title: "Single-phase online UPS 6 kVA, tower, 230 V · IST3-6 | AEC"
url: https://www.aecups.com/en/products/ist3/ist3-6k/
description: "The IST3-6 is a 6 kVA / 6 kW single-phase online double-conversion tower UPS on wheels."
language: en
---

IST3 · Single-phase UPS

# IST3-6 Single-phase online UPS 6 kVA, tower, 230 V

VRLA 6 kVA online tower UPS, 230 V

The IST3-6 is a 6 kVA / 6 kW single-phase online double-conversion tower UPS on wheels, with 16 internal 12 V 9 Ah batteries and its own maintenance bypass. For server rooms, laboratories and small plants with a single-phase supply and loads up to about 5 kW.

**6 kVA / 6 kW** Rating

**230 × 524 × 553 mm** W × D × H

**54.5 / 11.0 kg** Weight

**192 V (16–20 × 12 V settable)** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=13) [Contact us](https://www.aecups.com/en/contacts/?interest=Single-phase%20UPS&msg=About%20the%20AEC%20IST3-6%20(IST3)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist3-6/v68/)

Quick answers

## IST3-6: quick answers

**What it is**: The IST3-6 is a 6 kVA / 6 kW single-phase online double-conversion tower UPS on wheels, with 16 internal 12 V 9 Ah batteries and its own maintenance bypass.

**Who it is for**: For server rooms, laboratories and small plants with a single-phase supply and loads up to about 5 kW.

**Supply and configuration**: 208 / 220 / 230 / 240 V

**Battery and backup**: 192 V (16–20 × 12 V settable) · 5–20 min full / half load

**Size and weight**: 230 × 524 × 553 mm · 54.5 / 11.0 kg

**Ordering code**: IST3-6-16X9 · IST3-6-L

IST3

## What sets apart the IST3-6

At 6 kVA the IST3 changes construction: input, output and battery connect on a terminal bar, not on sockets, and the standard model carries a maintenance bypass switch, so the battery can be replaced with the load on. The 192 V battery of 16 × 9 Ah gives 4 minutes at full load and 13 at half load in AEC's data (the catalogue prints 5 and 20); the string can be set from 16 to 20 blocks.

The input window is 176–275 V at full load, with linear derating down to 80 V, and the output distortion is below 1% on linear load. Overload is held longer than on the small models: 105–130% for 10 minutes (1 minute above 30 °C). The long backup model is a compact 190 × 429 × 337 mm box of 11.0 kg.

- **Against the IST3-3** (one size down): Power 6000 VA / 6000 W against 3000 VA / 3000 W; Voltage range 176–275 V full load · 80–176 V linear derating against 176–295 V full load · 154–176 V load < 75% · 120–154 V load < 50%; Voltage distortion THD < 1% linear · < 4% non-linear against THD < 3% (linear load); Overload 105–130% 10 min (1 min above 30 °C) · 130–150% 30 s · > 150% 500 ms against 100–130% 1 min · 130–150% 1 s · > 150% 200 ms; Voltage, standard model 192 V (16–20 × 12 V settable) against 72 V.
- **Against the IST3-10** (one size up): Power 6000 VA / 6000 W against 10000 VA / 10000 W; Backup time, standard model 5–20 min full / half load against 1–15 min full / half load; Weight standard / long backup 54.5 / 11.0 kg against 56.2 / 12.5 kg.

Planning data

## IST3-6: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-6.

### Wall socket or terminal bar

**IST3-6 · Wall socket or terminal bar**

| Model | 6 kVA |
| --- | --- |
| AC input max. (A) | 36 |
| AC breaker (A) | 50 |
| DC input max. (A, long backup) | 39 |
| DC breaker (A) | 50 |
| AC cable (mm²) | 6 |
| Battery cable (mm²) | 6 |

Installation

## Installing the IST3-6: space, cables

Each figure with its source.

**IST3-6 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST3 user manual p.6 §1.2 |
| Cable entry | Rear terminal block | AEC IST3 user manual |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST3 user manual p.6 §1.2 |
| Switches and terminals | Terminal block (input, output, battery) under a cover at the rear; mains, bypass and battery breakers and the maintenance bypass switch on the rear panel (standard model). | AEC IST3 user manual p.6 §1.2 |

Size and floor

## How big it is

230 × 524 × 553 mm · 54.5 / 11.0 kg.

**0.12 m²** footprint

**91–452 kg/m²** floor load

**0.55 m** height

Floor load = weight ÷ footprint: 91 kg/m² at the lowest weight given (11 kg), 452 kg/m² at the highest (54.5 kg).

Efficiency

## How efficient is the AEC IST3-6 at your load?

IST3-6, 6 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 50%: 0.19 kW (η 94.05%) · 75%: 0.21 kW (η 95.5%) · 100%: 0.30 kW (η 95.3%). At 50% load, 24/7, it loses about 1,663 kWh a year.

**95.5** % 75% · Typical curve, derived from the datasheet efficiency of 95.5% (AEC method)

How the curve is drawn and where each figure comes from: [the IST3 range page](https://www.aecups.com/en/products/ist3/#efficiency). The IST3 pages of the EMEA 2026 catalogue give no efficiency figure. The 1, 2 and 3 kVA curves are the ones AEC measured on the IST3-J of the same rating (AEC technical datasheet IST3-J 1–3 kVA), which AEC states has the same electronics; the 6 and 10 kVA curve has the same shape, moved to their 95.5% figure.

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3% | Typical curve, derived from the datasheet efficiency of 95.5% (AEC method) | IST3-6 · IST3-10 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| ECO | 98.3% | Datasheet figure, load not stated | all | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83% | Measured (AEC datasheet) | IST3-1 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56% | Measured (AEC datasheet) | IST3-2 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1% | Measured (AEC datasheet) | IST3-3 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |

Drag to turn

In 3D

## Look around the IST3-6

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist3-6/v68/)

Technical data

## Technical data IST3-6

Only this model's values, from the EMEA 2026 catalogue table.

**IST3-6 · Technical data**

|  |  |
| --- | --- |
| Rating |  |
| Power (VA / W) | 6000 / 6000 |
| Efficiency (AC/AC) | up to 95.5% · 98.3% in ECO mode |
| Input |  |
| Voltage range | 176–275 V full load · 80–176 V linear derating |
| Frequency · connection | 50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE |
| Output |  |
| Voltage | 220 V ± 2% (default) · 208 / 220 / 230 / 240 V settable from the panel |
| Frequency · waveform | 50 / 60 Hz ± 0.2% in battery mode · sine wave |
| Voltage distortion | THD < 1% linear · < 4% non-linear |
| Power factor · transfer time | 1.0 (kVA = kW) · 0 ms mains to battery |
| Overload | 105–130% 10 min (1 min above 30 °C) · 130–150% 30 s · > 150% 500 ms |
| Battery |  |
| Voltage, standard model | 192 V (16–20 × 12 V settable) |
| Voltage, long backup model | 192 V |
| Backup time, standard model | 5–20 min full / half load |
| Charge recovery | standard model < 10 h · long backup: depends on the battery pack |
| General |  |
| Communication | RS232 and USB standard · SNMP card or RS485 and dry-contact card optional · EPO |
| Protections | battery undervoltage, overload, short circuit, over-temperature, input overvoltage |
| Noise | < 55 dB |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 1000 m without derating |
| Dimensions W × D × H, standard | 230 × 524 × 553 mm |
| Dimensions W × D × H, long backup | 190 × 429 × 337 mm |
| Weight standard / long backup (kg) | 54.5 / 11.0 |

**IST3-6 · Models**

| Item | IST3-6 |
| --- | --- |
| VA / W | 6000 / 6000 |
| Internal batteries | 16 × 9 Ah · 192 V |
| Backup, full / half load | 5 / 20 min |
| W × D × H (mm) | 230 × 524 × 553 |
| kg | 54.5 |
| Long backup: battery | 192 V |
| Long backup: kg | 11.0 |

Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST3-6

**Ordering codes IST3-6**

| Code | Description |
| --- | --- |
| IST3-6-16X9 · IST3-10-16X9 | 6 / 10 kVA with 16 internal 12 V 9 Ah batteries |
| IST3-6-L · IST3-10-L | Long backup 6 / 10 kVA, external batteries only |
| IST3-\[kVA\]-\[n\]X9 | UPS with battery cabinet BB1, BB2 or BB3, n × 12 V 9 Ah in total |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| MBYP-3K · MBYP-6K | External manual maintenance bypass, rack, max. 3 kVA · max. 10 kVA |

Questions

## Questions about the IST3-6

#### How long does the IST3-6 run on its internal batteries?

4 minutes at full load and 13 at half load with 16 × 12 V 9 Ah (192 V), in AEC's data (the catalogue prints 5 and 20). A BB3 tower cabinet adds up to 32 × 12 V 9 Ah, and more than one BB3 can be connected for longer backup.

#### What does the IST3-6 need on the supply side?

A single-phase L + N + PE supply with a 50 A breaker (36 A maximum input current) and a 6 mm² cable for about 5 m, earth cable of the same section. The long backup model draws up to 39 A from the battery on a 50 A DC breaker.

#### How long does a 6 kVA UPS like the IST3-6 run?

4 to 47 minutes at full load (6 kW), and 13 to 113 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 16 × 12 V 9 Ah (IST3-6-16X9): 4 minutes at 100% and 13 at 50%. For other loads and batteries use the backup-time tool.

#### How big is the AEC IST3-6 and how much does it weigh?

The AEC IST3-6 measures 230 × 524 × 553 mm; weight: 54.5 / 11.0 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST3-6?

In the EMEA 2026 catalogue the AEC IST3-6 is listed as IST3-6-16X9, IST3-6-L; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST3

[The whole range](https://www.aecups.com/en/products/ist3/)

[**IST3-1** 1 kVA](https://www.aecups.com/en/products/ist3/ist3-1k/) [**IST3-2** 2 kVA](https://www.aecups.com/en/products/ist3/ist3-2k/) [**IST3-3** 3 kVA · smaller rating](https://www.aecups.com/en/products/ist3/ist3-3k/) **IST3-6** 6 kVA [**IST3-10** 10 kVA · larger rating](https://www.aecups.com/en/products/ist3/ist3-10k/)

Batteries and cabinets: [BB3](https://www.aecups.com/en/products/battery-cabinets/bb3/) [OZ Power 12 V 9 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-9ah/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/) [External maintenance bypass](https://www.aecups.com/en/products/maintenance-bypass/)

Shared by the whole range, on the IST3 page: [the display simulator](https://www.aecups.com/en/products/ist3/#display) · [how the power flows in each mode](https://www.aecups.com/en/products/ist3/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist3/#gallery).

Read next: [How to choose a UPS: type, runtime, phases and service](https://www.aecups.com/en/blog/how-to-choose-a-ups/) [Single- or three-phase UPS: which does your site need?](https://www.aecups.com/en/blog/single-vs-three-phase-ups/) [UPS sizing: how to work out the power you need](https://www.aecups.com/en/blog/ups-sizing/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST3-6: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Single-phase%20UPS&msg=About%20the%20AEC%20IST3-6%20(IST3)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)