IST6 200–500 · Modular UPS

# IST6-400, 8 × 50 kVA Hot-swappable modular UPS, 400 V

VRLA 400 kVA modular online UPS, 50 kVA modules

The IST6-400 is a double-column modular online UPS cabinet for up to eight 50 kVA power modules: 400 kVA / 400 kW in 1203 × 864 × 2000 mm. For data centres and hospitals of 200 to 400 kW that prefer small 50 kVA steps, and fine N+1 granularity, at this power.

**400 kVA / 400 kW** Rating

**1203 × 864 × 2000 mm** W × D × H

**459 kg without modules** Weight

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=123) [Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6-400%2C%208%20%C3%97%2050%20kVA%20(IST6%20200%E2%80%93500)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist6-50m-400/v57/)

Quick answers

## IST6-400, 8 × 50 kVA: quick answers

**What it is**: The IST6-400 is a double-column modular online UPS cabinet for up to eight 50 kVA power modules: 400 kVA / 400 kW in 1203 × 864 × 2000 mm.

**Who it is for**: For data centres and hospitals of 200 to 400 kW that prefer small 50 kVA steps, and fine N+1 granularity, at this power.

**Supply and configuration**: 380 / 400 / 415 V

**Battery and backup**: ±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40

**Size and weight**: 1203 × 864 × 2000 mm · 459 kg without modules

**Ordering code**: IST6-400

IST6 200–500

## What sets apart the IST6-400, 8 × 50 kVA

400 kVA is also sold on the 100 kW-module frame, as a different product: the IST6 400 kVA with 4 × 100 kVA modules, one 801 × 1000 × 2000 mm column of 345 kg without modules, against this double column of 1203 × 864 × 2000 mm. AEC chooses the frame with you: 50 kVA modules spread the redundancy finer, 100 kVA modules take less floor.

The IST6-400 is the first double-column cabinet: 1203 mm wide, 459 kg without modules, with the power modules even above and odd below, a 3U bypass module and optional SPD with its own switch. Its 50 kVA step means N+1 at 350 kVA costs one 50 kVA module; the 400–1200 kVA range reaches 400 kVA with four 100 kVA modules instead.

Fully loaded it draws 690 A at the mains (2 × (4 × 185) mm², 800 A 3P breaker), 606 A at bypass and output and 868 A from a 40-block battery on 3 × (3 × 185) mm², and needs 4840 m³/h of air.

- **Against the IST6-300, 6 × 50 kVA** (one size down): Power modules · rating 8 × 50 kVA against 6 × 50 kVA; Bypass module 400 kVA · 3U against 300 kVA · 3U; W × D × H 1203 × 864 × 2000 mm against 607 × 860 × 2000 mm; Weight without power modules 459 kg against 236 kg.
- **Against the IST6-500, 10 × 50 kVA** (one size up): Power modules · rating 8 × 50 kVA against 10 × 50 kVA; Bypass module 400 kVA · 3U against 500 kVA · 4.5U; Weight without power modules 459 kg against 506 kg.

Planning data

## IST6-400, 8 × 50 kVA: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST6-400, 8 × 50 kVA.

### Four cabinets, one 50 kVA module

**IST6-400, 8 × 50 kVA · Four cabinets, one 50 kVA module**

| Cabinet | 400 kVA |
| --- | --- |
| Power modules (50 kVA) | 8 |
| Bypass module | 400 kVA · 3U |
| W × D × H (mm) | 1203 × 864 × 2000 |
| Weight without power modules | 459 kg |
| Mains input current | 690 A |
| Cooling air flow (min.) | 4840 m³/h |

### Site conditions and service

**IST6-400, 8 × 50 kVA · Site conditions and service**

| Line | 400 kVA |
| --- | --- |
| Mains input | 690 A · 2×(4×185) |
| Bypass / output | 606 A · 2×(4×185) |
| Battery (40 blocks) | 868 A · 3×(3×185) |
| Mains breaker | 800 A 3P |

Installation

## Installing the IST6-400, 8 × 50 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST6-400, 8 × 50 kVA · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | front 800 mm, rear 500 mm, top 500 mm; left and right: not given | AEC user manual Table 3-1; EMEA 2026 catalogue p.157 |
| Cable entry | Bottom (standard); Top (built to order) | AEC user manual Table 3-1; EMEA 2026 catalogue p.157 |
| Cooling air | 4,840 m³/h | EMEA 2026 catalogue p.157 |
| Heat at full load | 7.75 kW at 400 kW load, 98.1 % efficiency | IST6 200–500 data (up to 98.1 %, AEC); output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | 0 to 40 °C | IST6 200–500 AEC user manual |
| Switches and terminals | Mains, bypass, maintenance bypass and output switches inside the front door (single column 1,148–1,711 mm up; double column on the left, 462–1,658 mm). | IST6 200–500 user manual §3.5.1 p.43 (right-hand hinges, one door per column) |
| Door | One leaf, hinged on the right | IST6 200–500 user manual §3.5.1 p.43 (right-hand hinges, one door per column) |
| Module withdrawal | 650 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.143; AEC user manual A.2.1 |
| Units in parallel | Up to 8 units | AEC user manual A.1.2; EMEA 2026 catalogue p.139 |

Size and floor

## How big it is

1203 × 864 × 2000 mm · 459 kg without modules.

**1.04 m²** footprint

**2 m** height

Efficiency

## How efficient is the AEC IST6-400, 8 × 50 kVA at your load?

IST6-400, 8 × 50 kVA, 400 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 2.56 kW (η 97.5%) · 50%: 3.87 kW (η 98.1%) · 75%: 6.75 kW (η 97.8%) · 100%: 10.3 kW (η 97.5%). At 50% load, 24/7, it loses about 33,933 kWh a year.

**98.1** % 50% · Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)

How the curve is drawn and where each figure comes from: [the IST6 200–500 range page](https://www.aecups.com/en/products/ist6-200-500/#efficiency). ECO and W-ECO modes are listed without an efficiency figure.

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5% | Typical curve, derived from the datasheet efficiency of 98.1% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99.2% | Datasheet figure, load not stated | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |

EMEA 2026 catalogue figures: Online, double conversion up to 98.1%.

Drag to turn

In 3D

## Look around the IST6-400, 8 × 50 kVA

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist6-50m-400/v57/)

The turntable shows the IST6 500 kVA; the full 3D view opens on the IST6 400 kVA.

Technical data

## Technical data IST6-400, 8 × 50 kVA

Only this model's values, from the EMEA 2026 catalogue table.

**IST6-400, 8 × 50 kVA · Technical data**

|  |  |
| --- | --- |
| Cabinet |  |
| Power modules · rating | 8 × 50 kVA |
| Bypass module | 400 kVA · 3U |
| Input |  |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below) |
| Frequency · PF · THDi | 40–70 Hz · ≥ 0.99 · ≤ 1.5% at full load |
| Bypass | 304–438 V; synchronisation 50 ± 5 / 60 ± 6 Hz; settable window |
| Battery |  |
| Lead-acid | ±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40 |
| Lithium (with BMS card) | ±256 V DC nominal (±192 … ±294.4 V), 120–200 cells, standard 160 |
| Charging current | up to 30 A × number of modules · cold start · shared battery |
| Output |  |
| System · voltage | 3Ph+N+PE (3Ph+PE optional) · 380 / 400 / 415 V ± 1% |
| Power factor · THDv | settable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 4% non-linear |
| Frequency · phase error | tracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 3° unbalanced |
| Transfer | mains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms |
| Inverter overload (PF 1) | ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass |
| Bypass overload | ≤ 130% continuous · 130–150% 5 min · 150–200% 1 min · 200–300% 100 ms |
| System |  |
| Efficiency · modes | up to 98.1% · ECO, WECO, source share, redundancy sleep |
| Parallel | up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses) |
| Communication | Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS |
| Environment | 0 … 40 °C · 0–95% RH · ≤ 2000 m (derating to 4000 m) · IP20 · < 70 dB · EMC C3 |
| W × D × H (mm) | 1203 × 864 × 2000 |
| Weight without power modules | 459 kg |

**IST6-400, 8 × 50 kVA · Models**

| Item | IST6-400, 8 × 50 kVA |
| --- | --- |
| Power modules (50 kVA) | 8 |
| Bypass module | 400 kVA · 3U |
| W × D × H (mm) | 1203 × 864 × 2000 |
| Weight without power modules | 459 kg |
| Mains input current | 690 A |
| Cooling air flow (min.) | 4840 m³/h |

Power module 500 × 650 × 130 mm, 39 kg. Data from the IST6 200–500 kVA user manual. Specifications are subject to change without notice.

#### **More technical details** how it works, ordering codes

Diagrams

## How the power flows: AEC IST6-400, 8 × 50 kVA

Pick an operating mode: the path the power takes to the load lights up.

**Normal.** Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (double conversion, up to; ECO and WECO modes stated without a figure).

### Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 50 kVA module.

modules working · redundant · free slot

Ordering codes

## Ordering codes IST6-400, 8 × 50 kVA

**Ordering codes IST6-400, 8 × 50 kVA**

| Code | Description |
| --- | --- |
| IST6-400 | Modular cabinet, max. 8 × 50 kVA power modules, without modules |
| IST6-50-J | 50 kVA / 50 kW power module |
| PAR - IST6 | Parallel kit |

Questions

## Questions about the IST6-400, 8 × 50 kVA

#### IST6-400 with 50 kVA modules or IST6 400 kVA with 100 kVA modules?

The IST6-400 (8 × 50 kVA, 1203 mm wide) gives finer steps and cheaper redundancy. The 400 kVA cabinet of the 400–1200 range (4 × 100 kVA, 801 mm wide) takes less floor, reaches up to 98.1% efficiency with PLUS modules and keeps the same module up to 1.2 MW.

#### Can the IST6-400 run on lithium batteries?

Yes, with the BMS expansion card: lithium at ±256 V DC nominal, 120 to 200 cells (standard 160). Lead-acid runs at ±240 V nominal with 30 to 50 blocks, full output from 40 blocks.

#### How long does a 400 kVA UPS like the IST6-400, 8 × 50 kVA run?

5 to 78 minutes at full load (400 kW), and 16 to 156 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 120 × 12 V 100 Ah · 4 × 30 (IST6-400-120X100): 5 minutes at 100% and 16 at 50%. For other loads and batteries use the backup-time tool.

#### How big is the AEC IST6-400, 8 × 50 kVA and how much does it weigh?

The AEC IST6-400, 8 × 50 kVA measures 1203 × 864 × 2000 mm; weight: 459 kg without modules (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST6-400, 8 × 50 kVA?

In the EMEA 2026 catalogue the AEC IST6-400, 8 × 50 kVA is listed as IST6-400; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST6 200–500

[The whole range](https://www.aecups.com/en/products/ist6-200-500/)

[**IST6-200, 4 × 50 kVA** 200 kVA](https://www.aecups.com/en/products/ist6-200-500/ist6-200k-4x50/) [**IST6-300, 6 × 50 kVA** 300 kVA · smaller rating](https://www.aecups.com/en/products/ist6-200-500/ist6-300k-6x50/) **IST6-400, 8 × 50 kVA** 400 kVA [**IST6-500, 10 × 50 kVA** 500 kVA · larger rating](https://www.aecups.com/en/products/ist6-200-500/ist6-500k-10x50/)

Batteries and cabinets: [L6 Lithium](https://www.aecups.com/en/products/l6-lithium/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/)

Shared by the whole range, on the IST6 200–500 page: [the display simulator](https://www.aecups.com/en/products/ist6-200-500/#display) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist6-200-500/#gallery).

Read next: [Modular UPS: how to grow power module by module](https://www.aecups.com/en/blog/modular-ups/) [UPS redundancy: N+1 or 2N, and how much a site needs](https://www.aecups.com/en/blog/ups-redundancy-n-plus-1/) [UPS for data centres: how to choose and plan](https://www.aecups.com/en/blog/ups-for-data-centres/)