# BB7 Battery cabinet for UPS, 60 · 80 · 100 Ah

VRLA 60 · 80 · 100 Ah battery cabinet for AEC UPS

The BB7 is a tall floor-standing battery cabinet, 800 × 800 × 1900 mm and 160 kg empty, for 28 to 36 batteries of 12 V 80 or 100 Ah. For IST7 UPS up to 160 kVA in the code list (fuses up to 200 kW) that need large batteries on the BB6's footprint.

**800 × 800 × 1900 mm** W × D × H

**160 kg empty** Weight

**28–36 × 80 / 100 Ah** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=180) [Contact us](https://www.aecups.com/en/contacts/?interest=Battery%20cabinets%20and%20VRLA%20batteries&msg=About%20the%20AEC%20BB7%20(Battery%20cabinets)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/bb7/v66/)

Quick answers

## BB7: quick answers

**What it is**: The BB7 is a tall floor-standing battery cabinet, 800 × 800 × 1900 mm and 160 kg empty, for 28 to 36 batteries of 12 V 80 or 100 Ah.

**Who it is for**: For IST7 UPS up to 160 kVA in the code list (fuses up to 200 kW) that need large batteries on the BB6's footprint.

**Supply and configuration**: 12 V VRLA AGM blocks · string split at the neutral (+, N, −)

**Battery and backup**: 28–36 × 80 / 100 Ah

**Size and weight**: 800 × 800 × 1900 mm · 160 kg empty

**Ordering code**: BB7-10k … BB7-200k

Battery cabinets

## What sets apart the BB7

The BB7 keeps the BB6's 800 × 800 mm footprint and grows to 1900 mm: four shelves plus the Q1 level, which takes two or four batteries in the 34 and 36 configurations. It is fixed through four Ø9 mm holes at 685 × 700 mm centres. Q1 fuses go from 50 to 400 A (NH00 to NH2), for UPS up to 200 kW; the AEC code list pairs it up to the IST7-160.

With 100 Ah batteries it weighs 1095 to 1275 kg and puts 1992 kg/m² on the floor (36 × 100 Ah), the highest of the range: check the slab. Its largest layout stores 43.2 kWh nominal.

- **Against the BB6** (one size down): W × D × H 800 × 800 × 1900 mm against 800 × 800 × 1400 mm; Weight, empty 160 kg against 140 kg; Battery levels 4 + Q1 level against 3 + Q1 level; Internal frame 745 × 765 mm, 2–5 levels against 745 × 765 mm, 2–4 levels; Floor fixing 4 × Ø9, centres 685 × 700 against through the feet.
- **Against the BB8** (one size up): W × D × H 800 × 800 × 1900 mm against 1400 × 800 × 1900 mm; Weight, empty 160 kg against 250 kg; Front door with lock against two doors with lock; Battery levels 4 + Q1 level against 4 in two bays + Q1; Internal frame 745 × 765 mm, 2–5 levels against 1350 × 765 mm, 2–5 levels.

Planning data

## BB7: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the BB7.

### One design, four sizes

**BB7 · One design, four sizes**

| UPS kW | Fuse F1/F2 | Size | Cu mm² | PE mm² | BB7 |
| --- | --- | --- | --- | --- | --- |
| 10 | 50 A | NH00 | 10 | 10 | ● |
| 20 | 63 A | NH00 | 16 | 16 | ● |
| 40 | 100 A | NH00 | 25 | 16 | ● |
| 60 | 125 A | NH00 | 35 | 16 | ● |
| 80 | 160 A | NH00 | 70 | 35 | ● |
| 100 | 250 A | NH1 | 120 | 60 | ● |
| 120 | 250 A | NH1 | 120 | 60 | ● |
| 160 | 400 A | NH2 | 240 | 120 | ● |
| 200 | 400 A | NH2 | 240 | 120 | ● |

### Ventilation of the battery cabinet

**BB7 · Ventilation of the battery cabinet**

| Example | BB7 · 36 × 100 Ah |
| --- | --- |
| Q float | 1.08 m³/h |
| Q boost | 8.6 m³/h |
| Openings | 242 cm² |

Installation

## Installing the BB7: space, cables

Each figure with its source.

**BB7 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 100 mm, left 100 mm, right 100 mm; front and top: not given | BB user manual / drawings 2026-10-10 (MD-001, user manual §5) |
| Cable entry | Gland plate 100 × 100 mm in the roof (59 mm from the right, 99 mm from the rear) | BB user manual / drawings 2026-10-10 (GA) |
| Operating temperature | 0 to 40 °C, best 20–25 °C | AEC BB5–BB8 user manuals §3.3 |
| Switches and terminals | Q1 DC fuse switch-disconnector, its rotary handle on the door, about 1,640 mm up. | BB user manual / drawings 2026-10-10 GA (read at scale) |
| Door | One leaf, hinged on the right | BB user manual / drawings 2026-10-10 (GA) |

Size and floor

## How big it is

800 × 800 × 1900 mm · 160 kg empty.

**0.64 m²** footprint

**1.9 m** height

Drag to turn

In 3D

## Look around the BB7

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/bb7/v66/)

Technical data

## Technical data BB7

Only this model's values, from the EMEA 2026 catalogue table.

**BB7 · Technical data**

|  |  |
| --- | --- |
| Mechanical |  |
| W × D × H (mm) | 800 × 800 × 1900 |
| Weight, empty | 160 kg |
| Front | door with lock |
| Battery levels | 4 + Q1 level |
| Internal frame | 745 × 765 mm, 2–5 levels |
| Cable entry | top gland 100 × 100 · bottom |
| Floor fixing | 4 × Ø9, centres 685 × 700 |
| Batteries |  |
| Battery | 12 V 80 / 100 Ah |
| Configurations | 28–36 |
| String voltage | ±168 … ±216 V |
| Electrical |  |
| Disconnect Q1 (3-pole) | fuses on + and − |
| Fuses F1 / F2 | 63–400 A |
| UPS power (code) | 10–200 kW |
| Float · max. charge (per battery) | 13.5–13.7 V · 14.4 V |
| General |  |
| Colour | RAL 9005 |
| Protection | IP20 · IP21–IP44 option |
| Standards | [IEC/EN 62040-1](https://webstore.iec.ch/en/publication/80573) · [EN IEC 62485-2](https://webstore.iec.ch/en/publication/7091) · CE |
| Warranty (cabinet) | 3 years |

From the AEC BB5, BB6, BB7 and BB8 user manuals and installation manuals (Rev. 1.0, 2026). VRLA batteries have a 1-year warranty for 9 Ah blocks and 2 years for larger blocks. Specifications are subject to change without notice.

#### **More technical details** range tables, ordering codes

Planning data

## Battery cabinets range tables

### Tall cabinet, 80 to 100 Ah

The same footprint as the BB6, 1900 mm high, for large batteries. Four shelves plus the Q1 level, which takes 2 or 4 batteries in the 34 and 36 configurations.

**BB7 · Tall cabinet, 80 to 100 Ah**

| Batteries | Total kg | UPS kVA |
| --- | --- | --- |
| 30 × 80 Ah | 870 | 10–160 |
| 32 × 80 Ah | 930 | 10–160 |
| 34 × 80 Ah | 960 | 10–160 |
| 36 × 80 Ah | 1005 | 10–160 |
| 30 · 32 · 34 · 36 × 100 Ah | 1095 · 1155 · 1215 · 1275 | 10–160 |

Ordering codes

## Ordering codes BB7

**Ordering codes BB7**

| Code | Description |
| --- | --- |
| BB7-10k … BB7-200k | BB7 for UPS up to 10 · 20 · 40 · 60 · 80 · 100 · 120 · 160 · 200 kW |
| OZ Power 12 V | 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah · code on request |

Questions

## Questions about the BB7

#### What floor load does a BB7 put on the slab?

With 36 × 12 V 100 Ah the catalogue gives 1992 kg/m², 1275 kg on 800 × 800 mm. With 80 Ah batteries it weighs 870 to 1005 kg.

#### Which cable does a BB7-120k need to the UPS?

The catalogue's example: fuses F1/F2 250 A NH1, X1 → UPS cables of at least 120 mm² copper and PE 60 mm², single-core, 70 °C PVC in air, with site derating and voltage drop ≤ 0.5%.

#### How big is the AEC BB7 and how much does it weigh?

The AEC BB7 measures 800 × 800 × 1900 mm; weight: 160 kg empty (EMEA 2026 catalogue).

Related models

## The same range: Battery cabinets

[The whole range](https://www.aecups.com/en/products/battery-cabinets/)

[**BB1** 6 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb1/) [**BB2** 12 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb2/) [**BB3** 32 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb3/) [**BBJ** 2U · 8 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bbj/) [**BBJ2** 3U · 16 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bbj2/) [**BB4** 80 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb4/) [**BB5** 24 · 40 Ah](https://www.aecups.com/en/products/battery-cabinets/bb5/) [**BB6** 60 Ah · smaller rating](https://www.aecups.com/en/products/battery-cabinets/bb6/) **BB7** 60 · 80 · 100 Ah [**BB8** 80 · 100 Ah, 2 strings · larger rating](https://www.aecups.com/en/products/battery-cabinets/bb8/)

Shared by the whole range, on the Battery cabinets page: [the catalogue's photos and drawings](https://www.aecups.com/en/products/battery-cabinets/#gallery).

Read next: [Battery room ventilation to EN IEC 62485-2 for VRLA](https://www.aecups.com/en/blog/battery-room-ventilation/) [UPS datasheet explained: every line, with examples](https://www.aecups.com/en/blog/how-to-read-a-ups-datasheet/) [UPS batteries: VRLA vs lithium and how to choose](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/)