---
title: "Modular UPS 400 kVA–1.2 MVA, 400 V · IST6 | AEC"
url: https://www.aecups.com/en/products/ist6-400-1200/
description: "IST6 400–1200 kVA: modular online UPS, double conversion. 100 kVA power modules in 3U, from 400 kVA to 1.2 MVA per cabinet."
language: en
---

Modular UPS · 400 V

# IST6 400–1200 Modular UPS, 400 V, for data centres

VRLA Online double conversion

The AEC IST6 400–1200 is a modular online double-conversion UPS for data centres and large 400 V plants: hot-swappable 100 kVA power modules 3U high, from 400 kVA to 1.2 MVA in one cabinet. Efficiency up to 98.1% with PLUS modules and 99.2% in ECO mode, N+1 redundancy, and up to eight UPS in parallel.

**400→1200** kVA in 100 kVA steps

**N+1** one extra module

**98.1%** efficiency, PLUS modules

**Hot-swap** modules replaced online

Datasheet Manuals and catalogues [Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6%20400%E2%80%931200%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist6-100m-1200/v78/)

Drag to turn

In 3D

## Look around the IST6 400–1200

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist6-100m-1200/v78/)

Pick a size: the turn and the full 3D view follow it. Rendered from AEC's 3D models; the full 3D view zooms in, opens the unit and names every part.

Hands on

## Open the IST6 400–1200 yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

[Every part in 3D](https://www.aecups.com/assets/models3d/ist6-100m-1200/v78/)

Efficiency

## How efficient is the AEC IST6 400–1200 at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

**98.1** % 50% · Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5% | Typical curve, derived from the datasheet efficiency of 98.1% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99.2% | Datasheet figure, load not stated | all |  |
| W-ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Double conversion, General modules up to 97.2% · Double conversion, PLUS modules up to 98.1% · ECO up to 99.2% · W-ECO up to 99%.

The display

## The IST6 400–1200 kVA display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

UPS state

IST6 400–1200 kVA · the real display

### Normal operation

**Main pages**

What is what

## Inside the IST6 400–1200, part by part.

Each number on the picture is named in the list.

### Front, door open · 800 kVA

1. **Battery cold start**
2. **System control box**
3. **Power modules**

### Front, doors open · 1000 kVA

From 800 kVA the power switches sit in an optional distribution cabinet, fitted at the factory on the left of the UPS.

1. **Distribution cabinet** 1000 / 1200 kVA: mains, bypass and output breakers (no maintenance bypass), pre-assembled at the factory.
2. **SPD** Optional surge protection device, with its own switch.
3. **Battery cold start** Starts the UPS from the battery when there is no mains and no bypass.
4. **System control box** Five hot-swappable cards: expansion (dry contact or BMS) and SNMP (optional), control cards 1 and 2, monitoring card with Modbus, RS232, RS485, EPO1 NO, EPO2 NC, B-Temp input and dry contacts.
5. **Power modules** 100 kVA in 3U each, in three groups of four slots on 1200 kVA.

### Front, doors open · 1200 kVA

1. **SPD**
2. **Battery cold start**
3. **System control box**
4. **Power modules**

Overview

## Key facts

**Power range**: 400–1200 kVA

**Input / output**: 3/3 · 380 / 400 / 415 V

**Efficiency**: 97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99%

**Battery**: 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional

**Communication**: Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact

**Network card**: SNMP card (optional)

**Parallel**: up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses)

**Warranty**: 3 years

**Dimensions W × D × H**: 801 × 1000 × 2000 · 1201 × 1000 × 2000 mm

[Applications](https://www.aecups.com/en/applications/): Data centres Telecom Banking & finance Networks & IT rooms Transport Public buildings

Pictures

## The IST6 400–1200 in pictures

The photos and drawings of the EMEA 2026 catalogue: product views, displays, modules and connections. Tap a picture to enlarge it.

Models

## Which IST6 400–1200 fits your load?

Every rating has its own page: that model's technical data, ordering codes, batteries and the questions people ask.

[**IST6-400H, 4 × 100 kVA** 400 kVA The IST6 400 kVA is a single-column modular online UPS for four 100 kVA power modules, 801 × 1000 × 2000 mm, with mains, output, bypass and maintenance bypass switches inside. **801 × 1000 × 2000 mm**Size **345 kg without modules**Weight See the model](https://www.aecups.com/en/products/ist6-400-1200/ist6-400k-4x100/) [**IST6-500H, 5 × 100 kVA** 500 kVA The IST6 500 kVA of the 100 kVA platform is a single-column modular online UPS, 801 mm wide, with five 100 kVA modules and a 4.5U bypass module. **801 × 1000 × 2000 mm**Size **434 kg without modules**Weight See the model](https://www.aecups.com/en/products/ist6-400-1200/ist6-500k-5x100/) [**IST6-600H, 6 × 100 kVA** 600 kVA The IST6 600 kVA is a single-column modular online UPS with six 100 kVA modules, 801 × 1000 × 2000 mm, the most power in a cabinet with switches built in. **801 × 1000 × 2000 mm**Size **434 kg without modules**Weight See the model](https://www.aecups.com/en/products/ist6-400-1200/ist6-600k-6x100/) [**IST6-800, 8 × 100 kVA** 800 kVA The IST6-800 is a single-column modular online UPS for eight 100 kVA modules: 800 kW on 0.8 m², 801 × 1000 × 2000 mm. **801 × 1000 × 2000 mm**Size **435 kg without modules**Weight See the model](https://www.aecups.com/en/products/ist6-400-1200/ist6-800k-8x100/) [**IST6-1000, 10 × 100 kVA** 1000 kVA The IST6-1000 is a double-column modular online UPS with ten 100 kVA modules: 1 MW in 1201 × 1000 × 2000 mm. **1201 × 1000 × 2000 mm**Size **662 kg without modules**Weight See the model](https://www.aecups.com/en/products/ist6-400-1200/ist6-1000k-10x100/) [**IST6-1200, 12 × 100 kVA** 1200 kVA The IST6-1200 is the largest AEC UPS: twelve 100 kVA modules in a double-column cabinet, 1.2 MW in 1.2 m² of floor. **1201 × 1000 × 2000 mm**Size **662 kg without modules**Weight See the model](https://www.aecups.com/en/products/ist6-400-1200/ist6-1200k-12x100/)

Datasheet

## Datasheet IST6 400–1200.

Every model side by side: keep only what differs, take it as CSV or print it.

**IST6 400–1200 · Technical data**

| Model | 400 kVA | 500 kVA | 600 kVA | 800 kVA | 1000 kVA | 1200 kVA |
| --- | --- | --- | --- | --- | --- | --- |
| Cabinet |  |  |  |  |  |  |
| Power modules (100 kVA) | 4 | 5 | 6 | 8 | 10 | 12 |
| Bypass module | 3U | 4.5U | 4.5U | 4.5U | 4.5U | 4.5U |
| Input |  |  |  |  |  |  |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below) |  |  |  |  |  |
| Frequency · PF · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |  |  |  |  |  |
| Bypass | 304–438 V; synchronisation 50 / 60 ± 6 Hz; settable window |  |  |  |  |  |
| Battery |  |  |  |  |  |  |
| Lead-acid | 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional |  |  |  |  |  |
| Lithium (with BMS card) | 512 V DC nominal (384–640 V), 120–200 cells, standard 160 |  |  |  |  |  |
| Charging current | 20 A × number of modules · cold start · shared battery |  |  |  |  |  |
| Output |  |  |  |  |  |  |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V ± 1% |  |  |  |  |  |
| Power factor · THDv | settable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 3% non-linear |  |  |  |  |  |
| Frequency · phase error | tracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 2° unbalanced |  |  |  |  |  |
| Transfer | mains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms |  |  |  |  |  |
| Inverter overload (PF ≥ 0.95) | ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass |  |  |  |  |  |
| Bypass overload | ≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms |  |  |  |  |  |
| System |  |  |  |  |  |  |
| Efficiency · modes | 97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99% · energy storage, sleep, generator |  |  |  |  |  |
| Parallel | up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses) |  |  |  |  |  |
| Communication | Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS |  |  |  |  |  |
| Environment | 0 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 80 dB · EMC category C3 |  |  |  |  |  |
| W × D × H (mm) | 801 × 1000 × 2000 | 801 × 1000 × 2000 | 801 × 1000 × 2000 | 801 × 1000 × 2000 | 1201 × 1000 × 2000 | 1201 × 1000 × 2000 |
| With distribution cabinet | — | — | — | 1400 mm wide | 1800 mm wide | 1800 mm wide |
| Weight without modules | 345 kg | 434 kg | 434 kg | 435 kg | 662 kg | 662 kg |

Power module 440 × 760 × 130 mm (without ears and handles), 54 kg. Data from the IST6 400–1200 kVA user manual. Specifications are subject to change without notice.

#### **Full technical details** 22 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

### Why IST6 400–1200

01 **400→1200 · Sized to the site** Six cabinets with 4 to 12 power modules of 100 kVA: single column up to 800 kVA, double column for 1000 and 1200 kVA.

02 **98.1% · High efficiency** Up to 97.2% with General modules and 98.1% with PLUS modules in double conversion; 99.2% in ECO.

03 **1.2 MW · Compact power** 100 kVA = 100 kW in a 3U module: 800 kW in 0.8 m² and 1.2 MW in 1.2 m² of floor.

04 **Hot-swap · Continuity first** All modules hot-swappable, two system control cards backing each other up, dual DSP control.

05 **40 °C · No derating** No derating up to 40 °C, redundant fans, conformal-coated boards, dust filter and fuses on frame and modules.

06 **Storage · Smart energy** Energy storage mode for peak cutting and valley filling, ECO, W-ECO, redundancy sleep and generator mode.

OPERATING COST

## What PLUS modules save at 800 kW

From 97.2% to 98.1%: less than one point of efficiency, but at megawatt scale it is heat that is not paid for at the meter and in the cooling.

- 7.6 kW less losses (23.0 → 15.5 kW)
- 66,200 kWh saved per year
- ≈ € 13,200 per year at € 0.20/kWh
- Basis: IST6 1000 kVA at 80% load (800 kW), 8,760 h/year, cooling excluded. Losses = P × (1/η − 1) with the maximum system efficiencies 97.2% (General) and 98.1% (PLUS). Indicative values.

FEATURE OVERVIEW

## The features, group by group

The IST6 400–1200 kVA features, in the catalogue's four groups.

- Reliable: double key combination, two keys for ON / OFF
- Reliable: power walk-in and sequential rectifier restart
- Reliable: short-circuit protection, time settable 20–400 ms
- Reliable: backfeed protection, enabled on site
- Reliable: system and component redundancy, 40% load with one fan failed
- Reliable: wide input, 138–485 V, 40–70 Hz
- Reliable: conformal coating on all PCBs
- Flexible: lead-acid or lithium batteries, neutral optional
- Flexible: common battery bank in parallel systems
- Flexible: frequency converter 50 ↔ 60 Hz
- Flexible: top entry, bottom entry with side wiring cabinet
- Flexible: top air outlet kit for installation against the wall
- Intelligent: start-up guidance and diagnosis
- Intelligent: maintenance assistant
- Intelligent: smart integrated display for the parallel system
- Intelligent: smart files, asset and replacement records
- Intelligent: W-ECO and redundancy sleep
- Intelligent: fault trace, 200 ms before and after the fault
- Intelligent: programmable dry contacts, 10 input, 18 output functions
- Grid support: energy storage mode, peak cutting, valley filling
- Efficiency: 97.2% (General) / 98.1% (PLUS)
- Efficiency: ECO 99.2%, W-ECO 99%
- Testing: self-load test without external load banks
- 98.1% efficiency with PLUS modules · 1.2 MVA per cabinet · 20–400 ms short-circuit time · 9.6 MW with 8 UPS in parallel

THE RANGE

## Six cabinets, one 100 kVA module

Single-column cabinets from 400 to 800 kVA, double-column cabinets for 1000 and 1200 kVA; the same power module, display and functions.

- 400 · 500 · 600 · 800 kVA: single column, 801 mm wide
- 1000 · 1200 kVA: double column, 1201 mm wide
- 800 kVA + distribution cabinet: 1400 mm wide
- 1000 · 1200 kVA + distribution cabinet: 1800 mm wide
- 400–600 kVA: mains, output, maintenance bypass and bypass switches inside; version without switches available
- With the distribution cabinet fitted on the left side: 800 kVA mains, bypass, maintenance bypass and output switches; 1000 / 1200 kVA mains, bypass and output
- Height 2000 mm for all cabinets
- Codes: IST6-400H, IST6-500H, IST6-600H, IST6-800, IST6-1000, IST6-1200 cabinets without modules; IST6-100-J power module

POWER MODULE

## 100 kVA in 3U, 1.2 MW in 1.2 m²

The same 100 kVA module from 400 kVA to 1.2 MVA: rectifier, inverter and DC/DC converter in a 3U drawer, with output power factor 1 (kVA = kW).

- Front: limit lock (press to pull the module out), RUN (green), ALARM (yellow) and FAULT (red) LEDs, ready switch (green unlocked, red locked)
- Rear: output port; input port for AC mains and DC battery
- Intelligent fan control with redundant design: 100% load with all fans running, 40% with one fan failed, 15% with two
- Dual DSP control: no single point of failure
- Fuses on frame and modules
- Conformal coating on all PCB boards
- Dust filter: standard, self-dedusting
- ≈ 1 MW/m²: 800 kW on 0.8 m², 1.2 MW on 1.2 m²

**100 kVA in 3U, 1.2 MW in 1.2 m²**

| Item | Value |
| --- | --- |
| Rating | 100 kVA / 100 kW |
| W × D × H | 440 × 760 × 130 mm · 3U |
| Weight | 54 kg |
| Handling | three installers or a lift truck |
| Bypass module | 3U (400 kVA) · 4.5U (500–1200 kVA) |

INSIDE THE CABINET

## Every module in front, everything in reach

400–600 kVA single column with internal power switches, and 1000–1200 kVA double column (without switches: these are in the optional distribution cabinet).

- 400 kVA, 4 modules, with switches: mains switch, output switch, maintenance bypass switch, bypass switch, SPD switch (optional), SPD (optional), system control box with five hot-swappable cards, battery cold start, bypass module (3U, under the control box), fan control switch (optional), power modules of 100 kVA each, switch operating lever
- 1200 kVA, 12 modules: fan control switch, SPD switch (optional), SPD (optional), battery cold start, system control box with five hot-swappable cards, power modules in three groups of four slots, bypass module (4.5U)
- 500 / 600 kVA: 4.5U bypass module and 6 module slots
- 800 kVA: single column with 8 modules and no internal power switches

DISTRIBUTION CABINET

## Switchgear on board, factory fitted

For 800, 1000 and 1200 kVA the power switches come in an optional distribution cabinet, fitted at the factory on the left side of the UPS: one line-up, switches pre-assembled.

- 800 kVA + distribution, 1400 mm: mains, bypass, maintenance bypass and output switches, SPD switch and SPD (optional), system control box, battery cold start, bypass module, fan control switch, 8 × 100 kVA power modules
- 1200 kVA + distribution, 1800 mm: bypass switch, mains switch, output switch, fan module
- 1000 / 1200 kVA: mains, bypass and output breakers (no maintenance bypass)
- Option: side wiring cabinet for bottom cable entry; standard entry is from the top
- Option: top air outlet kit, hot air out from the top instead of the rear; factory fitted on 800–1200 kVA
- Option: single power source kit, mains and bypass from one source
- Option: earthing detection kit, battery earthing detection, 400–600 kVA

HOT-SWAP

## Service with the load running

All modules are hot-swappable: power modules, bypass module and the five cards of the system control box.

- Step 1, unlock: ready switch to unlocked, indication green, the module can be removed
- Step 2, pull out: remove the fixing screws, pull the module out by its handles, press the limit lock and lift it onto a lift truck; the other modules keep supplying the load
- Step 3, insert and lock: slide the new module in, fasten the screws and set the ready switch to locked, indication red, the module joins the system
- Green, yellow and red LEDs (RUN · ALARM · FAULT) on every power and bypass module
- A faulty module isolates itself from the system automatically; redundancy is reduced until it is replaced
- Service records: spare part replacements, dates and service people; pre-alarms on key components such as capacitors and fans
- 54 kg power module: lift truck or three installers
- 2 system control cards backing each other up; 5 hot-swappable control box cards
- Wait ≥ 15 min before opening a removed module

ARCHITECTURE

## Online double conversion in every module

Power flow in each operating mode: N power modules in parallel and one bypass module.

- Mains mode: each module rectifies the mains and the inverter supplies the load; the battery is charged
- Battery mode: mains abnormal, the DC/DC converter feeds the battery to the inverters, 0 ms
- Mains and battery source share: mains too low, mains and battery supply the modules together
- Bypass mode: overload or fault, the bypass module supplies the load
- Two control cards: primary and secondary system control cards, hot-swappable, backing each other up
- CAN communication inside and between cabinets for synchronisation and current sharing
- Load shared equally between power modules within 5%
- Mains ↔ battery transfer time 0 ms; bypass ↔ inverter < 1 ms synchronised
- Input power factor ≥ 0.99; input THDi ≤ 3% at full load; 100% unbalanced load

SCALE AND SLEEP

## 100 kVA steps, up to 9.6 MW with 8 UPS

Add 100 kVA modules or whole UPS as the site grows; set redundancy and redundancy sleep from the screen.

- Step size 100 kVA: one 3U module at a time, in free slots up to the cabinet rating
- 4 → 12 modules per cabinet: 400, 500, 600, 800, 1000 or 1200 kVA cabinets
- × 8 UPS in parallel: up to 9.6 MW, with N+X redundancy between UPS
- N+X, two redundancy levels: basic and redundant modules per cabinet and per parallel system
- Redundancy sleep: at light load the spare modules sleep at random, while the basic modules carry the load within the sleep safety load capacity set on screen
- Smart mode › Sleep redundancy: on / off, sleep cycle period (h), sleep safety load capacity (kVA), parallel basic and redundant UPS, basic and redundant modules inside the cabinet
- Parallel mode, parallel address and BSC address set in Cabinet setting › Mode manage; parameter match between UPS checked in Running info
- Alarms: power module without redundancy, redundancy insufficient, cabinet without redundancy, system card without redundancy
- Power walk-in limits inrush on mains or generator; delayed sequential rectifier restart in multi-UPS sites
- Firmware online: screen, power units, bypass unit and cards updated online in one step

SMART ENERGY

## Modes that save energy and work with the grid

ECO, W-ECO and energy storage modes, plus redundancy sleep, smart generator mode, self-load test and frequency converter.

- ECO mode, up to 99.2%: the load runs on the static bypass while the bypass is within the ECO window; the inverter is in standby and the rectifier keeps the battery charged
- ECO window: voltage ±5 / ±10 / ±15% (default ±15%), frequency ±2 / ±4% (default ±2%); parallel ECO available
- W-ECO mode, up to 99%: high-efficiency mode with input THDi below 5%; its state is shown live on the home page
- Energy storage mode: peak cutting and valley filling, the battery supplies part of the load at peak hours and recharges in the valley, following a plan curve set by discharge power or current for each period
- Energy storage UPS page: plan curve, battery safety SOC (e.g. 40%), discharge power or current for each period, electricity price setting
- Redundancy sleep: spare modules sleep at light load
- Smart generator mode: starts and stops the generator by dry contact and can take part of the power from the battery
- Self-load test at commissioning without costly temporary loads
- Frequency converter: 60 Hz to 50 Hz or 50 Hz to 60 Hz

PERFORMANCE

## Full power from 324 to 485 V

Full power from 324 to 485 V line voltage; from 138 to 323 V the UPS keeps running with linear derating of the load.

- Input: 40–70 Hz · PF ≥ 0.99 · THDi ≤ 3% at full load
- Power walk-in to limit inrush on mains or generator; delayed sequential rectifier restart in multi-UPS sites
- TN-S, TN-C, TN-C-S, TT; RCD breakers upstream not recommended
- Inverter overload (linear load, PF ≥ 0.95): ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min; above 150% to bypass at once
- PF 0.9: 105–110% 60 min, above 110% to bypass; PF 0.8: above 105% to bypass
- Bypass overload: ≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms; above 300% immediate protection
- With the top air outlet kit, overload values apply below 30 °C
- Backfeed protection: fitted, enabled on site; dry-contact outputs for single UPS and parallel system bypass backfeeding
- Option: output isolation transformer of the same capacity
- Settable bypass window: max. +10 … +25% (default +15%), min. −10 … −30% (default −20%), frequency ±2 … ±20% (default ±10%)
- No derating up to 40 °C

**Full power from 324 to 485 V**

| Output | Value |
| --- | --- |
| Voltage | 380 / 400 / 415 V ± 1% |
| Power factor | settable 0.8–1.0, default 1.0 |
| THDv | ≤ 1% linear · ≤ 3% non-linear |
| Phase error | ≤ 1° balanced · ≤ 2° unbalanced |
| Frequency, mains abnormal | 50 / 60 Hz ± 0.1 Hz |
| Load step 0↔100% | ≤ 5%, recovery ≤ 20 ms |
| DC component | −100 … +100 mV |
| Transfer bypass ↔ inverter | < 1 ms synchronised · < 15 ms |
| Short circuit | duration settable 20–400 ms |

PROTECTION AND SMART GUIDANCE

## Grid protections and service guidance

Advanced protection of the 100 kVA platform, plus the guidance tools that shorten installation and maintenance.

- Power walk-in: decreases the inrush to the mains or the generator; with several UPS the rectifiers restart in sequence when the mains returns
- Short-circuit protection: high short-circuit capacity for a settable time of 20–400 ms, so the breaker of the faulty load trips while the other loads keep running
- Backfeed protection: enabled on site; dry-contact outputs for single UPS and parallel system bypass backfeeding open the backfeed device upstream
- Start-up guidance and diagnosis: first power-on guidance with module self-test, potential risks are cleared before the system is powered on
- Maintenance assistant: locates the problem easily and quickly, reducing the time for maintenance
- Smart integrated display: one display checks the status of each UPS of the parallel system
- Key components pre-alarm and asset records: pre-alarm on capacitors and fans; full record of spare part replacements, dates and service people

BATTERIES

## 480 V lead-acid or 512 V lithium

480 V DC nominal with 40 blocks of 12 V (360–600 V); 30 to 50 blocks (46–50 on request), with the output factor below for short strings. Battery neutral optional (±240 V).

- 20 A charging current per power module (specification), three-stage charging
- Lithium: 512 V nominal, 120–200 cells (standard 160, full power from 160), with the BMS card
- Battery setting: cell voltages for protection, alarm, equalising and floating charge, charging current, test time
- Charge management: charge limit coefficient in C, temperature compensation, timed and forced equalising charge
- Battery test: standard or deep test with mains normal, battery floating and load ≥ 15%
- Common battery: shared battery pack mode fitted
- Battery cold start button: hold more than 3 s to start the UPS from the battery
- Optional BMS expansion card with charge- and discharge-disable inputs
- Intelligent battery management helps replace only the faulty battery
- 30–50 × 12 V blocks per string · 480 V lead-acid nominal · 0.05–0.5 C charge limit, lead-acid · 20–30 °C best battery temperature

**480 V lead-acid or 512 V lithium**

| 12 V blocks per string (lead-acid) | Output factor |
| --- | --- |
| 30 | 0.75 |
| 32 | 0.8 |
| 34 | 0.8 |
| 36 | 0.9 |
| 38 | 0.9 |
| 40 (standard) | 1 |
| 42 | 1 |
| 44 | 1 |
| 46 | 1 |
| 48 | 1 |
| 50 | 1 |

OPERATOR PANEL

## Seven-inch touch screen and status light bar

Seven-inch colour touch screen, five status LEDs, two-key ON / OFF commands and a status light bar.

- Colour touch screen, seven inches: live power flow, measurements, settings and records
- Five status LEDs: AC/DC, DC/AC, bypass, battery, load; green when normal or active, red when abnormal
- ON keys: press both keys for 3 s to power on, no accidental switching; OFF keys: press both keys for 3 s to power off
- Status light bar: blue normal operation; blue flashing battery mode; yellow abnormal, UPS still running; red abnormal, UPS stopped; alarms also light the yellow or red ambient lamp
- Screen settings: backlight time, brightness; 10 languages, including Italian; atmosphere light on / off; time zone and NTP time sync

Tap a light: green is normal operation, red an abnormal state, as in the catalogue's table.

AC/DC: green, Rectifier normal

**Seven-inch touch screen and status light bar**

| LED | Green | Red |
| --- | --- | --- |
| AC/DC | Rectifier normal | Rectifier abnormal |
| DC/AC | Inverter normal | Inverter abnormal |
| Bypass | Bypass output | Bypass abnormal |
| Battery | Battery output | Battery low voltage |
| Load | Output normal | Output overload |

TOUCH SCREEN

## Touch a block, read its measurements

The home page draws the UPS as it runs: yellow dots trace the active power path, abnormal blocks turn red, and the bottom line shows output voltage and frequency. Touch a block (bypass, mains, battery, rectifier, inverter, output) to open its page.

- Bypass info: phase and line voltage, current and frequency of the bypass input
- Mains info: phase and line voltage, current and frequency of the mains
- Battery info: voltage, charge and discharge current, remaining capacity and time, temperature, state
- Inverter info: output voltage, current, power and load of each module
- Information menu: running info, history, user log, smart record, device info, wave capture, running record, battery discharge record
- Settings menu: cabinet, battery, battery test, output, smart mode, dry contact, screen, password, communication, records, energy storage
- Running info: UPS info, parameter match between UPS, UPS status, system cards 1 and 2
- Device info: hardware and software versions of screen, system cards and modules
- 3 password levels: user, technician and service engineer
- 10 languages on the screen; 7″ colour touch screen with live single-line diagram
- Online firmware update of screen, units and cards in one step

RECORDS

## 10,000 events, 200 ms of fault waveform

10,000 records in the history, newest first; when the record is full, the earliest entry is overwritten.

- 200 ms of waveform recorded before and after the fault point (fault trace management)
- User log: user operations listed with date and time
- Current fault: active faults, time-stamped, from the alarm icon of the menu bar
- Smart record: maintenance actions such as part replacements
- Smart wave capture: when a fault occurs, the UPS stores the waveforms 200 ms before and after it, listed with date and time
- Running record: input voltages and current over time
- Battery discharge record: every discharge with date and time
- Record manage: save or clear history, user log, smart record and wave capture

OPERATION

## Every operating state, shown live

Real screens of the IST6 400–1200 kVA: the yellow dotted line traces the active power path.

- Inverter output: mains → rectifier → inverter → load, battery charging
- Battery: mains abnormal, the battery feeds the inverters, 0 ms
- Bypass: load on the bypass module, e.g. on overload or fault
- Maintenance bypass: load on the maintenance bypass for service
- Grid-tied self-load: load test at commissioning without external load banks
- Frequency converter: 60 Hz to 50 Hz or 50 Hz to 60 Hz
- ECO: load on the static bypass within the ECO window, up to 99.2%
- W-ECO: high-efficiency mode, up to 99%, THDi below 5%
- Transfers: 0 ms mains ↔ battery; < 1 ms inverter ↔ bypass, synchronised; < 15 ms inverter ↔ bypass, not synchronised
- Cold start: hold the battery cold start button for more than 3 s to start the UPS from the battery
- Restart after a long outage: after battery under-voltage protection, the UPS restarts and recharges the battery when the mains returns
- Two-key ON / OFF: press both ON or both OFF keys for 3 s, no accidental switching

CONNECTIVITY

## Five hot-swappable cards in the control box

System control box: all five cards are hot-swappable.

- Slots: expansion card (optional: dry contact or BMS), SNMP card (optional), system control card 1, system control card 2, monitoring card (Modbus, RS232, EPO, dry contacts)
- 4 inputs (NO), 10 functions: battery abnormal, battery earthing abnormal, battery switch off, bypass switch off, generator mode, SPD abnormal, maintenance bypass open, mains switch off, environment smoke abnormal, strip light switch off
- 3 outputs (NO / NC, 30 V DC / 2 A), 18 functions: inverter mode, bypass mode, battery trip, battery mode, battery under-voltage alarm, battery under-voltage protection, output overload, UPS abnormal, bypass abnormal, mains abnormal, start generator, ECO mode, inverter abnormal, single UPS bypass backfeeding, parallel system bypass backfeeding, UPS ON, fan abnormal, UPS alarm
- Standard: Modbus (address 1–247, 2400–19200 baud) · RS232 for an external SNMP card · RS485 linking the displays of a parallel system · EPO1 NO and EPO2 NC · B-Temp input for the battery temperature kit
- Option: SNMP card, Ethernet, SNMP or Modbus; RS485 port for a T/H sensor
- Option: dry contact expansion card, +3 inputs, +2 outputs (30 V DC / 2 A)
- Option: BMS expansion card, BMS port, charge / discharge disable inputs
- Option: class C SPD with SPD switch, factory fitting recommended
- Option: battery temperature kit, charge voltage compensated by temperature
- Option: battery trip kit, trip signal for the external battery breaker

PARALLEL AND MULTI-BUS

## Up to eight UPS, up to three buses

Parallel, dual-bus and multi-bus system layouts.

- Parallel system, up to 8 UPS: mains, bypass and AC outputs of each cabinet connected in parallel; the control modules keep all UPS synchronised and share the load (imbalance ≤ 5%)
- BSC dual-bus system: two independent UPS systems synchronised by the bus sync controller; an STS supplies single-input loads
- Multi-bus: three buses
- Parallel ring: PARALLEL ports of the system control cards in a ring, N UPS need N cables; a 7 m cable is supplied with each UPS
- Output of each UPS within ± 2 V and ± 0.1 Hz of the system setting
- Parallel mode, parallel address and BSC address set on the screen
- EPO linkage: one EPO stops the whole system, or only its UPS (set by AEC service)
- Shared battery pack and parallel ECO available
- Up to 8 UPS in parallel · 9.6 MW system power · ≤ 5% current imbalance · 3 buses in multi-bus mode

INSTALLATION AND SERVICE

## Site conditions and service

Clearances, airflow, environment, cabling and the AEC service path from sizing to expansion.

- Clearances: A front ≥ 800 mm · B rear ≥ 500 mm (400–600 kVA) or ≥ 800 mm (800–1200 kVA) · C top ≥ 500 mm (≥ 650 mm with the top air outlet kit, 400–600 kVA)
- Front to rear forced air: cold air in at the front, hot air out at the rear; minimum air flow from 3744 m³/h (400 kVA) to 8785 m³/h (1200 kVA)
- Top air outlet kit: hot air out from the top; factory fitted on 800–1200 kVA, shipped as an accessory for 400–600 kVA
- 0 … 40 °C without derating, 0–95% RH non-condensing
- Up to 2000 m · IP20 · noise < 80 dB at 1 m from the front
- TN-S, TN-C, TN-C-S, TT; RCD breakers not recommended
- Not for open installations within 3.7 km of the sea
- Top cable entry; bottom entry with the side wiring cabinet (trench 750 × 300 × 120 mm)
- M12 expansion bolts to the floor or C-steel base
- Forklift from the side or two forklifts from the front; tilt ≤ 15°
- Optional class C SPD with switch, factory fitting recommended
- Sizing: modules, redundancy, battery and parallel system sized by AEC engineers
- Commissioning: start-up guidance, settings, dry contacts, parallel addresses and self-load test
- Maintenance: monthly, quarterly and yearly checks; air filter cleaned or replaced
- Expansion: power modules added in free slots up to the cabinet rating or for redundancy; further UPS with the parallel kit
- 24/7 AEC technical assistance by phone and WhatsApp; WhatsApp reply in < 30 min to technical and commercial questions
- 3 years warranty, extendable with a maintenance contract
- 21+ countries with spare parts across the Allis Electric group
- AEC service: service@aecups.com · +39 393 080 5211 · www.aecups.com

### Ordering codes IST6 400–1200

| Code | Description |
| --- | --- |
| `IST6-400H` | Modular cabinet, max. 4 × 100 kVA power modules, without modules |
| `IST6-500H` | Modular cabinet, max. 5 × 100 kVA power modules, without modules |
| `IST6-600H` | Modular cabinet, max. 6 × 100 kVA power modules, without modules |
| `IST6-800` | Modular cabinet, max. 8 × 100 kVA power modules, without modules |
| `IST6-1000` | Modular cabinet, max. 10 × 100 kVA power modules, without modules |
| `IST6-1200` | Modular cabinet, max. 12 × 100 kVA power modules, without modules |
| `IST6-100-J` | 100 kVA / 100 kW power module |
| `PAR - IST6` | Parallel kit |

Diagrams

## The IST6 400–1200, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

### How the power flows

Pick an operating mode: the path the power takes to the load lights up.

**Normal.** Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (PLUS modules; 97.2% with General modules).

### The ratings

Every model in the range, in proportion to its power. Each notch is one 100 kVA module.

1. 400 kVA **400 kVA · 400 kW**
2. 500 kVA **500 kVA · 500 kW**
3. 600 kVA **600 kVA · 600 kW**
4. IST6-800 **800 kVA · 800 kW**
5. IST6-1000 **1,000 kVA · 1,000 kW**
6. IST6-1200 **1,200 kVA · 1,200 kW**

### Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 100 kVA module.

modules working · redundant · free slot

### Losses per 100 kW of load

Worked out as P × (1/η − 1) at the stated maximum efficiency, with the load steady all year. PLUS modules; 97.2% with General modules.

1. Double conversion 98.1% **1.94 kW16,970 kWh/year**
2. ECO 99.2% **0.81 kW7,060 kWh/year**

### Phase configurations

Input / output: three-phase (3) or single-phase (1).

**3/3** 3~ → 3~

**In parallel** Up to 8 units on the same load, for redundancy or for more power.

### Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

- **400 kVA cabinet, single column, without modules** 801 × 1,000 × 2,000 mm · 345 kg
- **500 kVA cabinet, single column, without modules** 801 × 1,000 × 2,000 mm · 434 kg
- **600 kVA cabinet, single column, without modules** 801 × 1,000 × 2,000 mm · 434 kg
- **800 kVA cabinet, single column, without modules** 801 × 1,000 × 2,000 mm · 435 kg
- **1000 kVA cabinet, double column, without modules** 1,201 × 1,000 × 2,000 mm · 662 kg
- **1200 kVA cabinet, double column, without modules** 1,201 × 1,000 × 2,000 mm · 662 kg

Questions

## Questions people ask

#### Which cabinet sizes does the IST6 400–1200 kVA come in?

Six cabinets with 4 to 12 power modules of 100 kVA (3U, 54 kg each). The 400, 500, 600 and 800 kVA in a single column of 801 × 1000 × 2000 mm, 1000 and 1200 kVA in a double column of 1201 × 1000 × 2000 mm. With the optional distribution cabinet the 800 kVA is 1400 mm wide and the 1000–1200 kVA 1800 mm.

#### What is the difference between General and PLUS power modules?

System efficiency in double conversion is up to 97.2% with General modules and 98.1% with PLUS modules; ECO mode reaches 99.2%. At 800 kW, AEC's indicative calculation shows PLUS modules saving 7.6 kW of losses, about 66,200 kWh per year.

#### How far can the system grow in parallel?

Up to eight UPS in parallel, for up to 9.6 MW, with N+X redundancy between UPS and load sharing within 5%. Dual-bus (BSC) and three-bus layouts are supported, and power modules can be added in free slots up to the cabinet rating.

#### Which battery configuration does it use?

Lead-acid: 480 V DC nominal with 40 × 12 V blocks (360–600 V), 30 to 50 blocks accepted with reduced output below 40 blocks, battery neutral optional (±240 V). Lithium: 512 V nominal with 120–200 cells (standard 160) and the BMS card; charging current is 20 A per power module.

#### What installation clearances does it need?

At least 800 mm at the front, 500 mm (400–600 kVA) or 800 mm (800–1200 kVA) at the rear and 500 mm on top (650 mm with the top air outlet kit on 400–600 kVA). It runs without derating up to 40 °C, up to 2000 m, with top cable entry as standard and bottom entry via the side wiring cabinet; it is not for open installations within 3.7 km of the sea.

#### How is service carried out without stopping the load?

All modules are hot-swappable, including the bypass module and the five cards of the system control box, with dual DSP control and two control cards backing each other up. The redundant fans keep a module running at 40% load with one fan failed.

#### Which communication options does it offer?

Modbus (address 1–247, 2400–19200 baud), RS232 for an external SNMP card, RS485, EPO1 / EPO2 and 4 dry-contact inputs / 3 outputs are standard. Options: SNMP card (Ethernet, SNMP or Modbus), dry-contact expansion and a BMS card for lithium batteries.

[All 22 questions](https://www.aecups.com/en/faq/ist6-400-1200/)

In the same family: [IST6-120](https://www.aecups.com/en/products/ist6-120/) [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/) [Modular UPS](https://www.aecups.com/en/products/modular-ups/)

References

## Where is the IST6 400–1200 installed?

[All projects](https://www.aecups.com/en/projects/)

[**5 MW of IST6 modular UPS for a data centre in Italy** Data centre · Italy](https://www.aecups.com/en/projects/#data-centre-italy-ist6-5mw) [**An IST6 1.2 MW modular UPS replaces the old system of a hospital in Turin** Hospital, emergency department · Italy (Turin)](https://www.aecups.com/en/projects/#turin-hospital-ist6) [**2 MW of IST7, IST6 and IST8 UPS across Saudi Aramco's sites** Oil and gas · Saudi Arabia](https://www.aecups.com/en/projects/#aramco-ist7-ist6-ist8)

Guides

## Guides on the IST6 400–1200

[All guides](https://www.aecups.com/en/blog/)

[**L6 lithium battery sizing: modules, cabinets, room** How AEC sizes an L6 lithium battery for an IST7 or IST6 UPS: power and energy counts, modules and cabinets for 10 to 30 minutes, floor and clearances.](https://www.aecups.com/en/blog/l6-lithium-battery-sizing/) [**UPS installation clearances: what to check on site** Clearances, operating gangways, door widths, floor load, cable entry and airflow for every AEC EMEA UPS and battery cabinet, before the delivery.](https://www.aecups.com/en/blog/ups-installation-clearances/) [**Modular UPS: how to grow power module by module** A modular UPS builds power from hot-swappable modules in one cabinet: how it grows with the load, against a conventional UPS, with IST6 examples.](https://www.aecups.com/en/blog/modular-ups/)

Read next: [UPS efficiency and ECO mode: losses and energy savings](https://www.aecups.com/en/blog/ups-efficiency-eco-mode/) [UPS redundancy: N+1 or 2N, and how much a site needs](https://www.aecups.com/en/blog/ups-redundancy-n-plus-1/) [UPS for data centres: how to choose and plan](https://www.aecups.com/en/blog/ups-for-data-centres/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST6 400–1200 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6%20400%E2%80%931200%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)
