title: "Modular UPS 30–120 kVA, 30 kVA modules · IST6-120 | AEC"
url: https://www.aecups.com/en/products/ist6-120/
description: "IST6-120 30–120 kVA: modular online UPS, double conversion. Start with one 30 kVA power module, grow to 120 kVA in the same cabinet."
language: en
---

Modular UPS · 400 V

# IST6-120 Modular UPS 30–120 kVA, 30 kVA modules

VRLA Online double conversion

The AEC IST6-120 is a modular online double-conversion UPS from 30 to 120 kVA in one cabinet: it grows in 30 kVA steps with hot-swappable 2U power modules, and the fifth slot takes a module for N+1 redundancy. For 400 V supplies, with 97% efficiency in double conversion and up to 99% in ECO mode.

**30→120** kVA in 30 kVA steps

**N+1** fifth slot for redundancy

**97%** double-conversion efficiency

**Hot-swap** modules replaced online

Datasheet Manuals and catalogues [Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6-120%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist6-120/v69/)

Drag to turn

In 3D

## Look around the IST6-120

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist6-120/v69/)

Rendered from AEC's 3D model of the IST6 120 kVA. The full 3D view zooms in, opens the unit and names every part.

Hands on

## Open the IST6 120 kVA yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

[Every part in 3D](https://www.aecups.com/assets/models3d/ist6-120/v69/)

Efficiency

## How efficient is the AEC IST6-120 at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

**97** % 50% · Typical curve, derived from the datasheet efficiency of 97% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 96.4% · 50%: 97% · 75%: 96.7% · 100%: 96.4% | Typical curve, derived from the datasheet efficiency of 97% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Online, double conversion up to 97% · ECO up to 99%.

The display

## The IST6 30–120 kVA display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

UPS state

IST6 30–120 kVA · the real display

### Normal operation

**Main pages**

What is what

## Inside the IST6-120, part by part.

Each number on the picture is named in the list.

### Front, door open

Everything is reached from the front: power modules, system control box and the four switches. Cables enter from the bottom (top entry with an accessory).

1. **Power modules** 30 kVA each, 2U, hot-swap: rectifier, inverter and battery converter in every module.
2. **System control box** Two control cards, monitor card, SNMP and expansion slots: 4 dry-contact inputs and 3 outputs (7 + 5 with the expansion card), Modbus, RS232, RS485, 2 EPO inputs (NO and NC).
3. **Battery cold start** Starts the UPS from the battery when there is no mains and no bypass.
4. **Mains switch** The rectifier's mains supply.
5. **SPD and SPD switch** Optional class C surge protection device with its own switch, inside the cabinet.
6. **Output switch** To the load.
7. **Bypass switch** The static bypass supply.
8. **Maintenance bypass switch** Manual bypass with no switching time, for service with the load running.

Overview

## Key facts

**Power range**: 30–120 kVA

**Input / output**: 3/3 · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L

**Efficiency**: 97% double conversion · up to 99% ECO

**Battery**: ±168 … ±276 V DC · ±14 … ±23 × 12 V (default ±16; below ±16 load 80%)

**Display**: 7" colour touch screen

**Communication**: Modbus · RS232 · RS485 · 4 dry-contact inputs, 3 outputs

**Network card**: SNMP card (optional)

**Parallel**: with parallel kit, ring cables; BSC dual bus

**Warranty**: 3 years

**Dimensions W × D × H**: 600 × 860 × 2000 mm

[Applications](https://www.aecups.com/en/applications/): Data centres Telecom Banking & finance Networks & IT rooms Transport Public buildings

Pictures

## The IST6-120 in pictures

The photos and drawings of the EMEA 2026 catalogue: product views, displays, modules and connections. Tap a picture to enlarge it.

Models

## Which IST6-120 fits your load?

Every rating has its own page: that model's technical data, ordering codes, batteries and the questions people ask.

[**IST6-120, 1 × 30 kVA** 30 kVA The IST6-120 with one 30 kVA power module is a 30 kVA / 30 kW modular online UPS: a 600 × 860 × 2000 mm cabinet with five slots, one of them used. **600 × 860 × 2000 mm**Size **195 kg + 1 × 24 kg module**Weight See the model](https://www.aecups.com/en/products/ist6-120/ist6-30k-1x30/) [**IST6-120, 2 × 30 kVA** 60 kVA The IST6-120 with two 30 kVA power modules is a 60 kVA / 60 kW modular online UPS in a 0.52 m² cabinet, with room for two more modules and a redundancy slot. **600 × 860 × 2000 mm**Size **195 kg + 2 × 24 kg modules**Weight See the model](https://www.aecups.com/en/products/ist6-120/ist6-60k-2x30/) [**IST6-120, 3 × 30 kVA** 90 kVA The IST6-120 with three 30 kVA power modules is a 90 kVA / 90 kW modular online UPS; with a fourth module it becomes 90 kVA N+1 in the same cabinet. **600 × 860 × 2000 mm**Size **195 kg + 3 × 24 kg modules**Weight See the model](https://www.aecups.com/en/products/ist6-120/ist6-90k-3x30/) [**IST6-120, 4 × 30 kVA** 120 kVA The IST6-120 with four 30 kVA power modules is the full 120 kVA / 120 kW modular online UPS, with a fifth slot for an N+1 module. **600 × 860 × 2000 mm**Size **195 kg + 4 × 24 kg modules**Weight See the model](https://www.aecups.com/en/products/ist6-120/ist6-120k-4x30/)

Datasheet

## Datasheet IST6-120.

Every model side by side: keep only what differs, take it as CSV or print it.

**IST6-120 · Technical data**

| Model | IST6-120 |
| --- | --- |
| General |  |
| Model | IST6-120 with IST6-30-J power modules |
| Rated power | 30 to 120 kVA / kW in 30 kVA steps (1–4 modules) + 1 redundancy slot |
| Topology | online double conversion, modular, hot-swap power modules, removable bypass module |
| Input |  |
| Connection · voltage | 3 ph + N + PE · 220 / 230 / 240 V L-N |
| Voltage range | 176–280 V full power · 80–176 V derated (linear load) |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 2% resistive, ≤ 3% non-linear full load |
| Bypass | 220 / 230 / 240 V L-N; synchronisation 50 / 60 Hz ± 6 Hz |
| Battery |  |
| Voltage · blocks | ±168 … ±276 V DC · ±14 … ±23 × 12 V (default ±16; below ±16 load 80%) |
| Charging current | 10 A × number of modules (max.) |
| Functions | cold start · standard / deep test · common battery · lithium with BMS card |
| Output |  |
| Connection · voltage | 3 ph + N + PE · 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L |
| Power factor · THDv | 1 · ≤ 1% linear, ≤ 4% non-linear |
| Frequency · phase error | tracks the bypass; 50 / 60 Hz ± 0.2% without mains · ≤ 1° (balanced load) |
| Transfer · dynamic response | 0 ms synchronised, < 15 ms not synchronised · < 5% for 0↔100% step |
| Inverter overload (PF 1) | ≤ 105% continuous · 106–110% 60 min · 111–125% 10 min · 126–150% 1 min · > 151% to bypass |
| Bypass overload | < 130% continuous · 131–150% 5 min · 151–200% 1 s · 201–300% 100 ms |
| Unbalanced load | 100% |
| System |  |
| Efficiency | 97% double conversion · up to 99% ECO |
| Display · records | 7" colour touch screen · 10,000 events · 5 LEDs · status light bar |
| Communication | Modbus · RS232 · RS485 · 4 dry-contact inputs, 3 outputs · options: SNMP, dry-contact expansion, BMS card |
| Parallel | with parallel kit, ring cables; BSC dual bus |
| Environment | −5 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 65 dB · EMC class C3 |
| Dimensions W × D × H | 600 × 860 × 2000 mm · cable entry bottom (top with accessory) |
| Weight | cabinet without power modules 195 kg · power module 24 kg · bypass module 17 kg |

Data from the IST6 120 kVA user manual. Specifications are subject to change without notice.

#### **Full technical details** 18 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

### Why IST6-120

01 **30→120 · Modules added as the load grows** Buy the power you need today. Add 30 kVA modules in the same cabinet when the load grows, with no new footprint.

02 **N+1 · Redundancy built in** Four power modules plus a redundancy slot for a fifth module, two system control cards (main and secondary) and a centralised bypass module.

03 **Hot-swap · Service without shutdown** Power modules are inserted and removed online. A faulty power module is isolated automatically; normally the others carry the load.

04 **99% · Efficiency that pays back** 97% in double conversion, up to 99% in ECO mode, plus a redundancy sleep function set from the screen.

05 **±14…±23 · Battery set on site** 28 to 46 × 12 V blocks (default ±16), charging current up to 10 A per module, lead-acid or lithium with the BMS card.

06 **7" · Easy to run** Colour touch screen with live power-flow topology, module-by-module data and 10,000 event records.

OPERATING COST

## What efficiency means at 96 kW

Losses become heat: you pay for them at the meter and again in the room cooling.

- IST6 120 kVA at 80% load (96 kW), 8,760 h/year, € 0.20/kWh, cooling excluded; losses = P × (1/η − 1). Indicative values.

**What efficiency means at 96 kW**

| Mode | Losses | Energy lost / year | Cost / year |
| --- | --- | --- | --- |
| Online double conversion · 97% | 2.97 kW | 26,010 kWh | ≈ € 5,200 |
| ECO mode · 99% | 0.97 kW | 8,490 kWh | ≈ € 1,700 |

SCALABILITY

## Power added one 30 kVA module at a time

The cabinet is the same from the first module to the last: power is added by sliding a 30 kVA module into a free slot.

- 30, 60, 90 or 120 kVA: add 30 kVA power modules (2U) in the free slots of the same cabinet; modules slide in from the front.
- Redundancy N+1: install one module more than the load needs; if a module stops, the others carry the load without transfer to bypass.
- Slots are numbered 1 to 5 from bottom to top; the fifth is the redundancy slot.
- Beyond 120 kVA: several IST6 cabinets work in parallel with the parallel kit; cables in a ring, one display can monitor the whole system, and a common battery group can be shared.
- Codes: IST6-120 modular cabinet for up to 4 × 30 kVA power modules, supplied without modules; IST6-30-J 30 kVA / 30 kW power module, 2U, hot-swappable, order as many as the load needs; PAR - IST6 parallel kit for cabinets in parallel.

**Power added one 30 kVA module at a time**

| Load up to | Modules (N) | Modules for N+1 |
| --- | --- | --- |
| 30 kVA | 1 | 2 |
| 60 kVA | 2 | 3 |
| 90 kVA | 3 | 4 |
| 120 kVA | 4 | 4 + redundancy slot |

SCALE AND SLEEP

## 30 kVA steps, redundancy sleep at light load

Add 30 kVA modules or whole cabinets as the site grows; set redundancy and redundancy sleep from the screen.

- Step size 30 kVA: one 2U module at a time, added online in a free slot.
- 4 + 1 slots per cabinet: four power modules plus a dedicated redundancy slot.
- More cabinets in parallel with the parallel kit, cables in a ring.
- N+X, two redundancy levels: basic and redundant modules per cabinet and cabinets per system.
- Redundancy sleep (Smart mode › Sleep redundancy): spare modules can sleep at light load, with a sleep cycle period (h) and a sleep safety load capacity (kVA) set on screen; an alarm warns if the load exceeds the safety load.
- Run information shows the parameter match between cabinets and the state of both system cards; module data is shown module by module.
- Alarms when module or cabinet redundancy is missing or insufficient, and when a system card has no redundancy.
- Over RS485, the integrated display can monitor the other UPS of a parallel system.
- Modules and further cabinets are added and configured by AEC service.

INSIDE THE CABINET

## Every module in front, everything modular

Power modules, bypass module, control box and switches are all reached from the front of the cabinet.

- 1 Redundancy slot: space for the N+1 module.
- 2 Power modules 1–4: 30 kVA each, 2U, hot-swap.
- 3 Bypass module: centralised static bypass, 3U, removable.
- 4 System control box: two control cards, monitor card, SNMP and expansion slots.
- 5 Battery cold start: starts the UPS from the battery with no mains and no bypass.
- 6 Mains switch; 7 surge protection switch (optional); 8 SPD (optional surge protection device); 9 output switch; 10 bypass switch; 11 maintenance bypass switch (manual bypass with no switching time).
- Power module: 30 kVA, 2U, 86 × 500 × 700 mm (H × W × D, with handles), 24 kg; rectifier, inverter and battery converter in each module.
- Bypass module: centralised, 3U, 130 × 500 × 635.5 mm, 17 kg; static bypass for the whole cabinet, with its own ready switch.
- Cabinet: 600 × 860 × 2000 mm; four switches as standard (mains, bypass, output, maintenance bypass); SPD optional; IP20.

HOT-SWAP

## Replace a module with the load running

Every power module has a ready switch and three status LEDs: power modules are replaced without shutting down the UPS.

- Power module front: ventilation grille, RUN / ALARM / FAULT LEDs, ready switch and handles; the bypass module has the same LEDs and ready switch.
- LEDs: green, inverter on (flashing: standby); yellow, input voltage, fan or overload alarm; red, module fault.
- A faulty power module is isolated automatically; normally the system continues on the other modules, with reduced redundancy.
- No master, no slave: modules share the load equally under digital control; any module can be removed or added online.
- Power module 2U, 24 kg; bypass module 3U, removable; 0 UPS shutdowns to add or replace a power module.
- Wait at least 10 minutes after removal before opening a module. Replacement by AEC or authorised personnel.

ARCHITECTURE

## Online double conversion in every module

N power modules (rectifier, inverter, DC/DC) and one bypass module, with a manual maintenance bypass.

- Mains mode: the PFC rectifier of each module builds the DC bus, the three-level inverter rebuilds a clean sine wave; the battery is charged at the same time.
- Battery mode: with the mains abnormal, the battery converter boosts the battery onto the DC bus; the output continues without a break.
- Bypass and maintenance: the bypass module transfers the load on overload or fault; the manual maintenance bypass keeps the load supplied during service.
- Fully digital DSP control of inverter, synchronisation, current sharing and module logic.
- Three-level inverter: THDv ≤ 1% on linear load, ≤ 4% on non-linear load.
- Two control cards (main and secondary system control cards); an alarm warns if one is missing.
- Short-circuit restart: after an output short circuit the UPS retries up to three times before protection.
- Input power factor ≥ 0.99; input THDi ≤ 3% at non-linear full load; 0 ms transfer when synchronised; 100% unbalanced load.

SMART ENERGY

## Efficiency features, from ECO to redundancy sleep

ECO mode: the load runs on the bypass while it is within the set window; outside it, the inverter takes over. Efficiency up to 99%.

- Grid-tied aging: a dedicated test state for commissioning, shown live on the home page, with its own alarms (self-load switch, time-out).
- Output set: bypass range, ECO voltage (e.g. ±5%) and frequency (e.g. ±4%) windows; Timing ECO for scheduled operation.
- Cooling: fan speed follows the load to extend fan life and reduce noise; a fan dedusting alarm is provided.
- Generator mode: dry contacts start a generator on mains failure; charging can be disabled while on generator.
- Timing ECO: ECO mode by schedule, set from the output settings.
- 97% efficiency in double conversion, up to 99% in ECO mode.

**Efficiency features, from ECO to redundancy sleep**

| Page | Setting | What it does |
| --- | --- | --- |
| Smart mode | Redundancy sleep · cycle period · safety load | Sleep function for redundant modules |
| Smart mode | Generator | Generator operation and charging control |
| Output set | ECO voltage and frequency range | Window in which the load stays on bypass |
| Output set | Timing ECO | ECO mode by schedule |
| Dry contact | Start generator · mains abnormal | Generator start and status signals |

PERFORMANCE

## Full power from 176 to 280 V

Full power from 176 to 280 V phase voltage; down to 80 V the UPS keeps working from the mains with derated power.

- Linear load: rated power decreases between 80 and 186 V. Input frequency 40–70 Hz.
- Input THDi ≤ 3% at non-linear full load.
- Inverter overload (linear load, PF 1): ≤ 105% continuous, 106–110% 60 min, 111–125% 10 min, 126–150% 1 min; above 151% transfer to bypass at once. PF 0.9: 106–110% 60 min, above 110% to bypass at once; PF 0.8: above 105% to bypass.
- Bypass overload: < 130% continuous, 131–150% 5 min, 151–200% 1 s, 201–300% 100 ms; above 300% immediate protection.

**Full power from 176 to 280 V**

| Output quality | Value |
| --- | --- |
| Voltage | 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L |
| THDv | ≤ 1% linear · ≤ 4% non-linear |
| Phase error | ≤ 1° balanced load |
| Frequency, no mains | 50 or 60 Hz ± 0.2% |
| Load step 0↔100% | voltage change < 5% |
| Unbalanced load | 100% |
| Transfer | 0 ms synchronised · < 15 ms not synchronised |

BATTERIES

## One battery strategy for every site

A split battery (+ / N / −) of ±14 to ±23 blocks of 12 V: ±168 to ±276 V DC. With fewer than ±16 blocks the output load is limited to 80%.

- Charging current 10 A per power module (max.); 40 A with four modules.
- Live battery information: voltage and current of each half string, remaining capacity and time, temperature, status.
- Lithium: optional BMS expansion card, with BMS port plus charge- and discharge-disable inputs for lithium battery systems.
- Common battery: in parallel systems one battery group can be shared by all cabinets (parameter set on screen).
- Battery cold start button: the UPS starts from the battery with no mains and no bypass.
- Options: battery temperature sensor for charge compensation; battery tripper control (24 V DC) for the DC breaker.
- First battery charge 24 h (UPS usable meanwhile); best battery temperature 20–30 °C.

**One battery strategy for every site**

| Battery setting | Value |
| --- | --- |
| Battery type | lead-acid; lithium with BMS card |
| Blocks per string | ±14 … ±23 × 12 V (default ±16) |
| Charging current | 10 A × number of modules (max.) |
| Equalising / floating | 2.350 / 2.270 V/cell (example screen) |
| Under-voltage alarm / protection | 1.950 / 1.667 V/cell (example screen) |
| Battery test | standard or deep, from the screen |

OPERATOR PANEL

## Seven-inch touch screen, LEDs and light bar

A seven-inch colour touch screen, five status LEDs, two-key ON / OFF commands and a status light bar.

- Colour touch screen, seven inches: live power flow, measurements, settings and records.
- Five status LEDs (AC/DC, DC/AC, bypass, battery, load): green when normal or active, red when abnormal.
- ON keys: press both keys for 3 s to power on, no accidental switching; OFF keys: press both keys for 3 s to power off.
- Status light bar, four states: blue, normal operation; blue flashing, battery mode; yellow, abnormal with UPS still running; red, abnormal with UPS stopped. Alarms also light the yellow or red ambient lamp.
- Screen settings: date and time, backlight time, language, brightness.

Tap a light: green is normal operation, red an abnormal state, as in the catalogue's table.

AC/DC: green, Rectifier normal

**Seven-inch touch screen, LEDs and light bar**

| LED | Green | Red |
| --- | --- | --- |
| AC/DC | Rectifier normal | Rectifier abnormal |
| DC/AC | Inverter normal | Inverter abnormal |
| Bypass | Bypass output | Bypass abnormal |
| Battery | Battery output | Battery low voltage |
| Load | Output normal | Output overload |

TOUCH SCREEN

## Touch a block, read its measurements

The home page draws the UPS as it runs: yellow dots trace the active power path, abnormal blocks turn red, and the bottom line shows output voltage and frequency. Touch a block (bypass, mains, battery, rectifier, inverter, output) to open its page.

- Bypass info: phase and line voltage, current and frequency of the bypass input.
- Mains info: phase and line voltage, current, frequency and input energy.
- Battery info: voltage, charge and discharge current, remaining capacity and time, temperature, state.
- Inverter info: output voltage, current, power and load of each module.
- Information menu: run info, history record, user log, smart record, device info, smart wave record.
- Settings menu: cabinet, battery, battery test, output, smart mode, dry contact, HMI, password, communication, records.
- Run information: system info, parameter match, system status, system cards 1 and 2.
- Output info: voltage, current, active and apparent power, load, PF, frequency and output energy.
- 10,000 records in the history, newest first; 6 live info pages (mains, bypass, rectifier, inverter, battery, output); live single-line diagram with the active power path; 3 s two-key ON / OFF commands.

RECORDS

## 10,000 events in the history

10,000 records in the history, newest first. When the record is full, the earliest entry is overwritten.

- Total input and output energy (MWh) on the information pages.
- Run information: parameter match between cabinets and state of both system cards.
- Current fault: active faults, time-stamped, from the alarm icon of the menu bar.
- Device info: hardware and software versions of screen and system cards.
- Record management: history record, user log, smart record and smart wave record are kept in the UPS and saved or cleared from the record manage page.
- User log: parameter changes with date and time. Smart wave record: waveforms of abnormal events.
- Further screens: battery test, communication set, HMI set.

OPERATION

## Every operating state, shown live

Real screens of the IST6: the yellow dotted line traces the active power path.

- Mains inverter: normal operation, mains → rectifier → inverter → load, battery charging.
- Battery inverter: mains abnormal, the battery feeds the inverter with no break.
- Bypass: load on the bypass module, e.g. on overload or inverter fault.
- ECO: load on the bypass within the ECO window; the rectifier keeps the battery charged.
- Grid-tied aging: test state shown live, with its own alarms.
- Maintenance bypass: load on the manual bypass, modules ready for service.
- Transfers: mains → battery with no break (the modules move to the battery input); inverter ↔ bypass 0 ms synchronised, < 15 ms not synchronised; inverter output state shown (Transducer INV. output).
- Start from battery: with no mains and no bypass, the battery cold start button starts the UPS from the battery.
- Mains outside range: the UPS starts from the mains between 80 and 280 V; outside this range it starts from the battery.

CONNECTIVITY

## 4 dry-contact inputs, 3 outputs, SNMP

The system control box holds the expansion card position (optional), the SNMP card position (optional), control cards 1 and 2 and the system monitor card.

- 4 dry-contact inputs (NO) and 3 outputs (NO / NC) as standard, each assigned from the screen; 7 + 5 with the expansion card.
- Inputs: battery abnormal, battery earth fault, battery switch disconnected, bypass switch disconnected, mains abnormal (generator start), input SPD abnormal.
- Outputs: inverter output, bypass output, battery output, battery trip, battery under-voltage alarm, battery under-voltage protection, output overload, UPS fault, bypass abnormal, mains abnormal, start generator.
- Modbus, RS232 · RS485 · SNMP; 2 EPO inputs (NO and NC).

PARALLEL AND DUAL BUS

## Parallel systems and dual bus

Parallel cables connect the control cards in a ring: N UPS need N cables, at least two per UPS, which improves parallel reliability.

- Dual bus with BSC: two independent systems feed dual-input loads; the BSC keeps their outputs synchronised in frequency and phase, so that the loads can switch between them.
- Common battery group: all cabinets can share one battery group; the UPS checks that battery parameters match.
- EPO linkage: enabled, the EPO of any cabinet stops the whole system; disabled, it stops only that cabinet. The system EPO always stops all cabinets.
- Separate mains and bypass: mains and bypass can come from different sources; the link bars are removed at installation.
- Parallel commissioning: phase-voltage difference between UPS below 5 V before paralleling; output of each UPS within ± 2 V and ± 0.1 Hz of its setting; same wiring and phase sequence on every cabinet.
- Redundancy at two levels: N+1 inside each cabinet; at cabinet level, alarms warn if the system has no redundancy or insufficient redundancy. Two control cards in every cabinet.
- Ring parallel cable topology; BSC dual bus synchronisation; one shared battery group possible; over RS485 one display monitors all UPS.

INSTALLATION AND SERVICE

## Quick to install, supported for years

Footprint 600 × 860 mm, height 2000 mm; four Ø14 mm holes to floor or U-steel base.

- Cables from the bottom as standard; from the top with the top wiring accessory (sections below 120 mm²), mounted on both sides of the cabinet and needing side space.
- Clearance ≥ 800 mm front and rear, ≥ 500 mm above; keep the front and rear ventilation openings clear.
- −5 … 40 °C, 0–95% RH non-condensing, up to 2000 m (derating above, [IEC 62040-3](https://webstore.iec.ch/en/publication/60140)), IP20, < 65 dB.
- Optional class C surge protection with its own switch, inside the cabinet.
- Cables from the IST6 120 kVA user manual; size on site according to local rules and cable length.
- Sizing: modules, redundancy, battery and parallel system sized by AEC engineers.
- Commissioning: start-up, settings, dry-contact functions and access passwords.
- Maintenance: quarterly preventive checks; terminal contacts checked every 6 months; fans checked.
- Expansion: new power modules added online; further cabinets added with the parallel kit by AEC service.
- 24/7 AEC technical assistance by phone and WhatsApp; < 30 min WhatsApp reply to technical and commercial questions; 3 years warranty, extendable with a maintenance contract; 21+ countries with spare parts across the Allis Electric group.
- AEC service: service@aecups.com · +39 393 080 5211 · www.aecups.com

**Quick to install, supported for years**

| Line | Current | Cable |
| --- | --- | --- |
| Mains input | 213 A | 1 × (4 × 120) mm² |
| Bypass input | 182 A | 1 × (4 × 95) mm² |
| Output | 182 A | 1 × (4 × 95) mm² |
| Battery (±16 blocks) | 330 A nom. · 377 A max. | 1 × (3 × 95) mm² |

### Ordering codes IST6-120

| Code | Description |
| --- | --- |
| `IST6-120` | Modular cabinet, max. 4 × 30 kVA power modules, supplied without modules |
| `IST6-30-J` | 30 kVA / 30 kW power module |
| `PAR - IST6` | Parallel kit |

Diagrams

## The IST6-120, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

### How the power flows

Pick an operating mode: the path the power takes to the load lights up.

**Normal.** Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 97%.

### The ratings

Every model in the range, in proportion to its power. Each notch is one 30 kVA module.

1. IST6-120 · 1 × IST6-30-J **30 kVA · 30 kW**
2. IST6-120 · 2 × IST6-30-J **60 kVA · 60 kW**
3. IST6-120 · 3 × IST6-30-J **90 kVA · 90 kW**
4. IST6-120 · 4 × IST6-30-J **120 kVA · 120 kW**

### Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 30 kVA module.

modules working · redundant · free slot

### Losses per 100 kW of load

Worked out as P × (1/η − 1) at the stated maximum efficiency, with the load steady all year.

1. Double conversion 97% **3.09 kW27,090 kWh/year**
2. ECO 99% **1.01 kW8,850 kWh/year**

### Phase configurations

Input / output: three-phase (3) or single-phase (1).

**3/3** 3~ → 3~

### Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

- **IST6-120 cabinet, without modules** 600 × 860 × 2,000 mm · 180 kg

Questions

## Questions people ask

#### How does the IST6-120 grow with the load?

The cabinet takes 30 kVA / 30 kW power modules (2U, 24 kg): 30, 60, 90 or 120 kVA with 1 to 4 modules, added online in free slots with no new footprint. Beyond 120 kVA, several IST6 cabinets work in parallel with the parallel kit.

#### How many modules do I need for N+1 redundancy?

Install one module more than the load needs: 2 modules for 30 kVA, 3 for 60 kVA, 4 for 90 kVA, and 4 plus a module in the dedicated fifth redundancy slot for 120 kVA. If a module stops, the others carry the load without transfer to bypass.

#### Can a power module be replaced without shutting down the UPS?

Yes: power modules are inserted and removed online, a faulty module is isolated automatically, and the 3U bypass module is removable. Wait at least 10 minutes after removal before opening a module; replacement is done by AEC or authorised personnel.

#### How efficient is the IST6-120?

97% in online double conversion and up to 99% in ECO mode, plus a redundancy sleep function for spare modules at light load. At 96 kW, AEC's indicative calculation gives 2.97 kW of losses in double conversion against 0.97 kW in ECO mode.

#### Which batteries does the IST6-120 use?

A split battery of ±14 to ±23 × 12 V blocks (±168 to ±276 V DC), default ±16; with fewer than ±16 blocks the load is limited to 80%. Charging current is up to 10 A per power module, lead-acid or lithium with the optional BMS card, and parallel cabinets can share one battery group.

#### What space does the IST6-120 need?

The cabinet measures 600 × 860 × 2000 mm and weighs 195 kg without power modules. Leave at least 800 mm at the front and rear and 500 mm above; cables enter from the bottom as standard, or from the top with the top wiring accessory.

#### Which communication options does the IST6-120 offer?

Modbus on RJ45, RS232, RS485, two EPO inputs and 4 dry-contact inputs / 3 outputs are standard (7 + 5 with the expansion card). An SNMP card with a temperature and humidity sensor port and a BMS expansion card are optional.

[All 17 questions](https://www.aecups.com/en/faq/ist6-120/)

In the same family: [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/) [IST6 400–1200](https://www.aecups.com/en/products/ist6-400-1200/) [Modular UPS](https://www.aecups.com/en/products/modular-ups/)

Guides

## Guides on the IST6-120

[All guides](https://www.aecups.com/en/blog/)

[**UPS installation clearances: what to check on site** Clearances, operating gangways, door widths, floor load, cable entry and airflow for every AEC EMEA UPS and battery cabinet, before the delivery.](https://www.aecups.com/en/blog/ups-installation-clearances/) [**How to choose a UPS: type, runtime, phases and service** How to choose a UPS once its size is known: online or line-interactive, runtime and shutdown, single- or three-phase, rack or tower, and service.](https://www.aecups.com/en/blog/how-to-choose-a-ups/) [**Modular UPS: how to grow power module by module** A modular UPS builds power from hot-swappable modules in one cabinet: how it grows with the load, against a conventional UPS, with IST6 examples.](https://www.aecups.com/en/blog/modular-ups/)

Read next: [UPS redundancy: N+1 or 2N, and how much a site needs](https://www.aecups.com/en/blog/ups-redundancy-n-plus-1/) [UPS for data centres: how to choose and plan](https://www.aecups.com/en/blog/ups-for-data-centres/) [UPS efficiency and ECO mode: losses and energy savings](https://www.aecups.com/en/blog/ups-efficiency-eco-mode/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST6-120 30–120 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6-120%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)