## Choosing, sizing and ordering 3 questions

#### What mains voltage variations can the IST7-T handle?

The input range is ±25%, with full load from −20% to +25% of rated voltage (320–500 V at 400 V rated). The IGBT rectifier keeps input power factor at 0.99 or above and THDi below 5%; it takes 3 wires + PE without neutral, while the bypass is 3 phases + N + PE.

Answered on [IST7-T](https://www.aecups.com/en/products/ist7-t/)

#### Which redundant architectures does the IST7-T support?

Parallel systems with an N+x redundancy alarm, series hot standby (UPS 2 feeds the bypass of UPS 1) and optional dual-bus systems synchronised through the LBS interface. Units in parallel can share one battery pack.

Answered on [IST7-T](https://www.aecups.com/en/products/ist7-t/)

#### Can two IST7T-120 feed a dual-bus system?

Yes. With the optional LBS interface two independent systems A and B are kept in phase and frequency, so dual-corded loads can be fed from both. Each side can be a single unit or a parallel system.

Answered on [IST7T-120](https://www.aecups.com/en/products/ist7-t/ist7t-120k/)

## Backup time and batteries 2 questions

#### Which batteries can the IST7-T use?

An external battery, chosen per site: 348–480 V DC (29–40 × 12 V blocks), 32 batteries by default. Lithium systems are supported, and with lithium the UPS can shift energy from off-peak to peak hours.

Answered on [IST7-T](https://www.aecups.com/en/products/ist7-t/)

#### What battery voltage does the IST7T-100 use?

348 to 480 V DC, 29 to 40 blocks of 12 V per string, 32 by default. With the optional battery logger (BMS link) the voltage, internal resistance and temperature of every cell appear on the UPS screen.

Answered on [IST7T-100](https://www.aecups.com/en/products/ist7-t/ist7t-100k/)

## Installation, size and connections 4 questions

#### What are the IST7-T ratings, dimensions and weights?

Three ratings: 100 kVA / 90 kW, 120 kVA / 108 kW and 200 kVA / 180 kW. Every model is a cabinet 1000 mm wide, 800 mm deep and 2000 mm high, weighing 720, 780 and 1280 kg (± 5%). Leave at least 700 mm free at the front and rear.

Answered on [IST7-T](https://www.aecups.com/en/products/ist7-t/)

#### IST7-T: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

| Model | Size | Weight |
| --- | --- | --- |
| [IST7T-100](https://www.aecups.com/en/products/ist7-t/ist7t-100k/) | 1000 × 800 × 2000 mm | 720 kg |
| [IST7T-120](https://www.aecups.com/en/products/ist7-t/ist7t-120k/) | 1000 × 800 × 2000 mm | 780 kg |
| [IST7T-200](https://www.aecups.com/en/products/ist7-t/ist7t-200k/) | 1000 × 800 × 2000 mm | 1280 kg |

Size and weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

#### What currents does the IST7T-120 draw?

216 A on the AC input and output and 333 A on the battery, with cables up to 2 × 150 mm² in the catalogue table. A bipolar disconnect switch is required on the external DC circuit.

Answered on [IST7T-120](https://www.aecups.com/en/products/ist7-t/ist7t-120k/)

#### What floor and space does the IST7T-200 need?

A concrete or non-flammable level floor for 1280 kg on 0.8 m², at least 700 mm free at front and rear, and front and rear vents kept clear. Units can be combined in a row.

Answered on [IST7T-200](https://www.aecups.com/en/products/ist7-t/ist7t-200k/)

## Communication and monitoring 1 question

#### Which communication interfaces does the IST7-T have?

RS232 / RS485 Modbus RTU and 8 output and 4 input configurable dry contacts are standard. Options include an SNMP card for remote monitoring and on / off, a BMS link for cell data, a parallel interface, LBS and a TCP/IP serial server.

Answered on [IST7-T](https://www.aecups.com/en/products/ist7-t/)

## Efficiency and operation 2 questions

#### Why choose a UPS with a built-in isolation transformer?

Every IST7-T has an output isolation transformer matched to the inverter, giving complete electrical isolation between input and output, with nothing external to add or size. It delivers full kVA at 100% non-linear load, avoids the inrush of an external transformer and improves short-circuit and inductive-load capability.

Answered on [IST7-T](https://www.aecups.com/en/products/ist7-t/)

#### Why not a transformerless UPS plus an external transformer at 200 kVA?

The IST7T-200's transformer is matched to the inverter: no external unit to size and install, and no excitation inrush on the inverter at start-up. It also gives full kVA at 100% non-linear load and 100% unbalanced load.

Answered on [IST7T-200](https://www.aecups.com/en/products/ist7-t/ist7t-200k/)

## Warranty, service and maintenance 2 questions

#### What warranty and service are included?

The IST7-T has a 3-year warranty, extendable with a maintenance contract, with 24/7 technical assistance by phone and WhatsApp. AEC engineers size, install, commission and maintain the system, and spare parts are stocked in 21+ countries.

Answered on [IST7-T](https://www.aecups.com/en/products/ist7-t/)

#### How is a 720 kg IST7T-100 moved into place?

By electric or hand forklift, kept upright and balanced, or hoisted from the four lifting eyes on top with the hook at least 1 m above the cabinet. Leave at least 700 mm free at front and rear for heat and service.

Answered on [IST7T-100](https://www.aecups.com/en/products/ist7-t/ist7t-100k/)

## By range

## Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.

[Contact AEC](https://www.aecups.com/en/contacts/#form) [Blog](https://www.aecups.com/en/blog/)