title: "IST3-J UPS questions and answers | AEC"
url: https://www.aecups.com/en/faq/ist3-j/
description: "20 questions about the AEC IST3-J: choosing the model, backup time, installation, communication and service, each with its answer and its page."
language: en
---

Questions and answers

# IST3-J: questions and answers

20 questions about the AEC IST3-J, from its range page and its 5 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

[IST3-J](https://www.aecups.com/en/products/ist3-j/) [All questions](https://www.aecups.com/en/faq/)

## Choosing, sizing and ordering 5 questions

#### Can IST3-J units run in parallel?

Only the 10 kVA /B version can be used in parallel, through its parallel port. The other models work as single units.

Answered on [IST3-J](https://www.aecups.com/en/products/ist3-j/)

#### Can two IST3-J 10 kVA run in parallel?

Yes, with the 10 kVA /B parallel version, which has its own parallel port on the rear panel. The 6 kVA and the 1–3 kVA models have no parallel version.

Answered on [IST3-J 10 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-10k/)

#### How many BBJ2 cabinets can the IST3-J 10 kVA take?

One to eight, that is 16 to 128 batteries of 12 V 9 Ah (codes IST3J-6/10-\[n\]X9). Each BBJ2 is 3U, 438 × 500 mm and 10 kg empty, and goes below the UPS in the rack.

Answered on [IST3-J 10 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-10k/)

#### IST3-J: what is the ordering code of each model?

As the EMEA 2026 catalogue lists them:

| Model | Catalogue code |
| --- | --- |
| [IST3-J 1 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-1k/) | IST3J-1-3X9 |
| [IST3-J 2 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-2k/) | IST3J-2-4X9 |
| [IST3-J 3 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-3k/) | IST3J-3-6X9 |
| [IST3-J 6 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-6k/) | IST3J-6, IST3J-6/10-\[n\]X9 |
| [IST3-J 10 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-10k/) | IST3J-10, IST3J-6/10-\[n\]X9 |

AEC gives the full code, batteries included, from the load and the backup time.

Each model's own page, linked in the table, gives its full answer and data.

#### What are the input limits of the IST3-J 1 kVA?

176–295 V above 75% load, 154–176 V at 50–75% and 120–154 V below 50%: at light load the battery is not touched down to 120 V. The maximum input current is 6 A, on a 10 A breaker.

Answered on [IST3-J 1 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-1k/)

## Backup time and batteries 5 questions

#### What backup time does the IST3-J offer?

The 1–3 kVA standard models give 3 minutes at full load with internal batteries, extended with BBJ (2U, up to 8 × 12 V 9 Ah) or BBJ2 (3U, up to 16 × 12 V 9 Ah) rack cabinets. The 6 and 10 kVA are long backup models with no internal batteries: an external string of 192 V by default (12–20 × 12 V settable) sets the backup time, with 1 to 8 BBJ2 cabinets.

Answered on [IST3-J](https://www.aecups.com/en/products/ist3-j/)

#### IST3-J: how long does each model run on battery?

Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):

| Model | Full load | Backup at full load | At half load | For example | Its backup |
| --- | --- | --- | --- | --- | --- |
| [IST3-J 1 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-1k/) | 1 kW | 4 to 53 minutes | 15 to 131 minutes | 3 × 12 V 9 Ah (IST3J-1-3X9) | 4 min at 100%, 15 at 50% |
| [IST3-J 2 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-2k/) | 2 kW | 2 to 41 minutes | 8 to 101 minutes | 4 × 12 V 9 Ah (IST3J-2-4X9) | 2 min at 100%, 8 at 50% |
| [IST3-J 3 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-3k/) | 3 kW | 2 to 30 minutes | 8 to 78 minutes | 6 × 12 V 9 Ah (IST3J-3-6X9) | 2 min at 100%, 8 at 50% |
| [IST3-J 6 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-6k/) | 6 kW | 4 to 86 minutes | 13 to 218 minutes | 16 × 12 V 9 Ah (IST3J-6-16X9) | 4 min at 100%, 13 at 50% |
| [IST3-J 10 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-10k/) | 10 kW | 2 to 45 minutes | 5 to 108 minutes | 16 × 12 V 9 Ah (IST3J-10-16X9) | 2 min at 100%, 5 at 50% |

For other loads and batteries use the backup-time tool.

Each model's own page, linked in the table, gives its full answer and data.

#### How long does the IST3-J 3 kVA run on battery?

2 minutes at full load and 8 at half load on its six internal 12 V 9 Ah batteries, in AEC's data (the catalogue prints 3 minutes). Battery boxes or BBJ cabinets extend it: the codes IST3J-3-\[n\]X9 give the total number of 9 Ah blocks, and AEC sizes the number for your load.

Answered on [IST3-J 3 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-3k/)

#### Can the IST3-J 3 kVA batteries be changed with the load on?

Yes: on 1–3 kVA the battery packs of the UPS and of the battery box are hot-pluggable from the front, after removing the plastic panel and the battery plate. Use packs of the same capacity, model and make.

Answered on [IST3-J 3 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-3k/)

#### Does the IST3-J 6 kVA have internal batteries?

No. It is a long backup model (L): the battery is external, 192 V by default, in one to eight BBJ2 rack cabinets of 16 × 12 V 9 Ah each. The backup time is set by the battery you choose.

Answered on [IST3-J 6 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-6k/)

## Installation, size and connections 8 questions

#### Can the IST3-J be mounted in a rack and as a tower?

Yes for the 1–3 kVA: every model from 1 to 10 kVA is 19-inch and 2U high, and the 1–3 kVA models can also stand as a tower: the LCD reading is set to RCK (rack, default) or TWR (tower) from the panel. The battery box always mounts below the UPS.

Answered on [IST3-J](https://www.aecups.com/en/products/ist3-j/)

#### What do the programmable outlets do?

On 1–3 kVA, the optional programmable outlets switch off non-critical loads after a time limit of 0–999 minutes on battery, set from the PC (default 999). The general outlets keep the critical loads running, so they get more backup time.

Answered on [IST3-J](https://www.aecups.com/en/products/ist3-j/)

#### What are the IST3-J dimensions, weights and outlets?

The 1 kVA measures 438 × 423 × 86 mm (14 kg) with 8 × IEC C13 outlets. The 2–3 kVA measure 438 × 572 × 86 mm (20 / 26 kg) with 8 × C13 + 1 × C19; the 6–10 kVA measure 438 × 500 × 86 mm (10.6 / 12.2 kg) with 2 × C13 and a wire terminal. On 1–3 kVA leave at least 300–500 mm around the UPS and 500 mm on top.

Answered on [IST3-J](https://www.aecups.com/en/products/ist3-j/)

#### IST3-J: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

| Model | Size | Weight |
| --- | --- | --- |
| [IST3-J 1 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-1k/) | 438 × 423 × 86 mm | 14 kg |
| [IST3-J 2 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-2k/) | 438 × 572 × 86 mm | 20 kg |
| [IST3-J 3 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-3k/) | 438 × 572 × 86 mm | 26 kg |
| [IST3-J 6 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-6k/)1 | 438 × 500 × 86 mm | 10.6 kg |
| [IST3-J 10 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-10k/)1 | 438 × 500 × 86 mm | 12.2 kg |

Unless marked: size from AEC's CAD drawing, weight from the EMEA 2026 catalogue.

1 Size and weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

#### Rack or tower: how is the IST3-J 1 kVA installed?

In a 19-inch rack with two angle irons (default reading RCK), or upright on its support bases with the display set to TWR from the panel. With a battery box, two 1U joint bases are added per box.

Answered on [IST3-J 1 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-1k/)

#### How much rack space do the IST3-J 2 kVA and its batteries take?

2U for the UPS (438 × 572 × 86 mm, 20 kg) and 2U for each battery box of the same footprint, which holds 2 × (4 × 12 V 9 Ah) and weighs 29 kg. The catalogue's example rack is the UPS with two battery boxes below it.

Answered on [IST3-J 2 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-2k/)

#### What breaker and cable does the IST3-J 2 kVA need?

12 A maximum input current, a 20 A breaker without leakage protection and a 1.5 mm² AC cable for about 5 m; 6 mm² for the external battery, rated 42.6 A.

Answered on [IST3-J 2 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-2k/)

#### What breaker does the IST3-J 6 kVA need?

The catalogue recommends a 50 A upstream input breaker (36 A maximum input current) and a 50 A DC breaker for the battery, which draws up to 39 A. Size the cables on these currents.

Answered on [IST3-J 6 kVA](https://www.aecups.com/en/products/ist3-j/ist3j-6k/)

## Communication and monitoring 1 question

#### Which communication options does the IST3-J have?

RS232 with power management software is standard, plus USB on 1–3 kVA and an EPO input. The intelligent slot takes an optional SNMP card (RJ45 network port and COM1 for a temperature and humidity module), an RS485 and dry-contact card, or a protocol transfer card (1–3 kVA).

Answered on [IST3-J](https://www.aecups.com/en/products/ist3-j/)

## Warranty, service and maintenance 1 question

#### Can the batteries be replaced without switching off?

Yes, on the 1–3 kVA: the battery packs of the UPS and of the battery box are hot-pluggable and replaced from the front, using the same capacity, model and make. The charging current is 1 A by default, settable to 2–8 A with the 7 A charging module.

Answered on [IST3-J](https://www.aecups.com/en/products/ist3-j/)

## By range

## Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.

[Contact AEC](https://www.aecups.com/en/contacts/#form) [Blog](https://www.aecups.com/en/blog/)