IST3 · Single-phase UPS

# IST3-2 Single-phase online UPS 2 kVA, tower, 230 V

VRLA 2 kVA online tower UPS, 230 V

The IST3-2 is a 2 kVA / 2000 W single-phase online double-conversion tower UPS with four internal 12 V 9 Ah batteries. For a small rack of servers and network devices, a medical or laboratory instrument, or a point of sale with several loads.

**2 kVA / 2 kW** Rating

**190 × 397 × 330 mm** W × D × H

**17.6 / 9.0 kg** Weight

**48 V** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=13) [Contact us](https://www.aecups.com/en/contacts/?interest=Single-phase%20UPS&msg=About%20the%20AEC%20IST3-2%20(IST3)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist3-2/v69/)

Quick answers

## IST3-2: quick answers

**What it is**: The IST3-2 is a 2 kVA / 2000 W single-phase online double-conversion tower UPS with four internal 12 V 9 Ah batteries.

**Who it is for**: For a small rack of servers and network devices, a medical or laboratory instrument, or a point of sale with several loads.

**Supply and configuration**: 208 / 220 / 230 / 240 V

**Battery and backup**: 48 V · 3 min at full load

**Size and weight**: 190 × 397 × 330 mm · 17.6 / 9.0 kg

**Ordering code**: IST3-2-4X9 · IST3-2-L

IST3

## What sets apart the IST3-2

The IST3-2 moves to the 190 × 397 × 330 mm frame it shares with the IST3-3, at 17.6 kg. Four 9 Ah blocks give a 48 V battery: 2 minutes at full load and 8 at half load in AEC's data (the catalogue prints 3 minutes). Loads connect to three Schuko outlets (not more than 5 A each, as a rule) and the input has a resettable overcurrent protector instead of a fuse.

On battery, the 1–3 kVA models hold any load below 75% with no time limit set by the UPS: the battery capacity decides. Above 75% the discharge time is capped (5.5 min at 75% falling to 3.0 min at 100%), which protects the battery from deep, fast discharges.

- **Against the IST3-1** (one size down): Power 2000 VA / 2000 W against 1000 VA / 1000 W; Voltage, standard model 48 V against 24 V; Voltage, long backup model 72 V against 36 V; Dimensions W × D × H, standard 190 × 397 × 330 against 145 × 357 × 226; Dimensions W × D × H, long backup 190 × 397 × 330 against 145 × 357 × 226.
- **Against the IST3-3** (one size up): Power 2000 VA / 2000 W against 3000 VA / 3000 W; Voltage, standard model 48 V against 72 V; Voltage, long backup model 72 V against 96 V; Noise < 50 dB against < 55 dB; Weight standard / long backup 17.6 / 9.0 kg against 22.5 / 9.2 kg.

Planning data

## IST3-2: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-2.

### Wall socket or terminal bar

**IST3-2 · Wall socket or terminal bar**

| Model | 2 kVA |
| --- | --- |
| AC input max. (A) | 12 |
| AC breaker (A) | 20 |
| DC input max. (A, long backup) | 37 |
| DC breaker (A) | 50 |
| AC cable (mm²) | 2.5 |
| Battery cable (mm²) | 6 |

Installation

## Installing the IST3-2: space, cables

Each figure with its source.

**IST3-2 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST3 user manual p.6 §1.2 |
| Cable entry | Plugs and sockets at the rear | AEC IST3 user manual |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST3 user manual p.6 §1.2 |
| Switches and terminals | Sockets, over-current protector and the battery connector on the rear panel. | AEC IST3 user manual p.6 §1.2 |

Size and floor

## How big it is

190 × 397 × 330 mm · 17.6 / 9.0 kg.

**0.08 m²** footprint

**119–233 kg/m²** floor load

**0.33 m** height

Floor load = weight ÷ footprint: 119 kg/m² at the lowest weight given (9 kg), 233 kg/m² at the highest (17.6 kg).

Efficiency

## How efficient is the AEC IST3-2 at your load?

IST3-2, 2 kW at its rating, online, double conversion (AEC's measured curve). Heat to remove on this curve: 50%: 0.10 kW (η 91.23%) · 75%: 0.13 kW (η 92.16%) · 100%: 0.16 kW (η 92.56%). At 50% load, 24/7, it loses about 842 kWh a year.

**92.56** % 100% · Measured (AEC datasheet)

How the curve is drawn and where each figure comes from: [the IST3 range page](https://www.aecups.com/en/products/ist3/#efficiency). The IST3 pages of the EMEA 2026 catalogue give no efficiency figure. The 1, 2 and 3 kVA curves are the ones AEC measured on the IST3-J of the same rating (AEC technical datasheet IST3-J 1–3 kVA), which AEC states has the same electronics; the 6 and 10 kVA curve has the same shape, moved to their 95.5% figure.

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56% | Measured (AEC datasheet) | IST3-2 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| ECO | 98.3% | Datasheet figure, load not stated | all | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83% | Measured (AEC datasheet) | IST3-1 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1% | Measured (AEC datasheet) | IST3-3 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3% | Typical curve, derived from the datasheet efficiency of 95.5% (AEC method) | IST3-6 · IST3-10 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |

Drag to turn

In 3D

## Look around the IST3-2

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist3-2/v69/)

Technical data

## Technical data IST3-2

Only this model's values, from the EMEA 2026 catalogue table.

**IST3-2 · Technical data**

|  |  |
| --- | --- |
| Rating |  |
| Power (VA / W) | 2000 / 2000 |
| Efficiency (AC/AC) | up to 92.6% · 98.3% in ECO mode |
| Input |  |
| Voltage range | 176–295 V full load · 154–176 V load < 75% · 120–154 V load < 50% |
| Frequency · connection | 50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE |
| Output |  |
| Voltage | 220 V ± 2% (default) · 208 / 220 / 230 / 240 V settable from the panel |
| Frequency · waveform | 50 / 60 Hz ± 0.2% in battery mode · sine wave |
| Voltage distortion | THD < 3% (linear load) |
| Power factor · transfer time | 1.0 (kVA = kW) · 0 ms mains to battery |
| Overload | 100–130% 1 min · 130–150% 1 s · > 150% 200 ms |
| Battery |  |
| Voltage, standard model | 48 V |
| Voltage, long backup model | 72 V |
| Backup time, standard model | 3 min at full load |
| Charge recovery | standard model < 10 h · long backup: depends on the battery pack |
| General |  |
| Communication | RS232 and USB standard · SNMP card or RS485 and dry-contact card optional · EPO |
| Protections | battery undervoltage, overload, short circuit, over-temperature, input overvoltage |
| Noise | < 50 dB |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 1000 m without derating |
| Dimensions W × D × H, standard | 190 × 397 × 330 |
| Dimensions W × D × H, long backup | 190 × 397 × 330 |
| Weight standard / long backup (kg) | 17.6 / 9.0 |

**IST3-2 · Models**

| Item | IST3-2 |
| --- | --- |
| VA / W | 2000 / 2000 |
| Internal batteries | 4 × 9 Ah · 48 V |
| Backup, full / half load | 3 min |
| W × D × H (mm) | 190 × 397 × 330 |
| kg | 17.6 |
| Long backup: battery | 72 V |
| Long backup: kg | 9.0 |

Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST3-2

**Ordering codes IST3-2**

| Code | Description |
| --- | --- |
| IST3-1-2X9 · IST3-2-4X9 · IST3-3-6X9 | Standard models with internal 12 V 9 Ah batteries (2, 4, 6) |
| IST3-1-L · IST3-2-L · IST3-3-L | Long backup, external batteries only (36 / 72 / 96 V) |
| IST3-\[kVA\]-\[n\]X9 | UPS with battery cabinet BB1, BB2 or BB3, n × 12 V 9 Ah in total |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| MBYP-3K · MBYP-6K | External manual maintenance bypass, rack, max. 3 kVA · max. 10 kVA |

Questions

## Questions about the IST3-2

#### Can I add batteries to the IST3-2?

Yes. The BB2 tower cabinet, same colour and front as the UPS, holds up to 12 × 12 V 9 Ah (code IST3-2-12X9). The long backup model IST3-2-L (9.0 kg) has no internal batteries and connects to a 72 V external string.

#### Which loads should not go on the IST3-2?

The catalogue excludes unbalanced, half-wave rectified or inductive loads such as air conditioners, motors, drills and fluorescent lamps. IT, network and electronic loads are what it is built for.

#### How long does a 2 kVA UPS like the IST3-2 run?

2 to 41 minutes at full load (2 kW), and 8 to 101 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 4 × 12 V 9 Ah (IST3-2-4X9): 2 minutes at 100% and 8 at 50%. For other loads and batteries use the backup-time tool.

#### How big is the AEC IST3-2 and how much does it weigh?

The AEC IST3-2 measures 190 × 397 × 330 mm; weight: 17.6 / 9.0 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST3-2?

In the EMEA 2026 catalogue the AEC IST3-2 is listed as IST3-2-4X9, IST3-2-L; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST3

[The whole range](https://www.aecups.com/en/products/ist3/)

[**IST3-1** 1 kVA · smaller rating](https://www.aecups.com/en/products/ist3/ist3-1k/) **IST3-2** 2 kVA [**IST3-3** 3 kVA · larger rating](https://www.aecups.com/en/products/ist3/ist3-3k/) [**IST3-6** 6 kVA](https://www.aecups.com/en/products/ist3/ist3-6k/) [**IST3-10** 10 kVA](https://www.aecups.com/en/products/ist3/ist3-10k/)

Batteries and cabinets: [BB2](https://www.aecups.com/en/products/battery-cabinets/bb2/) [OZ Power 12 V 9 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-9ah/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/) [External maintenance bypass](https://www.aecups.com/en/products/maintenance-bypass/)

Shared by the whole range, on the IST3 page: [the display simulator](https://www.aecups.com/en/products/ist3/#display) · [how the power flows in each mode](https://www.aecups.com/en/products/ist3/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist3/#gallery).

Read next: [How to choose a UPS: type, runtime, phases and service](https://www.aecups.com/en/blog/how-to-choose-a-ups/) [Single- or three-phase UPS: which does your site need?](https://www.aecups.com/en/blog/single-vs-three-phase-ups/) [UPS sizing: how to work out the power you need](https://www.aecups.com/en/blog/ups-sizing/)