---
title: "Battery cabinet for UPS, 80 · 100 Ah, 2 strings · BB8 | AEC"
url: https://www.aecups.com/en/products/battery-cabinets/bb8/
description: "The BB8 is a double floor-standing battery cabinet, 1400 × 800 × 1900 mm and 250 kg empty, for 40, 60 or 64 batteries of 12 V 80 or 100 Ah in two strings."
language: en
---

Battery cabinets · Batteries and cabinets

# BB8 Battery cabinet for UPS, 80 · 100 Ah, 2 strings

VRLA 80 · 100 Ah, 2 strings battery cabinet for AEC UPS

The BB8 is a double floor-standing battery cabinet, 1400 × 800 × 1900 mm and 250 kg empty, for 40, 60 or 64 batteries of 12 V 80 or 100 Ah in two strings. For IST7 UPS up to 200 kVA and long backup times: one or two BB8 per UPS.

**1400 × 800 × 1900 mm** W × D × H

**250 kg empty** Weight

**40 · 60 · 64 × 80 / 100 Ah** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=180) [Contact us](https://www.aecups.com/en/contacts/?interest=Battery%20cabinets%20and%20VRLA%20batteries&msg=About%20the%20AEC%20BB8%20(Battery%20cabinets)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/bb8/v71/)

Quick answers

## BB8: quick answers

**What it is**: The BB8 is a double floor-standing battery cabinet, 1400 × 800 × 1900 mm and 250 kg empty, for 40, 60 or 64 batteries of 12 V 80 or 100 Ah in two strings.

**Who it is for**: For IST7 UPS up to 200 kVA and long backup times: one or two BB8 per UPS.

**Supply and configuration**: 12 V VRLA AGM blocks · string split at the neutral (+, N, −)

**Battery and backup**: 40 · 60 · 64 × 80 / 100 Ah

**Size and weight**: 1400 × 800 × 1900 mm · 250 kg empty

**Ordering code**: BB8-10k … BB8-200k

Battery cabinets

## What sets apart the BB8

The BB8 has two bays and two doors, with Q1 in the right bay. Most configurations hold two identical strings in parallel at Q1, each with its own +, N and − cables: 40 = 2 × 20 (±120 V), 60 = 2 × 30 (±180 V), 64 = 2 × 32 (±192 V). Measure each string separately at commissioning. The largest layout stores 76.8 kWh nominal, 153.6 kWh with two BB8.

Full, it weighs from 1195 kg (40 × 80 Ah) to 2215 kg (64 × 100 Ah), 1978 kg/m² on the floor. It is the only cabinet the catalogue pairs with the IST7-200, and the one in the example code IST7-160-64X100.

- **Against the BB7** (one size down): W × D × H 1400 × 800 × 1900 mm against 800 × 800 × 1900 mm; Weight, empty 250 kg against 160 kg; Front two doors with lock against door with lock; Battery levels 4 in two bays + Q1 against 4 + Q1 level; Internal frame 1350 × 765 mm, 2–5 levels against 745 × 765 mm, 2–5 levels.

Planning data

## BB8: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the BB8.

### One design, four sizes

**BB8 · One design, four sizes**

| UPS kW | Fuse F1/F2 | Size | Cu mm² | PE mm² | BB8 |
| --- | --- | --- | --- | --- | --- |
| 10 | 50 A | NH00 | 10 | 10 | ● |
| 20 | 63 A | NH00 | 16 | 16 | ● |
| 40 | 100 A | NH00 | 25 | 16 | ● |
| 60 | 125 A | NH00 | 35 | 16 | ● |
| 80 | 160 A | NH00 | 70 | 35 | ● |
| 100 | 250 A | NH1 | 120 | 60 | ● |
| 120 | 250 A | NH1 | 120 | 60 | ● |
| 160 | 400 A | NH2 | 240 | 120 | ● |
| 200 | 400 A | NH2 | 240 | 120 | ● |

### Ventilation of the battery cabinet

**BB8 · Ventilation of the battery cabinet**

| Example | BB8 · 64 × 100 Ah |
| --- | --- |
| Q float | 1.92 m³/h |
| Q boost | 15.4 m³/h |
| Openings | 430 cm² |

Installation

## Installing the BB8: space, cables

Each figure with its source.

**BB8 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 100 mm, left 100 mm, right 100 mm; front and top: not given | BB user manual / drawings 2026-10-10 (MD-001, user manual §5) |
| Cable entry | Gland plate 100 × 100 mm in the roof (59 mm from the right, 99 mm from the rear) | BB user manual / drawings 2026-10-10 (GA) |
| Operating temperature | 0 to 40 °C, best 20–25 °C | AEC BB5–BB8 user manuals §3.3 |
| Switches and terminals | Q1 in the right bay, its handle on the right door, about 1,668 mm up. | BB user manual / drawings 2026-10-10 GA (read at scale) |
| Door | Two leaves, hinged at the outer edges | BB user manual / drawings 2026-10-10 (GA) |

Size and floor

## How big it is

1400 × 800 × 1900 mm · 250 kg empty.

**1.12 m²** footprint

**1.9 m** height

Drag to turn

In 3D

## Look around the BB8

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/bb8/v71/)

Technical data

## Technical data BB8

Only this model's values, from the EMEA 2026 catalogue table.

**BB8 · Technical data**

|  |  |
| --- | --- |
| Mechanical |  |
| W × D × H (mm) | 1400 × 800 × 1900 |
| Weight, empty | 250 kg |
| Front | two doors with lock |
| Battery levels | 4 in two bays + Q1 |
| Internal frame | 1350 × 765 mm, 2–5 levels |
| Cable entry | top gland 100 × 100 · bottom |
| Floor fixing | through the feet |
| Batteries |  |
| Battery | 12 V 80 / 100 Ah |
| Configurations | 40 · 60 · 64 (×2 strings) |
| String voltage | ±120 … ±192 V |
| Electrical |  |
| Disconnect Q1 (3-pole) | fuses on + and − |
| Fuses F1 / F2 | 63–400 A |
| UPS power (code) | 10–200 kW |
| Float · max. charge (per battery) | 13.5–13.7 V · 14.4 V |
| General |  |
| Colour | RAL 9005 |
| Protection | IP20 · IP21–IP44 option |
| Standards | [IEC/EN 62040-1](https://webstore.iec.ch/en/publication/80573) · [EN IEC 62485-2](https://webstore.iec.ch/en/publication/7091) · CE |
| Warranty (cabinet) | 3 years |

From the AEC BB5, BB6, BB7 and BB8 user manuals and installation manuals (Rev. 1.0, 2026). VRLA batteries have a 1-year warranty for 9 Ah blocks and 2 years for larger blocks. Specifications are subject to change without notice.

#### **More technical details** range tables, ordering codes

Planning data

## Battery cabinets range tables

### Double cabinet, two strings in parallel

Two bays, two doors, Q1 on the right. Most configurations hold two identical strings in parallel at Q1, each with its own +, N and − cables.

**BB8 · Double cabinet, two strings in parallel**

| Batteries | Total kg | UPS kVA |
| --- | --- | --- |
| 40 × 80 Ah | 1195 | 10–160 |
| 60 × 80 Ah | 1650 | 10–200 |
| 64 × 80 Ah | 1735 | 60–200 |
| 40 × 100 Ah | 1495 | 10–200 |
| 60 × 100 Ah | 2095 | 10–200 |
| 64 × 100 Ah | 2215 | 60–200 |

Ordering codes

## Ordering codes BB8

**Ordering codes BB8**

| Code | Description |
| --- | --- |
| BB8-10k … BB8-200k | BB8 for UPS up to 10 · 20 · 40 · 60 · 80 · 100 · 120 · 160 · 200 kW |
| OZ Power 12 V | 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah · code on request |

Questions

## Questions about the BB8

#### Why does the BB8 hold two strings?

Two identical strings in parallel halve the power each battery delivers, so the same blocks give longer backup; the catalogue's sizing method notes that BB8 cabinets hold two strings as standard.

#### Which UPS can a BB8 serve?

IST7 from 10 to 200 kVA (codes BB8-10k to BB8-200k): 40 × 80 Ah for 10–160 kVA, 60 × 80 / 100 Ah for 10–200 kVA, 64 × 80 / 100 Ah for 60–200 kVA.

#### How big is the AEC BB8 and how much does it weigh?

The AEC BB8 measures 1400 × 800 × 1900 mm; weight: 250 kg empty (EMEA 2026 catalogue).

Related models

## The same range: Battery cabinets

[The whole range](https://www.aecups.com/en/products/battery-cabinets/)

[**BB1** 6 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb1/) [**BB2** 12 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb2/) [**BB3** 32 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb3/) [**BBJ** 2U · 8 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bbj/) [**BBJ2** 3U · 16 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bbj2/) [**BB4** 80 × 9 Ah](https://www.aecups.com/en/products/battery-cabinets/bb4/) [**BB5** 24 · 40 Ah](https://www.aecups.com/en/products/battery-cabinets/bb5/) [**BB6** 60 Ah](https://www.aecups.com/en/products/battery-cabinets/bb6/) [**BB7** 60 · 80 · 100 Ah · smaller rating](https://www.aecups.com/en/products/battery-cabinets/bb7/) **BB8** 80 · 100 Ah, 2 strings

Shared by the whole range, on the Battery cabinets page: [the catalogue's photos and drawings](https://www.aecups.com/en/products/battery-cabinets/#gallery).

Read next: [Battery room ventilation to EN IEC 62485-2 for VRLA](https://www.aecups.com/en/blog/battery-room-ventilation/) [UPS datasheet explained: every line, with examples](https://www.aecups.com/en/blog/how-to-read-a-ups-datasheet/) [UPS batteries: VRLA vs lithium and how to choose](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC BB8: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Battery%20cabinets%20and%20VRLA%20batteries&msg=About%20the%20AEC%20BB8%20(Battery%20cabinets)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)
