Three-phase UPS · 400 V

# All-in-One Lithium UPS in one cabinet, 20 kVA

Lithium Online double conversion

The AEC All-in-One puts an IST9 20 kVA online double-conversion UPS, its distribution switches with maintenance bypass and 2 to 8 hot-swappable 50 Ah LFP lithium modules, or four of 100 Ah, in one cabinet on castors. Three-phase, 3/3 or 3/1; cells rated for 5,000 cycles at 50% depth of discharge, 15 to 60 minutes at 20 kW and up to 200 minutes at 6 kW.

**1 cabinet** UPS, switches and lithium

**20 kVA** IST9 inside, 3/3 · 3/1

**10+ years** LFP cells, 5,000 cycles

**up to 200 min** at 6 kW, 8 × 50 Ah or 4 × 100 Ah

Datasheet Manuals and catalogues [Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20All-in-One%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/aio-20/v69/)

Drag to turn

In 3D

## Look around the All-in-One

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/aio-20/v69/)

Rendered from AEC's 3D model of the All-in-One 20 kVA. The full 3D view zooms in, opens the unit and names every part.

Hands on

## Open the All-in-One 20 kVA yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

[Every part in 3D](https://www.aecups.com/assets/models3d/aio-20/v69/)

Efficiency

## How efficient is the AEC All-in-One at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

**96** % 50% · Typical curve, derived from the datasheet efficiency of 96% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4% | Typical curve, derived from the datasheet efficiency of 96% (AEC method) | All-in-One 20 kVA | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | All-in-One 20 kVA |  |

EMEA 2026 catalogue figures: Online, double conversion up to 96% · ECO up to 99%.

Backup time

## Every load, every number of modules.

All-in-One backup minutes from the EMEA 2026 catalogue: load down the side, lithium modules across. Touch a cell.

With 4 × 50 Ah modules and a 20 kW load: 30 minutes of backup.

**All-in-One, 50 Ah modules: backup in minutes by load and number of modules**

| Load | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| --- | --- | --- | --- | --- | --- | --- | --- |
| 6 kW |  |  |  |  |  |  |  |
| 10 kW |  |  |  |  |  |  |  |
| 12 kW |  |  |  |  |  |  |  |
| 14 kW |  |  |  |  |  |  |  |
| 16 kW |  |  |  |  |  |  |  |
| 18 kW |  |  |  |  |  |  |  |
| 20 kW |  |  |  |  |  |  |  |

Fewer minutes More minutes

Catalogue reference values, to be confirmed by actual measurement; AEC sizes every system. –: configuration not possible (at least two 50 Ah modules; the 100 Ah version always has four). All-in-One 20 kVA, IST9 three-phase: the load never exceeds 20 kW.

The display

## The All-in-One display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page, or touch the screen as on the UPS.

UPS state

All-in-One · the real display

### Normal

Normal: the rectifier and the inverter carry the load at 230 V per phase, 50 Hz, and charge the lithium modules.

**Main pages**

What is what

## Inside the All-in-One, part by part.

Each number on the picture is named in the list.

### Front, door open

1. **The IST9's own display, with the UPS status and measurements** The touch screen on the door also shows the battery, down to the cell.
2. **IST9 3U rack UPS, online double conversion** 96% efficient, 99% in ECO, output power factor 1 (kVA = kW).
3. **Distribution switches** Input, output, bypass and battery on one panel, with the maintenance bypass, its cover watched by a door switch.
4. **Lithium modules** Lithium iron phosphate modules, hot-swappable, each with its BMU, DC/DC converter, switch and indicators.

### Distribution switches of the All-in-One three-phase cabinet

Distribution switches on one front panel, below the UPS. Only mains, bypass and output are wired on site: the lithium modules are already connected inside.

1. **Maintenance bypass** Three-phase systems. Remove its cover (a cover switch moves the UPS to bypass), close it, then open input, output and battery: the load runs on the maintenance bypass.
2. **Output breaker** To the load.
3. **Input breaker** The UPS mains supply.
4. **Bypass breaker** The static bypass supply.
5. **Battery breaker** Between the lithium modules and the UPS.

Overview

## Key facts

**Power range**: 20 kVA

**Input / output**: 3/3 · 3/1 · 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (IST9 20 kVA, 3/3 · 3/1)

**Efficiency**: up to 96% · 99% in ECO mode

**Communication**: RS232 · EPO · RS485 · options: SNMP, RS485 + dry contact

**Network card**: SNMP card (optional)

**Warranty**: 3 years on the UPS, 5 years on the lithium batteries

**Dimensions W × D × H**: 600 × 1000 × 1110 · 1000 mm

[Applications](https://www.aecups.com/en/applications/): IT rooms Offices & finance Communication Transport Security systems Education & public

Pictures

## The All-in-One in pictures

The photos and drawings of the EMEA 2026 catalogue: product views, displays, modules and connections. Tap a picture to enlarge it.

Models

## Which All-in-One fits your load?

Every rating has its own page: that model's technical data, ordering codes, batteries and the questions people ask.

[**All-in-One 20 kVA** 20 kVA The All-in-One 20 kVA is one cabinet with an IST9 20 kVA UPS, distribution and maintenance bypass switches, and 2–8 × 50 Ah or 4 × 100 Ah lithium modules. **600 × 1000 × 1110 mm**Size **232 kg with 2 × 50 Ah, up to 460 kg with 8 × 50 Ah**Weight See the model](https://www.aecups.com/en/products/all-in-one/all-in-one-20k/)

Datasheet

## Datasheet All-in-One.

Every model side by side: keep only what differs, take it as CSV or print it.

**All-in-One · Technical data**

| Model | 20 kVA |
| --- | --- |
| Model |  |
| AEC codes | AIO-20K-2X50 … AIO-20K-8X50 · AIO-20K-4X100 |
| UPS inside | IST9 20 kVA, rack 3U |
| Rated power (kVA / kW) | 20 / 20 |
| Input / output | 3/3 · 3/1 |
| Technology | online double conversion · IGBT rectifier with PFC · DSP control · battery from isolated DC/DC lithium modules |
| Input |  |
| Voltage range | phase 176–280 V full load · 80–176 V with linear derating |
| Frequency | 40–70 Hz |
| Power factor · THDi | ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load |
| Output |  |
| Voltage | 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L · fine adjustment ± 5 V |
| Frequency on battery | 50 or 60 ± 0.1 Hz |
| Voltage distortion | ≤ 2% resistive full load |
| Power factor | 1.0 (kVA = kW) |
| Transfer time | < 1 ms synchronised · < 10 ms not synchronised |
| Overload | ≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms |
| Efficiency (AC/AC) | up to 96% · 99% in ECO mode |
| Modes | online · ECO · battery · bypass · generator · frequency converter · impact load · test load |
| Battery system |  |
| Lithium modules | 2 to 8 × 50 Ah (5.76–23.0 kWh) or 4 × 100 Ah (23.0 kWh) |
| Backup time | 15–60 min at 20 kW (50 Ah) · 60 min at 20 kW, 200 min at 6 kW (4 × 100 Ah) |
| Charge current, max. | 10 A (UPS charger); per module set from the number of modules |
| General |  |
| Communication | RS232 · EPO · RS485 · options: SNMP, RS485 + dry contact |
| System display | 4.3" touch screen, tilted, on the door, with 3-colour LED status bar · LCD of the UPS · USB for records and upgrades |
| Noise | < 65 dB at full load |
| Working temperature · humidity | UPS −5 … 40 °C · battery 0–40 °C (15–30 °C recommended) · humidity 5–95%, non-condensing |
| Altitude · protection degree | ≤ 2000 m (above: derating to [IEC 62040-3](https://webstore.iec.ch/en/publication/60140)) · IP20 |
| Earthing systems | TN-S · TN-C · TN-C-S |
| Cabinet size W × D × H (mm), on castors | 600 × 1000 × 1110 · 1000 mm high without castors |
| Cabinet weight with distribution, without UPS and modules (kg) | 138 ± 5 (50 Ah) · 134 ± 5 (100 Ah) |
| System weight (kg) | 232 (2 × 50 Ah) to 460 (8 × 50 Ah) · 352 (4 × 100 Ah) |
| UPS size W × D × H (mm) | 438 × 535 × 130 (3U) |
| UPS weight (kg) | 18.4 |

UPS data from the IST9 user manual; system data from the AEC All-in-One 20 kVA user manual and the EMEA 2026 catalogue. Specifications are subject to change without notice.

#### **Full technical details** 20 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

### Why All-in-One

01 **1 cabinet · Nothing to assemble on site** IST9 20 kVA UPS, distribution breakers with maintenance bypass and lithium modules in one 600 × 1000 mm cabinet on castors.

02 **20 kW · Full power from the battery** The modules carry the full 20 kW of the IST9 20 kVA inside: two 50 Ah modules (10 kW each) or four 100 Ah modules (5 kW each).

03 **Hot-swap · Modules change live** Modules of 50 or 100 Ah slide in like drawers. A faulty module leaves the system on its own while the others keep supplying the load.

04 **DC/DC · Isolated from the mains** Every module has its own DC/DC converter: the battery is electrically isolated from the mains, and old and new modules work together.

05 **2 layers · BMS from cell to system** A battery management unit in every module and a system BMS in the touch screen: cell, module and system data, fault records, early warning.

06 **1 screen · UPS and battery together** The tilted touch screen on the door shows UPS energy flow, battery cabinet, every module and every cell.

OLD AND NEW TOGETHER

## Grow the battery over the years

Modules added at different times work in the same system: each DC/DC converter balances its own module.

- Phase I · modules in service: SOH 88%
- Phase II · modules in service: SOH 91%
- Phase III · new modules: SOH 95%
- SOH: state of health of the battery modules.

LITHIUM VS LEAD-ACID

## All-in-One compared with UPS + VRLA

AEC comparison, indicative values; VRLA cycle life from 12 V 9 Ah battery data at 25 °C.

**All-in-One compared with UPS + VRLA**

| Item | All-in-One | UPS + VRLA |
| --- | --- | --- |
| Units to install | 1 cabinet | UPS + battery cabinet |
| Installation | 1 person, 30–60 min | 2 people, 2–4 h |
| Battery life | 10+ years · 5,000 cycles at 50% DoD | 3–5 years · about 500 cycles at 50% DoD |
| Battery service | one module at a time, load supplied | whole string, often with downtime |
| Monitoring | every cell, module and system | string voltage only |

THE RANGE

## One system, eight codes

The IST9 20 kVA inside, input / output 3/3 or 3/1. Seven codes with 2 to 8 lithium modules of 50 Ah, and one with four 100 Ah modules for long backup.

- From the top: tilted touch screen on the door; IST9 20 kVA rack UPS (3U); distribution switches (input, output, bypass, battery and maintenance bypass); lithium modules.
- Footprint 600 × 1000 mm (W × D); height 1110 mm on castors, 1000 mm without castors.
- 2 to 8 × 50 Ah: modules 223 mm wide, two per row; short and medium backup times.
- 4 × 100 Ah: modules 440 mm wide, one per row; long backup times.
- The number of modules depends on the load and the backup time required (see the backup tables). Configuration by AEC.

INSIDE THE CABINET

## Everything wired at the factory

The UPS and the distribution switches sit at the top, the lithium modules underneath, all wired at the factory.

- Rack UPS: IST9 20 kVA (3U), online double conversion, with its own display.
- Distribution switches: input, output, bypass and battery breakers and the maintenance bypass on one front panel; the bypass cover is monitored by a door switch.
- Lithium modules: below the UPS, behind the door, 2 to 8 × 50 Ah or 4 × 100 Ah; hot-swappable, each with its own switch, indicators, battery management unit and DC/DC converter.
- System touch screen on the door: UPS and battery status down to the cell, records, settings and upgrades, with a 3-colour LED status bar.
- Control electronics: two system power boards feed the control electronics; a communication box for the optional SNMP card and RS485 port; one adapter board per module for DC power and measurement; a system adapter for EPO input and communication between UPS, modules and touch screen.

LITHIUM MODULES

## Hot-swappable modules, managed one by one

Lithium iron phosphate modules of 50 or 100 Ah slide into the cabinet like drawers. Each one has its own battery management unit, DC/DC converter, switch and indicators.

- Module size 223 × 665 × 152 mm (50 Ah), 440 × 665 × 132 mm (100 Ah); kW = DC/DC rated output per module.
- Module rated output voltage 240 / ±240 / 480 V.
- Parts: front handle, indicators, in-place switch, fans, connector, rear handle, isolated DC/DC module, LFP cells, sealing plate.
- DC/DC isolation: the battery is electrically isolated from the mains.
- Zero voltage at the port: no risk of short-circuit shock when handling.
- Fire protection in the module, also under extreme battery failure.
- Automatic exit: a faulty module leaves the system, the others keep working.
- Less leakage risk from the battery cells; preventive alarm before a failure.
- Insulation monitored online, with early warning of an insulation fault.
- LFP: lithium iron phosphate cells, 3.2 V.
- Cell discharge rate 4C (50 Ah modules) or 1C (100 Ah modules).
- 5,000 cell cycles at 50% depth of discharge.
- SOC accuracy ≥ 95%.
- Battery working range 0–40 °C, 15–30 °C recommended.

**Hot-swappable modules, managed one by one**

| Module | V | kWh | kW | kg | per system |
| --- | --- | --- | --- | --- | --- |
| 50 Ah | 57.6 | 2.88 | 10 | > 38 | 2–8 |
| 100 Ah | 57.6 | 5.76 | 5 | > 50 | 4 |

LITHIUM MODULES

## Three indicators

Run (green), alarm (yellow) and fault (red) on every module. Flashing: once per second; (3 s): once every 3 seconds.

Pick a state: the module's lights come on as the catalogue's table gives them.

**Three indicators**

| Status | Run (green) | Alarm (yellow) | Fault (red) |
| --- | --- | --- | --- |
| Charge | on |  |  |
| Discharge | flashing |  |  |
| Sleep | on | on |  |
| Off |  | on |  |
| Module alarm |  | on |  |
| Communication fault |  | flashing (3 s) |  |
| Module protection |  |  | on |
| Battery fault |  |  | flashing |

ORDERING CODES

## Eight codes, one 20 kVA system

Every code: IST9 20 kVA, input / output 3/3 or 3/1. Weight: UPS 18.4 kg + cabinet with distribution 138 ± 5 kg (134 ± 5 kg for 100 Ah) + modules of more than 38 kg (50 Ah) or 50 kg (100 Ah) each. Backup times: reference values, to be confirmed by actual measurement; AEC sizes every system.

**Eight codes, one 20 kVA system**

| AEC code | Lithium modules | kWh | min at 20 kW | min at 10 kW | min at 6 kW | Weight (kg) |
| --- | --- | --- | --- | --- | --- | --- |
| AIO-20K-2X50 | 2 × 50 Ah | 5.76 | 15 | 30 | 50 | 232 |
| AIO-20K-3X50 | 3 × 50 Ah | 8.64 | 22 | 45 | 75 | 270 |
| AIO-20K-4X50 | 4 × 50 Ah | 11.5 | 30 | 60 | 100 | 308 |
| AIO-20K-5X50 | 5 × 50 Ah | 14.4 | 37 | 75 | 125 | 346 |
| AIO-20K-6X50 | 6 × 50 Ah | 17.3 | 45 | 90 | 150 | 384 |
| AIO-20K-7X50 | 7 × 50 Ah | 20.2 | 52 | 105 | 175 | 422 |
| AIO-20K-8X50 | 8 × 50 Ah | 23.0 | 60 | 120 | 200 | 460 |
| AIO-20K-4X100 | 4 × 100 Ah | 23.0 | 60 | 120 | 200 | 352 |

BACKUP TIME

## 50 Ah modules · minutes

Backup grows one module at a time: 2 to 8 modules of 50 Ah, 2.88 kWh each. Load in kW; backup in minutes. 6 kW: catalogue reference values at 25 °C; 10 to 20 kW (50 to 100% load): AEC's product data. To be confirmed by actual measurement; AEC sizes every system. –: configuration not possible (at least two modules).

**50 Ah modules · minutes**

| Load · modules | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| --- | --- | --- | --- | --- | --- | --- | --- | --- |
| 6 kW | – | 50 | 75 | 100 | 125 | 150 | 175 | 200 |
| 10 kW | – | 30 | 45 | 60 | 75 | 90 | 105 | 120 |
| 12 kW | – | 25 | 37 | 50 | 62 | 75 | 87 | 100 |
| 14 kW | – | 21 | 32 | 43 | 53 | 64 | 75 | 86 |
| 16 kW | – | 19 | 28 | 38 | 47 | 56 | 65 | 75 |
| 18 kW | – | 17 | 25 | 33 | 41 | 50 | 58 | 67 |
| 20 kW | – | 15 | 22 | 30 | 37 | 45 | 52 | 60 |

BACKUP TIME

## 100 Ah modules · minutes

Long backup with four 100 Ah modules, 23.0 kWh in all (AIO-20K-4X100); the 100 Ah version always has four. Catalogue reference values at 25 °C, to be confirmed by actual measurement. –: configuration not possible.

**100 Ah modules · minutes**

| Load · modules | 1 | 2 | 3 | 4 |
| --- | --- | --- | --- | --- |
| 6 kW | – | – | – | 200 |
| 10 kW | – | – | – | 120 |
| 20 kW | – | – | – | 60 |

BATTERY MANAGEMENT

## Two-layer battery management

A battery management unit in every module (CAN) and the system BMS in the touch screen watch the battery at cell, module and system level, and talk to the UPS over RS485.

- Equalisation: intelligent current and voltage equalisation between modules for longer backup time and better use of every module.
- Old + new: new modules work together with modules already in service, so capacity can grow over the years.
- SOC: adaptive charge control; intelligent charge and discharge management avoids over-charge and over-discharge.
- Test: each module is tested separately, without cutting the power supply.
- Records: fault recording and early warning for fast, accurate fault location.
- Expansion: plug and play, modules are added or replaced in minutes with the load supplied.

THE UPS INSIDE

## Online double conversion, three-phase

The All-in-One 20 kVA is built around the AEC rack UPS IST9 20 kVA, three-phase, online double conversion. Full details are in the IST9 section of this catalogue.

- Input / output 3/3 or 3/1 in the All-in-One.
- Efficiency 96% in double conversion, 99% in ECO mode; output power factor 1 (kVA = kW).
- Normal mode: rectifier and inverter supply the load; the lithium modules are charged.
- Battery mode: with the mains abnormal, the modules supply the inverter with no break at the output.
- Bypass mode: load on the static bypass when the UPS is off (if enabled) or on a fault.
- Maintenance bypass, through the distribution switches: the load stays supplied during service.
- Input: phase voltage 176–280 V at full load, 80–176 V with linear derating; 40–70 Hz; power factor ≥ 0.99; THDi ≤ 3% at resistive full load, ≤ 5% non-linear.
- Output: 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L; THDv ≤ 2%; output power factor 1.0 (kVA = kW).
- Inverter overload: ≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms.
- Battery cold start: the UPS starts from the lithium modules without mains.
- Operating modes: generator mode, frequency converter, impact load mode and test load.
- Output voltage adjustable by ± 5 V.
- 20 kVA UPS rating; 3U, 438 mm rack chassis; 5 modes: normal, battery, bypass, ECO, maintenance; UPS working temperature −5…40 °C.

SYSTEM TOUCH SCREEN

## From the cabinet down to the cell

The tilted touch screen on the door shows the whole system: UPS energy flow, battery system, every module and every cell. A 3-colour LED bar shows the state from across the room.

- Status bar: blue = normal, yellow = bypass, red = fault.
- Battery system, module and cell data; current fault, history and user log.
- Records downloaded to a USB stick; touch-screen and battery-system firmware upgraded from USB.
- Password levels protect the settings.
- Home page: live energy flow from mains, bypass and battery to the output, with run status, output voltage per phase and frequency.
- Battery information: voltage, current, status, system SOC and SOH, remaining time.
- Module data: pack voltage and temperature, SOC, SOH, current, inner temperature.
- Cell voltages: every cell of every module, page by page.
- Info manage: run information, history record, user log and device information.
- Run information: status of mains, bypass, inverter, output, battery, fans and EPO.
- History record: all abnormal events with date and time.
- Device manage: battery manage and test, communication, HMI, passwords, records, upgrade.
- Record manage: history and user log exported to USB.

SERVICE

## Serviced without switching off the load

Maintenance bypass, live module replacement and USB upgrades keep the load supplied during service.

- Distribution switches: maintenance, output, input, bypass and battery. Module switch: unlock to isolate a module.
- To maintenance bypass without a break, step 1 · Inverter off: press ON/OFF on the touch screen; the UPS transfers to bypass.
- Step 2 · Cover off: remove the maintenance bypass cover. If step 1 was skipped, the cover switch stops the inverter and transfers to bypass.
- Step 3 · Maintenance bypass on: close the maintenance bypass switch; the load is fed by both bypasses.
- Step 4 · Isolate: open UPS input, bypass, output and battery breakers and set every module switch to unlock; the load runs on the maintenance bypass.
- Back to normal: close input, bypass, output and battery breakers and lock the modules; when the touch screen shows the bypass voltage, open the maintenance bypass and refit its cover; switch the inverter on from the touch screen (start-up about 30 s).
- Start without mains: lock any one battery module; it powers the system and the touch screen starts automatically.
- AEC service: 24/7 technical assistance by phone and WhatsApp; < 30 min WhatsApp reply to technical and commercial questions; warranty 3 years on the UPS and 5 years on the lithium modules, extendable with a maintenance contract; spare parts in 21+ countries across the Allis Electric group.
- service@aecups.com · +39 393 080 5211 · www.aecups.com

PLANNING

## One cabinet to connect · IST9 20 kVA max. steady-state current (A)

Only mains, bypass and output are wired on site; the lithium modules are already connected to the UPS inside the cabinet.

- Site: cabinet 600 × 1000 × 1110 mm on castors (1000 mm high without); 800 mm free in front and behind, 500 mm above.
- Floor: 232 kg (2 × 50 Ah) to 460 kg (8 × 50 Ah) on 0.6 m²; 352 kg with 4 × 100 Ah.
- Commissioning: date, time, language, module quantity and lithium charge current (up to 10 A) set on the touch screen by AEC.
- Choose the number of modules from the backup tables; AEC sizes and configures the system.

**One cabinet to connect · IST9 20 kVA max. steady-state current (A)**

| kVA | Mode | AC in | Bypass | AC out |
| --- | --- | --- | --- | --- |
| 20 | 3/3 | 35 | — | 30 |
| 20 | 3/1 | 35 | 91 | 91 |

PLANNING

## IST9 20 kVA · recommended breakers (A)

From the IST9 user manual. Breaker 1.5–2 × max. input current, without leakage protection.

**IST9 20 kVA · recommended breakers (A)**

| kVA | Mode | AC in | Bypass | AC out |
| --- | --- | --- | --- | --- |
| 20 | 3/3 | 63 × 3P | 50 × 3P | 50 × 3P |
| 20 | 3/1 | 63 × 3P | 125 × 1P | 125 × 1P |

CHOOSING THE MODULES

## 50 Ah or 100 Ah?

Same cabinet, same UPS: the module decides the backup. Catalogue reference values; AEC sizes every system.

**50 Ah or 100 Ah?**

| Item | 50 Ah | 100 Ah |
| --- | --- | --- |
| Modules | 2 to 8, two per row | 4, one per row |
| Module width | 223 mm | 440 mm |
| Cells | 4C | 1C |
| Energy per module | 2.88 kWh | 5.76 kWh |
| Energy in all | 5.76–23.0 kWh | 23.0 kWh |
| Backup at 20 kW | 15–60 min | 60 min |
| System weight | 232–460 kg | 352 kg |
| Best for | short and medium backup | long backup, low and medium loads |

TECHNICAL DATA · BATTERY AND CABINET

## Lithium modules

Lithium module data from the EMEA 2026 catalogue.

**Lithium modules**

| Lithium module | 50 Ah | 100 Ah |
| --- | --- | --- |
| Cells | LFP 3.2 V 50 Ah, 18 in series | LFP 3.2 V 100 Ah, 18 in series |
| Cell discharge / charge rate | 4C / 1C | 1C / 0.5C |
| Rated voltage (V) | 57.6 | 57.6 |
| Energy (kWh) | 2.88 | 5.76 |
| DC/DC rated output power (kW) | 10 | 5 |
| Rated output voltage (V) | 240 / ±240 / 480 | 240 / ±240 / 480 |
| Size W × D × H (mm) | 223 × 665 × 152 | 440 × 665 × 132 |
| Weight (kg) | > 38 | > 50 |
| Modules per system | 2 to 8 | 4 |
| Energy per system | 5.76–23.0 kWh | 23.0 kWh |
| Cycle life | 5,000 cell cycles at 50% DoD | 5,000 cell cycles at 50% DoD |
| SOC accuracy | ≥ 95% | ≥ 95% |
| Storage | 25–50% SOC, recharge every 3 months | 25–50% SOC, recharge every 3 months |

TECHNICAL DATA · BATTERY AND CABINET

## Cabinet and system

Cabinet and system data from the AEC All-in-One 20 kVA user manual and the EMEA 2026 catalogue. Specifications are subject to change without notice.

- 20 kVA: one system, eight codes
- 2–8 × 50 Ah or 4 × 100 Ah modules
- 200 min at 6 kW with 8 × 50 Ah or 4 × 100 Ah
- 0.6 m² floor space of the cabinet

**Cabinet and system**

| Cabinet and system | All-in-One 20 kVA |
| --- | --- |
| Cabinet W × D × H (mm) | 600 × 1000 × 1110 on castors · 600 × 1000 × 1000 without castors |
| Cabinet weight | with distribution, without UPS and modules: 138 ± 5 kg (50 Ah) · 134 ± 5 kg (100 Ah) |
| System weight | UPS 18.4 + cabinet + modules: 232 kg (2 × 50 Ah) to 460 kg (8 × 50 Ah) · 352 kg (4 × 100 Ah) |
| Clearances | 800 mm in front and behind · 500 mm above |
| Breakers | input, output, bypass, battery · maintenance bypass |
| Displays | UPS display · tilted system touch screen with 3-colour LED status bar |
| Battery management | two layers: BMU in every module (CAN) · system BMS in the touch screen (RS485 to the UPS) |
| System communication | RS485 · USB on the touch screen (records, upgrades) · options: SNMP card, dry-contact card |
| Alarms | low battery, abnormal AC input, UPS failure, overload and more |
| Protections | low battery, overload, short circuit, over-temperature and more |
| Black start | any one locked module powers the system and the touch screen |
| Working temperature | UPS −5 … 40 °C · battery 0–40 °C, 15–30 °C recommended |
| Relative humidity | 5–95%, non-condensing |
| Warranty | lithium modules: 5 years |

### Ordering codes All-in-One

| Code | Description |
| --- | --- |
| `AIO-20K-2X50` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 2 × 50 Ah lithium modules (5.76 kWh) |
| `AIO-20K-3X50` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 3 × 50 Ah lithium modules (8.64 kWh) |
| `AIO-20K-4X50` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 4 × 50 Ah lithium modules (11.5 kWh) |
| `AIO-20K-5X50` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 5 × 50 Ah lithium modules (14.4 kWh) |
| `AIO-20K-6X50` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 6 × 50 Ah lithium modules (17.3 kWh) |
| `AIO-20K-7X50` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 7 × 50 Ah lithium modules (20.2 kWh) |
| `AIO-20K-8X50` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 8 × 50 Ah lithium modules (23.0 kWh) |
| `AIO-20K-4X100` | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 4 × 100 Ah lithium modules (23.0 kWh), one per row |
| Options | SNMP card · dry-contact card · extra 50 Ah modules, up to 8 per cabinet |

Diagrams

## The All-in-One, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

### How the power flows

Pick an operating mode: the path the power takes to the load lights up.

**Normal.** Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 96% (IST9 20 kVA inside).

### Losses per 100 kW of load

Worked out as P × (1/η − 1) at the stated maximum efficiency, with the load steady all year. IST9 20 kVA inside.

1. Double conversion 96% **4.17 kW36,500 kWh/year**
2. ECO 99% **1.01 kW8,850 kWh/year**

### Phase configurations

Input / output: three-phase (3) or single-phase (1). 3/3 or 3/1; no 1/1 on the All-in-One.

**3/3** 3~ → 3~

**3/1** 3~ → 1~

### Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

- **Cabinet on castors, 20 kVA** 600 × 1,000 × 1,110 mm · 138 ± 5 kg with distribution, without UPS and modules (134 ± 5 kg, 100 Ah version); 232–460 kg complete

Questions

## Questions people ask

#### What is inside the All-in-One cabinet?

An IST9 20 kVA online double-conversion rack UPS (three-phase, 3/3 or 3/1), the distribution switches with maintenance bypass and 2 to 8 hot-swappable 50 Ah lithium modules, or four of 100 Ah, factory-built into one 600 × 1000 × 1110 mm cabinet on castors. One touch screen on the door shows UPS and battery down to the cell.

#### What backup time can the All-in-One reach?

Up to 200 minutes at 6 kW with 8 × 50 Ah or 4 × 100 Ah modules. At the full 20 kW the tables give 15 to 60 minutes with 2 to 8 × 50 Ah modules and 60 minutes with 4 × 100 Ah. These are reference values to be confirmed by actual measurement, and AEC sizes every system.

#### Which lithium modules should I choose?

The 50 Ah modules (2.88 kWh each, 2 to 8 per cabinet, 10 kW each) are for short and medium backup times; the 100 Ah version (5.76 kWh each, always 4 per cabinet, 5 kW each) is for long backup. Both are lithium iron phosphate and hot-swappable, and a faulty module leaves the system on its own while the others keep supplying the load.

#### Which All-in-One fits my load?

There is one: the All-in-One 20 kVA, with the IST9 20 kVA inside, three-phase input, 3/3 or 3/1, for loads up to 20 kW. Two 50 Ah modules already carry the full 20 kW; more modules, or the 100 Ah version, give longer backup. For a single-phase supply or above 20 kVA, AEC proposes another range.

#### How long do the lithium modules last compared with lead-acid?

The LFP cells are rated for 5,000 cycles at 50% depth of discharge and 10+ years, against about 500 cycles and 3–5 years for VRLA in AEC's indicative comparison. Each module has its own DC/DC converter, so new modules can be added later and work together with the older ones.

#### How long does installation take?

AEC indicates 1 person and 30–60 minutes for the All-in-One, against 2 people and 2–4 hours for a UPS with a separate VRLA cabinet. Only mains, bypass and output are wired on site; the cabinet measures 600 × 1000 × 1110 mm on castors and weighs 232 to 460 kg complete (352 kg with 4 × 100 Ah).

#### How is the All-in-One monitored?

RS485 links UPS, battery BMS and touch screen as standard, and the touch screen exports records and takes firmware upgrades from USB. An SNMP card and a dry-contact card are optional.

[All 14 questions](https://www.aecups.com/en/faq/all-in-one/)

In the same family: [IST9](https://www.aecups.com/en/products/ist9/) [IST7 10–40](https://www.aecups.com/en/products/ist7-10-40/) [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/) [IST7-T](https://www.aecups.com/en/products/ist7-t/) [Three-phase UPS](https://www.aecups.com/en/products/three-phase-ups/)

Guides

## Guides on the All-in-One

[All guides](https://www.aecups.com/en/blog/)

[**UPS for blackouts and storms: what to know** A UPS keeps equipment running through a blackout and filters storm sags and surges. What to check, how long it lasts and which AEC ranges fit.](https://www.aecups.com/en/blog/ups-for-blackouts/) [**UPS backup time: how to estimate and extend runtime** UPS runtime depends on the load in watts, battery energy and discharge rate: the estimate formula, why the maker's tables matter and how to extend it.](https://www.aecups.com/en/blog/ups-backup-time/) [**UPS batteries: VRLA vs lithium and how to choose** UPS batteries compared: VRLA AGM lead-acid vs LiFePO4 lithium on life, cycles, space and heat, plus how to read 12 V 9 Ah and a buyer's checklist.](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC All-in-One 20 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20All-in-One%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)