title: "CPSS to EN 50171, 1–10 kVA · CPSS3 | AEC"
url: https://www.aecups.com/en/products/cpss-1-10/
description: "CPSS 1–10 kVA: AEC CPSS3 central power supply to EN 50171, tower. Digital control, 120% constant overload, recharge in under 12 hours."
language: en
---

Central power supply (CPSS) · [EN 50171](https://mycatalogo.ceinorme.it/cei/item/0000018393?sso=y)

# CPSS 1–10 Central power supply (CPSS) to EN 50171,, single-phase

VRLA

The AEC CPSS3 is a single-phase central power supply system for emergency lighting and other safety services, designed to EN 50171: five ratings from 1 to 10 kVA (800 to 8,000 W), online double conversion, 120% constant overload, recharge in under 12 hours and batteries with a 10–12-year expected life.

**120%** constant overload

**10–12 years** expected battery life

**< 12 h** recharge time

**95.5%** AC/AC efficiency, 6–10 kVA

Datasheet Manuals and catalogues [Contact us](https://www.aecups.com/en/contacts/?msg=About%20the%20AEC%20CPSS%201%E2%80%9310%3A%20%0AQuantity%3A%20#form)

Display

## The CPSS 1–10 display.

The LCD shows the state of the system; alarms and protections cover battery, input, load and temperature.

DISPLAY AND PROTECTION

### Everything on the LCD

- Display: input / output voltage and frequency, protected load level, battery charge status, temperature, operation and lockout / fault.
- Alarms: low battery, abnormal input, overload, lockout / fault.
- Protection: low battery, overload, short circuit, over-temperature.
- Output voltage 208 / 220 / 230 / 240 V ± 1%, configurable from the display.

Overview

## Key facts

**Ratings**: 1–10 kVA

**Voltage**: 208 / 220 / 230 / 240 V

**Models**: CPSS3-1K · CPSS3-2K · CPSS3-3K · CPSS3-6K · CPSS3-10K

**Frequency (Hz)**: 50 / 60 ± 10% (50 / 60 Hz automatic regulation)

**Power factor**: ≥ 0.99

**THDi**: < 5%

**Output · power factor**: 0.8

**Voltage (V AC)**: 208 / 220 / 230 / 240 ± 1% (configurable from the display)

**Output · frequency (hz)**: 50 / 60 ± 0.2% (battery mode)

**Overload**: constant up to 120%

[Applications](https://www.aecups.com/en/applications/): Emergency lighting systems

Hands on

## Open the CPSS 1–10.

Pick an operating mode: the power path lights up to the load.

Models

## Choose your CPSS 1–10.

Central power supply system to EN 50171, tower, 1–10 kVA

**CPSS3-1K** 800 **36 V DC**Battery voltage **92%**Max. AC/AC efficiency

**CPSS3-2K** 1600 **72 V DC**Battery voltage **93%**Max. AC/AC efficiency

**CPSS3-3K** 2400 **96 V DC**Battery voltage **94%**Max. AC/AC efficiency

**CPSS3-6K** 4800 **192–240 V DC**Battery voltage **95.5%**Max. AC/AC efficiency

**CPSS3-10K** 8000 **192–240 V DC**Battery voltage **95.5%**Max. AC/AC efficiency

**CPSS 1–10 Models**

| Model | Output power (W) | Battery voltage | Max. AC/AC efficiency | L × W × H (mm) | Weight (kg) |
| --- | --- | --- | --- | --- | --- |
| CPSS3-1K | 800 | 36 V DC | 92% | 145 × 357 × 226 | 9.2 or 11.6 / 4.5 |
| CPSS3-2K | 1600 | 72 V DC | 93% | 190 × 397 × 330 | 17.7 or 22.4 / 8.5 |
| CPSS3-3K | 2400 | 96 V DC | 94% | 190 × 397 × 330 | 22.9 or 27.6 / 9.2 |
| CPSS3-6K | 4800 | 192–240 V DC | 95.5% | 230 × 524 × 553 / 190 × 429 × 337 (L) | 54.5 / 10.9 |
| CPSS3-10K | 8000 | 192–240 V DC | 95.5% | 230 × 524 × 553 / 190 × 429 × 337 (L) | 56.2 / 12.5 |

Datasheet

## Datasheet CPSS 1–10.

Every model side by side: keep only what differs, take it as CSV or print it.

**CPSS 1–10 · Technical data**

| Model | CPSS3-1K | CPSS3-2K | CPSS3-3K | CPSS3-6K | CPSS3-10K |
| --- | --- | --- | --- | --- | --- |
| Input |  |  |  |  |  |
| Voltage (V AC) | 120–295 | 80–275 |  |  |  |
| Frequency (Hz) | 50 / 60 ± 10% (50 / 60 Hz automatic regulation) |  |  |  |  |
| Power factor | ≥ 0.99 |  |  |  |  |
| THDi | < 5% |  |  |  |  |
| Output |  |  |  |  |  |
| Power (W) | 800 | 1600 | 2400 | 4800 | 8000 |
| Max. AC/AC efficiency | 92% | 93% | 94% | 95.5% |  |
| Power factor | 0.8 |  |  |  |  |
| Voltage (V AC) | 208 / 220 / 230 / 240 ± 1% (configurable from the display) |  |  |  |  |
| Frequency (Hz) | 50 / 60 ± 0.2% (battery mode) |  |  |  |  |
| THD | < 2% (linear loads) · < 5% (non-linear loads) | < 1% (linear loads) · < 4% (non-linear loads) |  |  |  |
| Overload | constant up to 120% |  |  |  |  |
| Batteries |  |  |  |  |  |
| Voltage (V DC) | 36 | 72 | 96 | 192–240 |  |
| Max. charging current (A) | 1–4 | 1–4 | 1–4 | 1–8 |  |
| Other specifications |  |  |  |  |  |
| Communications | RS232, EPO, USB (slot) · SNMP, RS485 + dry-contact card optional |  |  |  |  |
| LCD display | Input / output voltage and frequency, protected load level, battery charge status, temperature, UPS operation and lockout / fault |  |  |  |  |
| Alarms | Low battery, abnormal input, overload, lockout / fault, etc. |  |  |  |  |
| Protection | Low battery, overload, short circuit, over-temperature, etc. |  |  |  |  |
| Noise (dB) | < 50 | < 55 |  |  |  |
| Temperature (°C) | −5 … 40 |  |  |  |  |
| Humidity | 0–95% |  |  |  |  |
| Dimensions L × W × H (mm) | 145 × 357 × 226 | 190 × 397 × 330 | 230 × 524 × 553 / 190 × 429 × 337 (L) |  |  |
| Weight (kg) | 9.2 or 11.6 / 4.5 | 17.7 or 22.4 / 8.5 | 22.9 or 27.6 / 9.2 | 54.5 / 10.9 | 56.2 / 12.5 |
| Standards and certifications | CE (reference standards: safety IEC [EN 62040-1](https://webstore.iec.ch/en/publication/80573); EMC IEC [EN 62040-2](https://webstore.iec.ch/en/publication/33696); classification IEC [EN 62040-3](https://webstore.iec.ch/en/publication/60140)), EN 50171 |  |  |  |  |

All information is indicative, may be modified by AEC at any time and does not constitute a contractual obligation.

#### **Full technical details** 2 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

### Why CPSS 1–10

01 **Fully digital, high frequency** Digital control and high-frequency conversion for high efficiency (up to 95.5% AC/AC) and input power factor ≥ 0.99.

02 **120% constant overload** The output holds a constant overload of up to 120%.

03 **Long-life batteries, fast recharge** Batteries with 10–12 years expected life, recharged in less than 12 hours.

04 **EN 50171 central power supply** Central power supply to EN 50171, structure compliant with CEI EN 62040, for emergency lighting systems.

Diagrams

## The CPSS 1–10, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

### The ratings

Every model in the range, in proportion to its power.

1. CPSS3-1K **1 kVA · 0.8 kW**
2. CPSS3-2K **2 kVA · 1.6 kW**
3. CPSS3-3K **3 kVA · 2.4 kW**
4. CPSS3-6K **6 kVA · 4.8 kW**
5. CPSS3-10K **10 kVA · 8 kW**

In the same family: [CPSS 10–200](https://www.aecups.com/en/products/cpss-10-200/) [Central power supply (CPSS)](https://www.aecups.com/en/products/cpss-en-50171/)

Guides

## Guides on the CPSS 1–10

[All guides](https://www.aecups.com/en/blog/)

[**CPSS to EN 50171: what it asks and how to size one** A CPSS is a central battery system that powers emergency lighting and safety loads. What EN 50171 covers, how to size a CPSS and a worked example.](https://www.aecups.com/en/blog/cpss-en-50171/) [**UPS vs CPSS: which one does a building need?** A UPS keeps equipment running; a CPSS keeps safety systems such as emergency lighting on. How they differ and when a building needs both.](https://www.aecups.com/en/blog/ups-vs-cpss/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC CPSS 1–10 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?msg=About%20the%20AEC%20CPSS%201%E2%80%9310%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)