aecups.com/en/products/all-in-one/), 20 kVA:** an IST9 20 kVA rack UPS, distribution switches with maintenance bypass and 2 to 8 hot-swappable 50 Ah lithium modules, or four of 100 Ah, in one cabinet on castors, 3/3 or 3/1.
- **IST6 modular:** the IST6-120 grows from 30 to 120 kVA in 30 kVA modules, with a fifth slot for N+1. The IST6 200-500 uses 50 kVA modules, and the IST6 400-1200 uses 100 kVA modules up to 1.2 MW per cabinet and 9.6 MW with 8 units in parallel.

In the worked example above, a 40 kVA IST9 or IST7-40 would fit the server room. A site with heavy unbalance or a harsh grid would point to the IST7-T. Not sure which fits? [Send us your measured currents](https://www.aecups.com/en/contacts/#form) and we will help you size the system.

The [UPS finder](https://www.aecups.com/en/tools/ups-finder/) takes the supply (230 V or 400 V), the load in kVA and the battery, and gives the ranges and the rating that fit.

Questions

## Questions people ask

#### What is a 3 phase UPS?

A 3 phase UPS is an uninterruptible power supply fed from a three-phase 400 V supply. It keeps critical loads running through mains failures and disturbances, usually with online double conversion. It is the normal choice for loads above about 10-20 kVA.

#### What is the difference between a 3/3 and a 3/1 UPS?

A 3/3 UPS takes three phases in and delivers three phases out, for three-phase boards and machines. A 3/1 UPS takes three phases in and delivers one single-phase output, so single-phase loads need no phase balancing. On 3/1 the output cabling must carry the full single-phase current.

#### How do I calculate the size of a three-phase UPS?

Multiply √3 × line voltage × average phase current to get VA, then multiply by the power factor to get W. For example, √3 × 400 V × 38.3 A is about 26.5 kVA. Also check that the busiest phase stays within a third of the UPS rating, and add a margin of about 20-25%.

#### Why is the neutral important in a three-phase UPS system?

The neutral carries the difference between unbalanced phase currents. With IT loads, third-harmonic currents add up in the neutral, so its current can approach or exceed the phase current. Size it at least as large as the phase conductors.

#### When should I choose a UPS with an isolation transformer?

Choose one when the load or site needs galvanic isolation between input and output, for example on industrial sites or harsh grids. The transformer can also provide a locally derived neutral. Otherwise a transformerless UPS is smaller and generally more efficient.

Products

## Products in this guide

[All products](https://www.aecups.com/en/products/)

### IST9

VRLA

10–40 kVA

Online UPS, rack / tower, 10–40 kVA

Details

### IST7 10–40

VRLA

10–40 kVA

Online UPS, double conversion, 10–40 kVA

Details

### IST7 60–200

VRLA

60–200 kVA

Three-phase online UPS, double conversion, 60–200 kVA

Details

### IST7-T

VRLA

100–200 kVA

Online UPS with isolation transformer, 100–200 kVA

Details

Blog

## Keep reading

[All articles](https://www.aecups.com/en/blog/)

[**Single- or three-phase UPS: which does your site need?** Single-phase or three-phase UPS? Where the line falls in kVA and amps, what the supply and the loads decide, a 12 kW worked example and a checklist.](https://www.aecups.com/en/blog/single-vs-three-phase-ups/) [**UPS efficiency and ECO mode: losses and energy savings** UPS efficiency explained: how losses change with load, the P × (1/η − 1) formula with a worked example, ECO mode trade-offs and how to read datasheets.](https://www.aecups.com/en/blog/ups-efficiency-eco-mode/) [**Battery room ventilation to EN IEC 62485-2 for VRLA** The EN IEC 62485-2 air flow for a VRLA battery, term by term, worked out for every AEC BB4–BB8 cabinet, with the size of the openings.](https://www.aecups.com/en/blog/battery-room-ventilation/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.

[Contact us](https://www.aecups.com/en/contacts/#form) [+39 02 9415 8991](tel:+390294158991)