title: "Battery cabinet for UPS, 24 · 40 Ah · BB5 | AEC"
url: https://www.aecups.com/en/products/battery-cabinets/bb5/
description: "The BB5 is a slim floor-standing battery cabinet, 460 × 800 × 1400 mm and 110 kg empty, for 30 to 40 batteries of 12 V 24 or 40 Ah, or 100–120 of 9 Ah."
language: en
---

Battery cabinets · Batteries and cabinets

# BB5 Battery cabinet for UPS, 24 · 40 Ah

VRLA 24 · 40 Ah battery cabinet for AEC UPS

The BB5 is a slim floor-standing battery cabinet, 460 × 800 × 1400 mm and 110 kg empty, for 30 to 40 batteries of 12 V 24 or 40 Ah, or 100–120 of 9 Ah. For IST7 UPS of 10 to 60 kVA, and the IST3 10 kVA, where floor space is short and backup is in the tens of minutes.

**460 × 800 × 1400 mm** W × D × H

**110 kg empty** Weight

**30–40 × 24 / 40 Ah** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=180) [Contact us](https://www.aecups.com/en/contacts/?interest=Battery%20cabinets%20and%20VRLA%20batteries&msg=About%20the%20AEC%20BB5%20(Battery%20cabinets)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/bb5/v88/)

Quick answers

## BB5: quick answers

**What it is**: The BB5 is a slim floor-standing battery cabinet, 460 × 800 × 1400 mm and 110 kg empty, for 30 to 40 batteries of 12 V 24 or 40 Ah, or 100–120 of 9 Ah.

**Who it is for**: For IST7 UPS of 10 to 60 kVA, and the IST3 10 kVA, where floor space is short and backup is in the tens of minutes.

**Supply and configuration**: 12 V VRLA AGM blocks · string split at the neutral (+, N, −)

**Battery and backup**: 30–40 × 24 / 40 Ah

**Size and weight**: 460 × 800 × 1400 mm · 110 kg empty

**Ordering code**: BB5-11 · BB5-10k … BB5-60k

Battery cabinets

## What sets apart the BB5

At 460 mm the BB5 is the narrowest floor-standing cabinet. Five levels hold the batteries, the top one also carrying the disconnect Q1, which on the BB5 has fuses on +, N and − (50 to 125 A, UPS up to 60 kW). The front is a screwed panel; cables enter on the right side, top or bottom. Its largest layout stores 18.2 kWh nominal.

Loaded weights run from 340 kg (30 × 24 Ah) to 580 kg (38 × 40 Ah); with 38 × 40 Ah the floor load reaches 1576 kg/m². It is the cabinet in the catalogue's IST7 codes such as IST7-20-32X40 and IST7-10-150X9.

- **Against the BB6** (one size up): W × D × H 460 × 800 × 1400 mm against 800 × 800 × 1400 mm; Weight, empty 110 kg against 140 kg; Front screwed panel against door with lock; Battery levels 4 + Q1 level against 3 + Q1 level; Internal frame 458 × 785 mm, 5 levels against 745 × 765 mm, 2–4 levels.

Planning data

## BB5: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the BB5.

### One design, four sizes

**BB5 · One design, four sizes**

| UPS kW | Fuse F1/F2 | Size | Cu mm² | PE mm² | BB5 |
| --- | --- | --- | --- | --- | --- |
| 10 | 50 A | NH00 | 10 | 10 | ● |
| 20 | 63 A | NH00 | 16 | 16 | ● |
| 40 | 100 A | NH00 | 25 | 16 | ● |
| 60 | 125 A | NH00 | 35 | 16 | ● |
| 80 | 160 A | NH00 | 70 | 35 |  |
| 100 | 250 A | NH1 | 120 | 60 |  |
| 120 | 250 A | NH1 | 120 | 60 |  |
| 160 | 400 A | NH2 | 240 | 120 |  |
| 200 | 400 A | NH2 | 240 | 120 |  |

### Ventilation of the battery cabinet

**BB5 · Ventilation of the battery cabinet**

| Example | BB5 · 40 × 40 Ah |
| --- | --- |
| Q float | 0.48 m³/h |
| Q boost | 3.8 m³/h |
| Openings | 108 cm² |

Installation

## Installing the BB5: space, cables

Each figure with its source.

**BB5 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 100 mm, left 100 mm, right 100 mm; front and top: not given | BB user manual / drawings 2026-10-10 (MD-001, user manual §5) |
| Cable entry | Right side, top and bottom knock-outs | BB user manual / drawings 2026-10-10 (MD-001, user manual §5) |
| Operating temperature | 0 to 40 °C, best 20–25 °C | AEC BB5–BB8 user manuals §3.3 |
| Switches and terminals | Screwed steel front panel (no door). | BB user manual / drawings 2026-10-10 (MD-001, user manual §5) |

Size and floor

## How big it is

460 × 800 × 1400 mm · 110 kg empty.

**0.37 m²** footprint

**1.4 m** height

Drag to turn

In 3D

## Look around the BB5

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/bb5/v88/)

Technical data

## Technical data BB5

Only this model's values, from the EMEA 2026 catalogue table.

**BB5 · Technical data**

|  |  |
| --- | --- |
| Mechanical |  |
| W × D × H (mm) | 460 × 800 × 1400 |
| Weight, empty | 110 kg |
| Front | screwed panel |
| Battery levels | 4 + Q1 level |
| Internal frame | 458 × 785 mm, 5 levels |
| Cable entry | right side, top and bottom |
| Floor fixing | through the base |
| Batteries |  |
| Battery | 12 V 24 / 40 Ah · 9 Ah |
| Configurations | 30–40 · 100 / 120 × 9 Ah |
| String voltage | ±180 … ±240 V |
| Electrical |  |
| Disconnect Q1 (3-pole) | fuses on +, N, − |
| Fuses F1 / F2 | 32–125 A |
| UPS power (code) | 10–60 kW |
| Float · max. charge (per battery) | 13.5–13.7 V · 14.4 V |
| General |  |
| Colour | RAL 9005 |
| Protection | IP20 · IP21–IP44 option |
| Standards | [IEC/EN 62040-1](https://webstore.iec.ch/en/publication/80573) · [EN IEC 62485-2](https://webstore.iec.ch/en/publication/7091) · CE |
| Warranty (cabinet) | 3 years |

From the AEC BB5, BB6, BB7 and BB8 user manuals and installation manuals (Rev. 1.0, 2026). VRLA batteries have a 1-year warranty for 9 Ah blocks and 2 years for larger blocks. Specifications are subject to change without notice.

#### **More technical details** range tables, ordering codes

Planning data

## Battery cabinets range tables

### Slim cabinet, 24 to 40 Ah

Only 460 mm wide, with a screwed front panel. Five levels: four battery shelves and the top shelf with the disconnect Q1, which also takes batteries in the 34–40 configurations.

**BB5 · Slim cabinet, 24 to 40 Ah**

| Batteries | Total kg | UPS kVA |
| --- | --- | --- |
| 30 · 32 · 34 × 24 Ah | 340 · 356 · 372 | 10 · 20 |
| 36 · 38 · 40 × 24 Ah | 388 · 400 · 420 | 10 · 20 · 30 · 40 |
| 30–38 × 40 Ah | 480–580 | 10 · 20 · 30 · 40 · 60 |
| 100 × 9 Ah | 355 | IST3 10 |
| 120 × 9 Ah | 405 | IST7 10 · 20 · 30 · 40 |

Ordering codes

## Ordering codes BB5

**Ordering codes BB5**

| Code | Description |
| --- | --- |
| BB4-11 · BB5-11 | Cabinets for single-phase UPS: max 80 × 9 Ah (BB4) · 120 × 9 Ah (BB5) |
| BB5-10k … BB5-60k | BB5 for UPS up to 10 · 20 · 40 · 60 kW; 24 / 40 Ah or up to 120 × 9 Ah; 3 fuse holders |
| OZ Power 12 V | 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah · code on request |

Questions

## Questions about the BB5

#### Which UPS can use a BB5?

IST7 from 10 to 60 kVA (codes BB5-10k to BB5-60k) and the IST3 10 kVA with 100 × 9 Ah. With 24 Ah batteries the catalogue lists 10–20 kVA for 30–34 blocks and 10–40 kVA for 36–40; with 40 Ah, 10 to 60 kVA.

#### How much ventilation does a BB5 need?

The catalogue's EN IEC 62485-2 example for a BB5 with 40 × 40 Ah: 0.48 m³/h on float, 3.8 m³/h on boost charge, and natural ventilation openings of at least 108 cm² each for inlet and outlet.

#### How big is the AEC BB5 and how much does it weigh?

The AEC BB5 measures 460 × 800 × 1400 mm; weight: 110 kg empty (EMEA 2026 catalogue).

Related models

## The same range: Battery cabinets

[The whole range](https://www.aecups.com/en/products/battery-cabinets/)

[**BB1** 6 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb1/) [**BB2** 12 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb2/) [**BB3** 32 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb3/) [**BBJ** 2U · 8 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bbj/) [**BBJ2** 3U · 16 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bbj2/) [**BB4** 80 × 9 Ah · smaller rating](https://www.aecups.com/en/products/battery-cabinets/bb4/) **BB5** 24 · 40 Ah [**BB6** 60 Ah · larger rating](https://www.aecups.com/en/products/battery-cabinets/bb6/) [**BB7** 60 · 80 · 100 Ah](https://www.aecups.com/en/products/battery-cabinets/bb7/) [**BB8** 80 · 100 Ah, 2 strings](https://www.aecups.com/en/products/battery-cabinets/bb8/)

Shared by the whole range, on the Battery cabinets page: [the catalogue's photos and drawings](https://www.aecups.com/en/products/battery-cabinets/#gallery).

Read next: [Battery room ventilation to EN IEC 62485-2 for VRLA](https://www.aecups.com/en/blog/battery-room-ventilation/) [UPS datasheet explained: every line, with examples](https://www.aecups.com/en/blog/how-to-read-a-ups-datasheet/) [UPS batteries: VRLA vs lithium and how to choose](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC BB5: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Battery%20cabinets%20and%20VRLA%20batteries&msg=About%20the%20AEC%20BB5%20(Battery%20cabinets)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)