---
title: "IST6 200–500 UPS questions and answers | AEC"
url: https://www.aecups.com/en/faq/ist6-200-500/
description: "18 questions about the AEC IST6 200–500: choosing the model, backup time, installation, communication and service, each with its answer and its page."
language: en
---

Questions and answers

# IST6 200–500: questions and answers

18 questions about the AEC IST6 200–500, from its range page and its 4 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

[IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/) [All questions](https://www.aecups.com/en/faq/)

## Choosing, sizing and ordering 8 questions

#### Which IST6 cabinet sizes are available from 200 to 500 kVA?

Four cabinets with 4, 6, 8 or 10 power modules of 50 kVA. The 200 and 300 kVA are in a single column of 607 × 860 × 2000 mm (224 / 236 kg without modules), 400 and 500 kVA in a double column of 1203 × 864 × 2000 mm (459 / 506 kg). Each 3U power module weighs 39 kg.

Answered on [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)

#### How many UPS can be connected in parallel?

Up to eight UPS, with N+X redundancy between UPS and load sharing within 5%. BSC dual-bus and three-bus layouts are supported, and a 7 m parallel cable is supplied with each UPS.

Answered on [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)

#### Can modules be replaced with the load running?

Yes: the power modules and the five cards of the system control box are hot-swappable, and two control cards back each other up. A module is unlocked, pulled out and replaced while the others keep supplying the load; wait at least 15 minutes before opening a removed module.

Answered on [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)

#### How do I get N+1 with an IST6-200?

Run up to 150 kVA on three modules and fit the fourth as the redundant one, or parallel a second UPS (up to eight in a system, N+X between UPS). Redundancy sleep lets spare modules rest at light load.

Answered on [IST6-200, 4 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-200k-4x50/)

#### IST6 200–500: what is the ordering code of each model?

As the EMEA 2026 catalogue lists them:

| Model | Catalogue code |
| --- | --- |
| [IST6-200, 4 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-200k-4x50/) | IST6-200 |
| [IST6-300, 6 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-300k-6x50/) | IST6-300 |
| [IST6-400, 8 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-400k-8x50/) | IST6-400 |
| [IST6-500, 10 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-500k-10x50/) | IST6-500 |

AEC gives the full code, batteries included, from the load and the backup time.

Each model's own page, linked in the table, gives its full answer and data.

#### IST6-400 with 50 kVA modules or IST6 400 kVA with 100 kVA modules?

The IST6-400 (8 × 50 kVA, 1203 mm wide) gives finer steps and cheaper redundancy. The 400 kVA cabinet of the 400–1200 range (4 × 100 kVA, 801 mm wide) takes less floor, reaches up to 98.1% efficiency with PLUS modules and keeps the same module up to 1.2 MW.

Answered on [IST6-400, 8 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-400k-8x50/)

#### Is there an ordering code for the IST6 500 kVA?

Yes: IST6-500 is the 500 kVA cabinet for up to ten 50 kVA modules, without modules; the power modules are IST6-50-J. Ask AEC with the load and backup time and AEC sends the configuration.

Answered on [IST6-500, 10 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-500k-10x50/)

#### What protects the load if a downstream circuit shorts?

The 50 kVA modules supply a high short-circuit current for a set time, 20 to 200 ms, so the breaker of the faulty circuit trips while the other loads keep running. Backfeed protection opens the backfeed device if the static bypass fails.

Answered on [IST6-500, 10 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-500k-10x50/)

## Backup time and batteries 2 questions

#### How many batteries does the IST6 200–500 kVA need?

The lead-acid nominal is ±240 V DC with 40 × 12 V blocks; 30 to 50 blocks are accepted, with an output factor of 0.75 at 30 blocks, 0.8 at 32–34, 0.9 at 36–38 and 1 from 40. Lithium runs at ±256 V nominal with 120–200 cells (standard 160) and the BMS card; charging current is up to 30 A per module.

Answered on [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)

#### IST6 200–500: how long does each model run on battery?

Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):

| Model | Full load | Backup at full load | At half load | For example | Its backup |
| --- | --- | --- | --- | --- | --- |
| [IST6-200, 4 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-200k-4x50/) | 200 kW | 3 to 156 minutes | 8 to 311 minutes | 40 × 12 V 100 Ah (IST6-200-40X100) | 3 min at 100%, 8 at 50% |
| [IST6-300, 6 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-300k-6x50/) | 300 kW | 3 to 104 minutes | 8 to 207 minutes | 60 × 12 V 100 Ah · 2 × 30 (IST6-300-60X100) | 3 min at 100%, 8 at 50% |
| [IST6-400, 8 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-400k-8x50/) | 400 kW | 5 to 78 minutes | 16 to 156 minutes | 120 × 12 V 100 Ah · 4 × 30 (IST6-400-120X100) | 5 min at 100%, 16 at 50% |

For other loads and batteries use the backup-time tool.

Each model's own page, linked in the table, gives its full answer and data.

## Lithium batteries 1 question

#### Can the IST6-400 run on lithium batteries?

Yes, with the BMS expansion card: lithium at ±256 V DC nominal, 120 to 200 cells (standard 160). Lead-acid runs at ±240 V nominal with 30 to 50 blocks, full output from 40 blocks.

Answered on [IST6-400, 8 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-400k-8x50/)

## Installation, size and connections 4 questions

#### What installation clearances and cooling does it need?

Leave at least 800 mm at the front, 500 mm at the rear and 500 mm on top, with front-to-rear airflow of 2420 m³/h (200 kVA) up to 6050 m³/h (500 kVA). It works at 0 … 40 °C up to 2000 m on TN-S, TN-C, TN-C-S or TT systems; upstream RCD breakers are not recommended.

Answered on [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)

#### What breaker and cables does an IST6-200 need?

A 400 A 3P mains breaker. Mains 345 A on 2 × (4 × 120) mm², bypass and output 303 A on 2 × (4 × 120) mm², battery 434 A (40 blocks) on 2 × (3 × 120) mm², copper at 90 °C, breakers valid for short-circuit currents below 65 kA.

Answered on [IST6-200, 4 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-200k-4x50/)

#### IST6 200–500: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

| Model | Size | Weight |
| --- | --- | --- |
| [IST6-200, 4 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-200k-4x50/) | 607 × 860 × 2000 mm | 224 kg without modules |
| [IST6-300, 6 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-300k-6x50/) | 607 × 860 × 2000 mm | 236 kg without modules |
| [IST6-400, 8 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-400k-8x50/) | 1203 × 864 × 2000 mm | 459 kg without modules |
| [IST6-500, 10 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-500k-10x50/) | 1203 × 864 × 2000 mm | 506 kg without modules |

Size from AEC's CAD drawing, weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

#### What clearances does the IST6-300 need?

At least 800 mm in front, 500 mm behind and 500 mm above, airflow front to rear, at 0–40 °C up to 2000 m. Handling by forklift from the short side, or two forklifts from the front.

Answered on [IST6-300, 6 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-300k-6x50/)

## Communication and monitoring 1 question

#### Which communication options are available?

Modbus, RS232, RS485, two EPO inputs and 4 dry-contact inputs / 3 outputs with programmable functions are standard. Options: SNMP card (Ethernet, SNMP or Modbus), dry-contact expansion to 7 + 5 and a BMS card for lithium batteries.

Answered on [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)

## Efficiency and operation 2 questions

#### How efficient is it, and what does THDi ≤ 1.5% mean in practice?

Efficiency reaches 98.1% in double conversion, with ECO and W-ECO modes and redundancy sleep. Input power factor of 0.99 or above and THDi ≤ 1.5% at full load allow smaller upstream cables, transformers and generators.

Answered on [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/)

#### How much energy does an IST6-300 lose in a year?

At 80% load (240 kW), 8,760 hours, the losses at 98.1% efficiency are about 4.65 kW, about 40,700 kWh a year, cooling excluded. Each additional point of efficiency saves about 2.5 kW, about 22,100 kWh a year.

Answered on [IST6-300, 6 × 50 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-300k-6x50/)

## By range

## Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.

[Contact AEC](https://www.aecups.com/en/contacts/#form) [Blog](https://www.aecups.com/en/blog/)
