IST6 400–1200 · Modular UPS

# IST6-1200, 12 × 100 kVA Modular UPS, 400 V, for data centres

VRLA 1200 kVA modular online UPS, 100 kVA modules

The IST6-1200 is the largest AEC UPS: twelve 100 kVA modules in a double-column cabinet, 1.2 MW in 1.2 m² of floor. For large data centres and critical infrastructure with 1 to 1.2 MW per UPS, and up to 9.6 MW with eight in parallel.

**1200 kVA / 1200 kW** Rating

**1201 × 1000 × 2000 mm** W × D × H

**662 kg without modules** Weight

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=140) [Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6-1200%2C%2012%20%C3%97%20100%20kVA%20(IST6%20400%E2%80%931200)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist6-100m-1200/v78/)

Quick answers

## IST6-1200, 12 × 100 kVA: quick answers

**What it is**: The IST6-1200 is the largest AEC UPS: twelve 100 kVA modules in a double-column cabinet, 1.2 MW in 1.2 m² of floor.

**Who it is for**: For large data centres and critical infrastructure with 1 to 1.2 MW per UPS, and up to 9.6 MW with eight in parallel.

**Supply and configuration**: 380 / 400 / 415 V

**Battery and backup**: 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional

**Size and weight**: 1201 × 1000 × 2000 mm · 662 kg without modules

**Ordering code**: IST6-1200

IST6 400–1200

## What sets apart the IST6-1200, 12 × 100 kVA

With all twelve slots used, the IST6-1200 draws 1982 A at the mains and needs 8785 m³/h of cooling air, the highest of the range. Eight units in parallel make 9.6 MW, with BSC dual-bus or three-bus layouts; a 7 m parallel cable comes with each UPS and the rings need N cables for N UPS.

Like every cabinet of the platform it runs without derating up to 40 °C, keeps 40% load with one fan failed and 15% with two, and records 200 ms of waveform before and after a fault. The energy storage mode lets the battery cut peaks and fill valleys on a plan curve.

- **Against the IST6-1000, 10 × 100 kVA** (one size down): Power modules (100 kVA) 12 against 10.

Installation

## Installing the IST6-1200, 12 × 100 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST6-1200, 12 × 100 kVA · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 800 mm; front, left, right and top: not given | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Cable entry | Top (standard); Bottom, with the side wiring cabinet | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Heat at full load | 34.6 kW at 1,200 kW load, 97.2 % efficiency | IST6 400–1200 AEC data; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | 0 to 40 °C | IST6 400–1200 AEC user manual |
| Switches and terminals | 600 kVA: switches inside the UPS cabinet. 800–1200 kVA: in the 599 mm distribution cabinet on the left. | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Module withdrawal | 760 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.163, 180 |
| Units in parallel | Up to 8 units | AEC IST6 400–1200 user manual; EMEA 2026 catalogue p.160–178 |

Size and floor

## How big it is

1201 × 1000 × 2000 mm · 662 kg without modules.

**1.2 m²** footprint

**2 m** height

Efficiency

## How efficient is the AEC IST6-1200, 12 × 100 kVA at your load?

IST6-1200, 12 × 100 kVA, 1,200 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 7.69 kW (η 97.5%) · 50%: 11.6 kW (η 98.1%) · 75%: 20.2 kW (η 97.8%) · 100%: 30.8 kW (η 97.5%). At 50% load, 24/7, it loses about 101,798 kWh a year.

**98.1** % 50% · Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)

How the curve is drawn and where each figure comes from: [the IST6 400–1200 range page](https://www.aecups.com/en/products/ist6-400-1200/#efficiency).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5% | Typical curve, derived from the datasheet efficiency of 98.1% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99.2% | Datasheet figure, load not stated | all |  |
| W-ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Double conversion, General modules up to 97.2% · Double conversion, PLUS modules up to 98.1% · ECO up to 99.2% · W-ECO up to 99%.

Drag to turn

In 3D

## Look around the IST6-1200, 12 × 100 kVA

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist6-100m-1200/v78/)

Technical data

## Technical data IST6-1200, 12 × 100 kVA

Only this model's values, from the EMEA 2026 catalogue table.

**IST6-1200, 12 × 100 kVA · Technical data**

|  |  |
| --- | --- |
| Cabinet |  |
| Power modules (100 kVA) | 12 |
| Bypass module | 4.5U |
| Input |  |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below) |
| Frequency · PF · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |
| Bypass | 304–438 V; synchronisation 50 / 60 ± 6 Hz; settable window |
| Battery |  |
| Lead-acid | 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional |
| Lithium (with BMS card) | 512 V DC nominal (384–640 V), 120–200 cells, standard 160 |
| Charging current | 20 A × number of modules · cold start · shared battery |
| Output |  |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V ± 1% |
| Power factor · THDv | settable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 3% non-linear |
| Frequency · phase error | tracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 2° unbalanced |
| Transfer | mains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms |
| Inverter overload (PF ≥ 0.95) | ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass |
| Bypass overload | ≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms |
| System |  |
| Efficiency · modes | 97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99% · energy storage, sleep, generator |
| Parallel | up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses) |
| Communication | Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS |
| Environment | 0 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 80 dB · EMC category C3 |
| W × D × H (mm) | 1201 × 1000 × 2000 |
| With distribution cabinet | 1800 mm wide |
| Weight without modules | 662 kg |

**IST6-1200, 12 × 100 kVA · Models**

| Item | IST6-1200, 12 × 100 kVA |
| --- | --- |
| Power modules (100 kVA) | 12 |
| Columns · doors | 2 · 2 |
| Internal power switches | option¹ |
| W × D (mm) · H 2000 | 1201 × 1000 |
| Weight without modules | 662 kg |
| Mains input current | 1982 A |
| Cooling air flow (min.) | 8785 m³/h |

Power module 440 × 760 × 130 mm (without ears and handles), 54 kg. Data from the IST6 400–1200 kVA user manual. Specifications are subject to change without notice.

#### **More technical details** how it works, ordering codes

Diagrams

## How the power flows: AEC IST6-1200, 12 × 100 kVA

Pick an operating mode: the path the power takes to the load lights up.

**Normal.** Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (PLUS modules; 97.2% with General modules).

### Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 100 kVA module.

modules working · redundant · free slot

Ordering codes

## Ordering codes IST6-1200, 12 × 100 kVA

**Ordering codes IST6-1200, 12 × 100 kVA**

| Code | Description |
| --- | --- |
| IST6-1200 | Modular cabinet, max. 12 × 100 kVA power modules, without modules |
| IST6-100-J | 100 kVA / 100 kW power module |
| PAR - IST6 | Parallel kit |

Questions

## Questions about the IST6-1200, 12 × 100 kVA

#### How many IST6-1200 can work in parallel?

Up to eight, for 9.6 MW, with current imbalance within 5% and N+X redundancy between UPS. Each UPS output is kept within ± 2 V and ± 0.1 Hz of the system setting.

#### What noise and environment does the IST6-1200 need?

Below 80 dB at 1 m from the front; 0–40 °C without derating, 0–95% humidity, up to 2000 m, IP20. It is not for open installations within 3.7 km of the sea.

#### How long does a 1200 kVA UPS like the IST6-1200, 12 × 100 kVA run?

3 to 26 minutes at full load (1,200 kW), and 8 to 52 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 240 × 12 V 100 Ah · 8 × 30 (IST6-1200-240X100): 3 minutes at 100% and 8 at 50%. For other loads and batteries use the backup-time tool.

#### How big is the AEC IST6-1200, 12 × 100 kVA and how much does it weigh?

The AEC IST6-1200, 12 × 100 kVA measures 1201 × 1000 × 2000 mm; weight: 662 kg without modules (EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST6-1200, 12 × 100 kVA?

In the EMEA 2026 catalogue the AEC IST6-1200, 12 × 100 kVA is listed as IST6-1200; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST6 400–1200

[The whole range](https://www.aecups.com/en/products/ist6-400-1200/)

[**IST6-400H, 4 × 100 kVA** 400 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-400k-4x100/) [**IST6-500H, 5 × 100 kVA** 500 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-500k-5x100/) [**IST6-600H, 6 × 100 kVA** 600 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-600k-6x100/) [**IST6-800, 8 × 100 kVA** 800 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-800k-8x100/) [**IST6-1000, 10 × 100 kVA** 1000 kVA · smaller rating](https://www.aecups.com/en/products/ist6-400-1200/ist6-1000k-10x100/) **IST6-1200, 12 × 100 kVA** 1200 kVA

Batteries and cabinets: [L6 Lithium](https://www.aecups.com/en/products/l6-lithium/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/)

Shared by the whole range, on the IST6 400–1200 page: [the display simulator](https://www.aecups.com/en/products/ist6-400-1200/#display) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist6-400-1200/#gallery).

Read next: [UPS efficiency and ECO mode: losses and energy savings](https://www.aecups.com/en/blog/ups-efficiency-eco-mode/) [L6 lithium battery sizing: modules, cabinets, room](https://www.aecups.com/en/blog/l6-lithium-battery-sizing/) [UPS installation clearances: what to check on site](https://www.aecups.com/en/blog/ups-installation-clearances/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST6-1200, 12 × 100 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6-1200%2C%2012%20%C3%97%20100%20kVA%20(IST6%20400%E2%80%931200)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)