## Choosing, sizing and ordering 6 questions

#### Can an IST7 60–200 kVA be upgraded later?

Yes, selected models: the IST7-80 is upgraded to 100 or 120 kVA, the IST7-100 to 120 kVA and the IST7-160 to 200 kVA, by setting the capacity from the display. Hardware and footprint stay the same.

Answered on [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)

#### How many IST7 units can run in parallel?

Up to 8 units, for capacity or N+X redundancy, reaching 1.6 MW with 8 × IST7-200. BSC synchronisation supports dual-bus architectures, current sharing between units is within 5%, and the units can share a common battery bank.

Answered on [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)

#### How much energy does the IST7-100 lose at full load?

At 100 kW, 24/7, the catalogue gives 3.6 kW of losses and 31,800 kWh a year in double conversion at 96.5%, and 1.0 kW and 8,850 kWh in ECO mode at 99%. Room cooling comes on top; the values are indicative.

Answered on [IST7-100](https://www.aecups.com/en/products/ist7-60-200/ist7-100k/)

#### IST7 60–200: what is the ordering code of each model?

As the EMEA 2026 catalogue lists them:

| Model | Catalogue code |
| --- | --- |
| [IST7-60](https://www.aecups.com/en/products/ist7-60-200/ist7-60k/) | IST7-60 |
| [IST7-80](https://www.aecups.com/en/products/ist7-60-200/ist7-80k/) | IST7-80 |
| [IST7-100](https://www.aecups.com/en/products/ist7-60-200/ist7-100k/) | IST7-100 |
| [IST7-120](https://www.aecups.com/en/products/ist7-60-200/ist7-120k/) | IST7-120 |
| [IST7-160](https://www.aecups.com/en/products/ist7-60-200/ist7-160k/) | IST7-160 |
| [IST7-200](https://www.aecups.com/en/products/ist7-60-200/ist7-200k/) | IST7-200 |

AEC gives the full code, batteries included, from the load and the backup time.

Each model's own page, linked in the table, gives its full answer and data.

#### How many IST7-200 can run in parallel?

Up to eight, for 1.6 MW, with parallel cables in a ring (N units, N cables) and addresses 1–8 set from the display. A parameter match page shows any setting that differs between units and copies it to all.

Answered on [IST7-200](https://www.aecups.com/en/products/ist7-60-200/ist7-200k/)

#### How is the IST7-80 upgraded to 100 or 120 kVA?

The rated capacity is set from the display at engineering level, on the same hardware: no new power unit and no new cabinet. AEC service configures the upgrade.

Answered on [IST7-80](https://www.aecups.com/en/products/ist7-60-200/ist7-80k/)

## Backup time and batteries 8 questions

#### Which batteries does the IST7 60–200 kVA use?

A string of 28–48 × 12 V blocks set on site, VRLA or lithium with the BMS card: default ±192 V (32 blocks) on IST7-60/80 and ±216 V (36 blocks) on IST7-100…200. The maximum charge current is 30 A on 60–120 kVA and 60 A on 160–200 kVA, and AEC BB5 to BB8 cabinets are ordered with the UPS in one code.

Answered on [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)

#### Can IST7-100 units share one battery?

Yes: the units of a parallel system can share a common battery bank, or each keep its own. Up to eight units run on one load bus with the parallel kit PAR-IST7-60/200, current sharing within 5%.

Answered on [IST7-100](https://www.aecups.com/en/products/ist7-60-200/ist7-100k/)

#### IST7 60–200: how long does each model run on battery?

Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):

| Model | Full load | Backup at full load | At half load | For example | Its backup |
| --- | --- | --- | --- | --- | --- |
| [IST7-60](https://www.aecups.com/en/products/ist7-60-200/ist7-60k/) | 60 kW | 2 to 98 minutes | 8 to 239 minutes | 30 × 12 V 40 Ah (IST7-60-30X40) | 2 min at 100%, 8 at 50% |
| [IST7-80](https://www.aecups.com/en/products/ist7-60-200/ist7-80k/) | 80 kW | 2 to 60 minutes | 8 to 167 minutes | 30 × 12 V 60 Ah (IST7-80-30X60) | 2 min at 100%, 8 at 50% |
| [IST7-100](https://www.aecups.com/en/products/ist7-60-200/ist7-100k/) | 100 kW | 2 to 50 minutes | 5 to 117 minutes | 30 × 12 V 60 Ah (IST7-100-30X60) | 2 min at 100%, 5 at 50% |
| [IST7-120](https://www.aecups.com/en/products/ist7-60-200/ist7-120k/) | 120 kW | 1 to 39 minutes | 4 to 98 minutes | 30 × 12 V 60 Ah (IST7-120-30X60) | 1 min at 100%, 4 at 50% |
| [IST7-160](https://www.aecups.com/en/products/ist7-60-200/ist7-160k/) | 160 kW | 2 to 26 minutes | 5 to 60 minutes | 30 × 12 V 80 Ah (IST7-160-30X80) | 2 min at 100%, 5 at 50% |
| [IST7-200](https://www.aecups.com/en/products/ist7-60-200/ist7-200k/) | 200 kW | 3 to 19 minutes | 8 to 50 minutes | 60 × 12 V 80 Ah · 2 × 30 (IST7-200-60X80) | 4 min at 100%, 10 at 50% |

For other loads and batteries use the backup-time tool.

Each model's own page, linked in the table, gives its full answer and data.

#### How heavy is an IST7-160 with its batteries?

The catalogue example IST7-160-64X100 weighs 294 kg for the UPS plus 2,215 kg for a BB8 with 64 × 12 V 100 Ah. A BB8 so loaded puts about 1,978 kg/m² on the floor: check the slab.

Answered on [IST7-160](https://www.aecups.com/en/products/ist7-60-200/ist7-160k/)

#### Which battery cabinets suit the IST7-160?

BB7 with 30–36 × 80 / 100 Ah, BB8 with 60 / 64 × 80 / 100 Ah, or two BB8 with 120 / 128 × 80 / 100 Ah. BB5 and BB6 are not listed for it.

Answered on [IST7-160](https://www.aecups.com/en/products/ist7-60-200/ist7-160k/)

#### Which batteries suit the IST7-200?

The catalogue lists BB8 with 60 / 64 × 80 / 100 Ah or two BB8 with 120 / 128 × 80 / 100 Ah, the string split at the neutral (+, N, −). Lithium cabinets are available on request with the BMS card.

Answered on [IST7-200](https://www.aecups.com/en/products/ist7-60-200/ist7-200k/)

#### Which battery cabinets suit the IST7-60?

BB5 with 30–38 × 40 Ah, BB6 with 30–36 × 60 Ah, BB7 with 30–36 × 80 / 100 Ah, BB8 with 60 / 64 × 80 / 100 Ah and two BB8 with 120 / 128 × 80 / 100 Ah. Lithium cabinets are available on request.

Answered on [IST7-60](https://www.aecups.com/en/products/ist7-60-200/ist7-60k/)

#### Which battery cabinets go with the IST7-80?

From BB6 (30–36 × 60 Ah) upwards: BB7 with 30–36 × 80 / 100 Ah, BB8 with 60 / 64 × 80 / 100 Ah, or two BB8. The BB5 is not listed for the 80–120 kVA.

Answered on [IST7-80](https://www.aecups.com/en/products/ist7-60-200/ist7-80k/)

## Installation, size and connections 3 questions

#### What are the dimensions, weights and clearances?

The 60–120 kVA cabinet measures 400 × 960 × 1193 mm (153–167 kg) with bottom cable entry; the 160–200 kVA cabinet 600 × 1000 × 1600 mm (294–296 kg) with top cable entry. Leave at least 800 mm at the front, rear and above: cooling air enters at the front and leaves at the rear.

Answered on [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)

#### IST7 60–200: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

| Model | Size | Weight |
| --- | --- | --- |
| [IST7-60](https://www.aecups.com/en/products/ist7-60-200/ist7-60k/) | 400 × 960 × 1193 mm | 153 kg |
| [IST7-80](https://www.aecups.com/en/products/ist7-60-200/ist7-80k/) | 400 × 960 × 1193 mm | 163 kg |
| [IST7-100](https://www.aecups.com/en/products/ist7-60-200/ist7-100k/) | 400 × 960 × 1193 mm | 165 kg |
| [IST7-120](https://www.aecups.com/en/products/ist7-60-200/ist7-120k/) | 400 × 960 × 1193 mm | 167 kg |
| [IST7-160](https://www.aecups.com/en/products/ist7-60-200/ist7-160k/) | 600 × 1000 × 1600 mm | 294 kg |
| [IST7-200](https://www.aecups.com/en/products/ist7-60-200/ist7-200k/) | 600 × 1000 × 1600 mm | 296 kg |

Size from AEC's CAD drawing, weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

#### How much space does the IST7-60 need?

The cabinet is 400 mm wide and 960 mm deep, with at least 800 mm free at the front, rear and above: air enters at the front and leaves at the rear. Cables come in from below; the unit is positioned on castors and then anchored to the floor.

Answered on [IST7-60](https://www.aecups.com/en/products/ist7-60-200/ist7-60k/)

## Communication and monitoring 2 questions

#### Which communication interfaces does it have?

RS485, Modbus RTU, RS232, EPO, USB and 4 dry-contact inputs / 3 outputs with assignable functions are standard. Options include an SNMP card with a temperature and humidity sensor port, dry-contact expansion (+3 inputs, +2 outputs) and a BMS card for lithium batteries.

Answered on [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)

#### IST7-120 or an upgraded IST7-80 / IST7-100?

All three end at 120 kVA in the same cabinet. Buy the IST7-120 when the load is already there; buy the IST7-80 or IST7-100 when it will grow, and raise the capacity from the display later.

Answered on [IST7-120](https://www.aecups.com/en/products/ist7-60-200/ist7-120k/)

## Efficiency and operation 2 questions

#### How efficient is the IST7 60–200 kVA?

Peak AC/AC efficiency is 96.5% in online double conversion and 99% in ECO mode, with output power factor 1 (kVA = kW). At a 100 kW load, AEC's indicative calculation gives 3.6 kW of losses (≈ € 6,350 per year) in double conversion against 1.0 kW (≈ € 1,770) in ECO.

Answered on [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)

#### What overload does the IST7-120 accept?

On the inverter: 105% continuous, 110% for 60 minutes, 125% for 10 minutes, then immediate protection above 125%. The static bypass carries 130% continuous, 150% for 5 minutes, 200% for 1 s and 300% for 100 ms.

Answered on [IST7-120](https://www.aecups.com/en/products/ist7-60-200/ist7-120k/)

## Warranty, service and maintenance 1 question

#### What warranty and service come with the IST7 60–200 kVA?

A 3-year warranty, extendable with a maintenance contract, and 24/7 technical assistance by phone and WhatsApp. The UPS stores up to 10,000 events and wave captures that are exported to USB for the service report.

Answered on [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/)