title: "Battery cabinets UPS questions and answers | AEC"
url: https://www.aecups.com/en/faq/battery-cabinets/
description: "28 questions about the AEC Battery cabinets: choosing the model, backup time, installation, communication and service, each with its answer and its page."
language: en
---

Questions and answers

# Battery cabinets: questions and answers

28 questions about the AEC Battery cabinets, from its range page and its 10 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

[Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/) [All questions](https://www.aecups.com/en/faq/)

## Choosing, sizing and ordering 8 questions

#### Which UPS does the BB1 go with?

The IST3 1 kVA tower, in the code IST3-1-6X9 (UPS plus BB1 with 6 × 12 V 9 Ah). Larger IST3 use the BB2 (2–3 kVA) or BB3 (6–10 kVA).

Answered on [BB1](https://www.aecups.com/en/products/battery-cabinets/bb1/)

#### Does the BB2 fit both IST3 2 kVA and 3 kVA?

Yes: the catalogue gives the codes IST3-2-12X9 and IST3-3-12X9, each UPS with a BB2 and 12 × 12 V 9 Ah. AEC wires the strings to the voltage of the UPS.

Answered on [BB2](https://www.aecups.com/en/products/battery-cabinets/bb2/)

#### How many BB3 can one IST3 take?

The catalogue says more BB3 per UPS for longer backup without a fixed limit; AEC sets the number on the load and backup time. Each holds up to 32 × 12 V 9 Ah.

Answered on [BB3](https://www.aecups.com/en/products/battery-cabinets/bb3/)

#### Which UPS can use a BB5?

IST7 from 10 to 60 kVA (codes BB5-10k to BB5-60k) and the IST3 10 kVA with 100 × 9 Ah. With 24 Ah batteries the catalogue lists 10–20 kVA for 30–34 blocks and 10–40 kVA for 36–40; with 40 Ah, 10 to 60 kVA.

Answered on [BB5](https://www.aecups.com/en/products/battery-cabinets/bb5/)

#### Which UPS can use a BB6?

IST7 of 10, 20, 30, 40, 60, 80, 100 and 120 kVA, with codes BB6-10k to BB6-120k that set the fuses (50 to 250 A) and cables for the UPS power.

Answered on [BB6](https://www.aecups.com/en/products/battery-cabinets/bb6/)

#### Which UPS can a BB8 serve?

IST7 from 10 to 200 kVA (codes BB8-10k to BB8-200k): 40 × 80 Ah for 10–160 kVA, 60 × 80 / 100 Ah for 10–200 kVA, 64 × 80 / 100 Ah for 60–200 kVA.

Answered on [BB8](https://www.aecups.com/en/products/battery-cabinets/bb8/)

#### How many BBJ can one IST3-J take?

Up to three BBJ per IST3-J 1–3 kVA, each 2U with up to 8 × 12 V 9 Ah. For the 6–10 kVA, use the 3U BBJ2.

Answered on [BBJ](https://www.aecups.com/en/products/battery-cabinets/bbj/)

#### How many BBJ2 can an IST9 20 kVA take?

2, 4, 6, 8 or 10 cabinets, that is 32, 64, 96, 128 or 160 × 12 V 9 Ah (codes IST9-20-\[n\]X9). A DC battery switch goes between battery and UPS.

Answered on [BBJ2](https://www.aecups.com/en/products/battery-cabinets/bbj2/)

## Backup time and batteries 7 questions

#### Which batteries go in the BB1?

OZ Power 12 V 9 Ah AGM blocks, 151 × 65 × 94 mm and 2.3 kg each, with a design life of 6–8 years in float at 25 °C. Use the same model, capacity and batch across the whole string.

Answered on [BB1](https://www.aecups.com/en/products/battery-cabinets/bb1/)

#### How long do the batteries in a BB2 last?

The IST3 catalogue gives a typical battery life of 3–5 years, depending on temperature and use; the OZ Power 9 Ah block is designed for 6–8 years in float at 25 °C. Above 25 °C life shortens quickly.

Answered on [BB2](https://www.aecups.com/en/products/battery-cabinets/bb2/)

#### Can a BB4 be added to an IST7 with internal batteries?

Yes, that is its purpose: the IST7 10–40 kVA S keeps its internal string and the BB4 adds a second string of 40 × 12 V 9 Ah (e.g. IST7-20-80X9). Choose the code for the UPS power: BB4-10k, -20k or -40k.

Answered on [BB4](https://www.aecups.com/en/products/battery-cabinets/bb4/)

#### Which batteries go in the BB4?

OZ Power 12 V 9 Ah AGM blocks, up to 20 per layer on four layers, 80 in total. Batteries of one string must be the same type, model and manufacturer.

Answered on [BB4](https://www.aecups.com/en/products/battery-cabinets/bb4/)

#### Why does the BB8 hold two strings?

Two identical strings in parallel halve the power each battery delivers, so the same blocks give longer backup; the catalogue's sizing method notes that BB8 cabinets hold two strings as standard.

Answered on [BB8](https://www.aecups.com/en/products/battery-cabinets/bb8/)

#### What charge current suits an IST3-J with BBJ cabinets?

The catalogue recommends 0.1–0.2 C of the battery capacity. The UPS gives 1 A by default and 2–8 A only with the optional 7 A charging module.

Answered on [BBJ](https://www.aecups.com/en/products/battery-cabinets/bbj/)

#### Which battery cabinet fits my AEC UPS?

BB1, BB2 and BB3 are tower cabinets for the IST3 1 / 2–3 / 6–10 kVA; BBJ (2U) and BBJ2 (3U) are rack cabinets for the IST3-J and IST9. For the IST7, BB4 and BB5 serve 10–40 kVA (BB5 up to 60 kW), BB6 up to 120 kW, and BB7 and BB8 up to 200 kW.

Answered on [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/)

## Installation, size and connections 11 questions

#### Battery cabinets: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

| Model | Size | Weight |
| --- | --- | --- |
| [BB1](https://www.aecups.com/en/products/battery-cabinets/bb1/) | 145 × 360 × 225 mm | 4 kg empty |
| [BB2](https://www.aecups.com/en/products/battery-cabinets/bb2/) | 190 × 400 × 330 mm | 6 kg empty |
| [BB3](https://www.aecups.com/en/products/battery-cabinets/bb3/) | 230 × 502 × 553 mm | 15 kg empty |
| [BB4](https://www.aecups.com/en/products/battery-cabinets/bb4/) | 250 × 756 × 880 mm | 58 kg empty |
| [BB5](https://www.aecups.com/en/products/battery-cabinets/bb5/) | 460 × 800 × 1400 mm | 110 kg empty |
| [BB6](https://www.aecups.com/en/products/battery-cabinets/bb6/) | 800 × 800 × 1400 mm | 140 kg empty |
| [BB7](https://www.aecups.com/en/products/battery-cabinets/bb7/) | 800 × 800 × 1900 mm | 160 kg empty |
| [BB8](https://www.aecups.com/en/products/battery-cabinets/bb8/) | 1400 × 800 × 1900 mm | 250 kg empty |
| [BBJ](https://www.aecups.com/en/products/battery-cabinets/bbj/) | 438 × 413 mm, 2U | 6 kg empty |
| [BBJ2](https://www.aecups.com/en/products/battery-cabinets/bbj2/) | 438 × 500 mm, 3U | 10 kg empty |

Size and weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

#### What DC breaker goes between a BB3 and an IST3-10?

The IST3 table gives a 100 A DC breaker and a 10 mm² battery cable for the 10 kVA (65 A maximum DC input on the long backup model), and 50 A with 6 mm² for the 6 kVA.

Answered on [BB3](https://www.aecups.com/en/products/battery-cabinets/bb3/)

#### How much ventilation does a BB5 need?

The catalogue's [EN IEC 62485-2](https://webstore.iec.ch/en/publication/7091) example for a BB5 with 40 × 40 Ah: 0.48 m³/h on float, 3.8 m³/h on boost charge, and natural ventilation openings of at least 108 cm² each for inlet and outlet.

Answered on [BB5](https://www.aecups.com/en/products/battery-cabinets/bb5/)

#### What does a full BB6 weigh?

660 kg with 30 × 60 Ah, 695 kg with 32, 730 kg with 34 and 760 kg with 36, on an 800 × 800 mm footprint. Check the floor: 1188 kg/m² with 36 × 60 Ah.

Answered on [BB6](https://www.aecups.com/en/products/battery-cabinets/bb6/)

#### What floor load does a BB7 put on the slab?

With 36 × 12 V 100 Ah the catalogue gives 1992 kg/m², 1275 kg on 800 × 800 mm. With 80 Ah batteries it weighs 870 to 1005 kg.

Answered on [BB7](https://www.aecups.com/en/products/battery-cabinets/bb7/)

#### Which cable does a BB7-120k need to the UPS?

The catalogue's example: fuses F1/F2 250 A NH1, X1 → UPS cables of at least 120 mm² copper and PE 60 mm², single-core, 70 °C PVC in air, with site derating and voltage drop ≤ 0.5%.

Answered on [BB7](https://www.aecups.com/en/products/battery-cabinets/bb7/)

#### Where does the BBJ2 go, above or below the UPS?

Always below: battery cabinets are the heavy units of the rack. On the IST9 the optional distribution module goes above the UPS and the battery box below it.

Answered on [BBJ2](https://www.aecups.com/en/products/battery-cabinets/bbj2/)

#### Which batteries and how many go in each floor-standing cabinet?

All cabinets use 12 V VRLA AGM batteries. BB5 takes 30–40 × 24 or 40 Ah (or 100–120 × 9 Ah), BB6 30–40 × 60 Ah, BB7 28–36 × 60, 80 or 100 Ah, and BB8 40, 60 or 64 × 80 or 100 Ah in two strings. With 40 batteries the three-pole string gives +240 V and −240 V around the neutral, 480 V in total.

Answered on [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/)

#### What are the cabinet dimensions and weights?

Empty, BB5 measures 460 × 800 × 1400 mm (110 kg), BB6 800 × 800 × 1400 mm (140 kg), BB7 800 × 800 × 1900 mm (160 kg) and BB8 1400 × 800 × 1900 mm (250 kg). With batteries the floor load reaches, for example, 1992 kg/m² for a BB7 with 36 × 100 Ah.

Answered on [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/)

#### What clearances and room conditions does a battery cabinet need?

Leave at least 600 mm free in front and 100 mm behind and at the sides, in an indoor, dry and clean room, never a sealed enclosure, with each cabinet earthed by its own PE conductor. 20–25 °C gives the best battery life (0–40 °C allowed): life halves about every 8 °C above 25 °C.

Answered on [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/)

#### How is the cabinet protected and isolated from the UPS?

A three-pole DC switch-disconnector Q1 with fuses on + and − (BB5 also on N) isolates the UPS terminals from the batteries when OFF. The cabinet code (model + UPS power, e.g. BB7-120k) sets the fuse rating, from 50 A NH00 to 400 A NH2, and the cable sections.

Answered on [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/)

## Warranty, service and maintenance 2 questions

#### What warranty do the battery cabinets have?

The cabinet has a 3-year warranty; VRLA batteries have 1 year for 9 Ah blocks and 2 years for larger blocks. Cabinets are RAL 9005 painted steel, IP20 as standard, IP21 to IP44 on request.

Answered on [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/)

#### What maintenance do the battery cabinets need?

Monthly, a visual check of cases, leaks, corrosion, ventilation and room temperature; every 6 months, the float voltage of every battery; every 12 months, terminal torque with Q1 OFF and dust cleaning. Every 3–5 years, a capacity test or replacement.

Answered on [Battery cabinets](https://www.aecups.com/en/products/battery-cabinets/)

## By range

## Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.