IST6 400–1200 · Modular UPS

# IST6-400H, 4 × 100 kVA Modular UPS, 400 V, for data centres

VRLA 400 kVA modular online UPS, 100 kVA modules

The IST6 400 kVA is a single-column modular online UPS for four 100 kVA power modules, 801 × 1000 × 2000 mm, with mains, output, bypass and maintenance bypass switches inside. For data centres and sites of 300 to 400 kW that want the 100 kVA platform from the start, with switchgear on board.

**400 kVA / 400 kW** Rating

**801 × 1000 × 2000 mm** W × D × H

**345 kg without modules** Weight

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=140) [Contact us](https://www.aecups.com/en/contacts/?interest=Modular%20UPS&msg=About%20the%20AEC%20IST6-400H%2C%204%20%C3%97%20100%20kVA%20(IST6%20400%E2%80%931200)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist6-100m-600/v77/)

Quick answers

## IST6-400H, 4 × 100 kVA: quick answers

**What it is**: The IST6 400 kVA is a single-column modular online UPS for four 100 kVA power modules, 801 × 1000 × 2000 mm, with mains, output, bypass and maintenance bypass switches inside.

**Who it is for**: For data centres and sites of 300 to 400 kW that want the 100 kVA platform from the start, with switchgear on board.

**Supply and configuration**: 380 / 400 / 415 V

**Battery and backup**: 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional

**Size and weight**: 801 × 1000 × 2000 mm · 345 kg without modules

**Ordering code**: IST6-400H

IST6 400–1200

## What sets apart the IST6-400H, 4 × 100 kVA

400 kVA is also sold on the 50 kW-module frame, as a different product: the IST6 400 kVA with 8 × 50 kVA modules of the IST6 200–500 range, a double column of 1203 × 864 × 2000 mm. This one is a single 801 × 1000 × 2000 mm column.

The 400 kVA is the lightest cabinet of the range, 345 kg without modules, and the only one with a 3U bypass module (4.5U from 500 kVA). Its four modules are 54 kg each, 440 × 760 × 130 mm: a lift truck or three installers to handle them. Rear clearance is 500 mm here (800 mm from 800 kVA), and a earthing detection kit for the battery is an option on 400–600 kVA.

With all four slots used, N+1 at 400 kVA comes from a second UPS in parallel (up to eight); at 300 kVA the fourth module is the redundant one. Fully loaded it draws 661 A at the mains and needs at least 3744 m³/h of cooling air.

- **Against the IST6-500H, 5 × 100 kVA** (one size up): Power modules (100 kVA) 4 against 5; Bypass module 3U against 4.5U; Weight without modules 345 kg against 434 kg.

Installation

## Installing the IST6-400H, 4 × 100 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST6-400H, 4 × 100 kVA · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 800 mm; front, left, right and top: not given | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Cable entry | Top (standard); Bottom, with the side wiring cabinet | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Cooling air | 3,744 m³/h | IST6 400–1200 AEC data |
| Heat at full load | 11.5 kW at 400 kW load, 97.2 % efficiency | IST6 400–1200 AEC data; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | 0 to 40 °C | IST6 400–1200 AEC user manual |
| Switches and terminals | 600 kVA: switches inside the UPS cabinet. 800–1200 kVA: in the 599 mm distribution cabinet on the left. | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Module withdrawal | 760 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.163, 180 |
| Units in parallel | Up to 8 units | AEC IST6 400–1200 user manual; EMEA 2026 catalogue p.160–178 |

Size and floor

## How big it is

801 × 1000 × 2000 mm · 345 kg without modules.

**0.8 m²** footprint

**2 m** height

Efficiency

## How efficient is the AEC IST6-400H, 4 × 100 kVA at your load?

IST6-400H, 4 × 100 kVA, 400 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 2.56 kW (η 97.5%) · 50%: 3.87 kW (η 98.1%) · 75%: 6.75 kW (η 97.8%) · 100%: 10.3 kW (η 97.5%). At 50% load, 24/7, it loses about 33,933 kWh a year.

**98.1** % 50% · Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)

How the curve is drawn and where each figure comes from: [the IST6 400–1200 range page](https://www.aecups.com/en/products/ist6-400-1200/#efficiency).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5% | Typical curve, derived from the datasheet efficiency of 98.1% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99.2% | Datasheet figure, load not stated | all |  |
| W-ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Double conversion, General modules up to 97.2% · Double conversion, PLUS modules up to 98.1% · ECO up to 99.2% · W-ECO up to 99%.

In 3D

## Look around the IST6-400H, 4 × 100 kVA

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist6-100m-600/v77/)

Technical data

## Technical data IST6-400H, 4 × 100 kVA

Only this model's values, from the EMEA 2026 catalogue table.

**IST6-400H, 4 × 100 kVA · Technical data**

|  |  |
| --- | --- |
| Cabinet |  |
| Power modules (100 kVA) | 4 |
| Bypass module | 3U |
| Input |  |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below) |
| Frequency · PF · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |
| Bypass | 304–438 V; synchronisation 50 / 60 ± 6 Hz; settable window |
| Battery |  |
| Lead-acid | 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional |
| Lithium (with BMS card) | 512 V DC nominal (384–640 V), 120–200 cells, standard 160 |
| Charging current | 20 A × number of modules · cold start · shared battery |
| Output |  |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V ± 1% |
| Power factor · THDv | settable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 3% non-linear |
| Frequency · phase error | tracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 2° unbalanced |
| Transfer | mains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms |
| Inverter overload (PF ≥ 0.95) | ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass |
| Bypass overload | ≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms |
| System |  |
| Efficiency · modes | 97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99% · energy storage, sleep, generator |
| Parallel | up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses) |
| Communication | Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS |
| Environment | 0 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 80 dB · EMC category C3 |
| W × D × H (mm) | 801 × 1000 × 2000 |
| Weight without modules | 345 kg |

**IST6-400H, 4 × 100 kVA · Models**

| Item | IST6-400H, 4 × 100 kVA |
| --- | --- |
| Power modules (100 kVA) | 4 |
| Columns · doors | 1 · 1 |
| Internal power switches | yes\* |
| W × D (mm) · H 2000 | 801 × 1000 |
| Weight without modules | 345 kg |
| Mains input current | 661 A |
| Cooling air flow (min.) | 3744 m³/h |

Power module 440 × 760 × 130 mm (without ears and handles), 54 kg. Data from the IST6 400–1200 kVA user manual. Specifications are subject to change without notice.

#### **More technical details** how it works, ordering codes

Diagrams

## How the power flows: AEC IST6-400H, 4 × 100 kVA

Pick an operating mode: the path the power takes to the load lights up.

**Normal.** Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (PLUS modules; 97.2% with General modules).

### Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 100 kVA module.

modules working · redundant · free slot

Ordering codes

## Ordering codes IST6-400H, 4 × 100 kVA

**Ordering codes IST6-400H, 4 × 100 kVA**

| Code | Description |
| --- | --- |
| IST6-400H | Modular cabinet, max. 4 × 100 kVA power modules, without modules |
| IST6-100-J | 100 kVA / 100 kW power module |
| PAR - IST6 | Parallel kit |

Questions

## Questions about the IST6-400H, 4 × 100 kVA

#### Does the IST6 400 kVA include the power switches?

Yes: on 400–600 kVA the mains, output, maintenance bypass and bypass switches are inside the cabinet; a version without switches is also available. From 800 kVA the switches move to an optional distribution cabinet.

#### Can the IST6 400 kVA stand against a wall?

Yes, with the top air outlet kit, shipped as an accessory for 400–600 kVA: hot air leaves from the top instead of the rear; the top clearance then rises to 650 mm. Without it, keep 500 mm free at the rear.

#### How big is the AEC IST6-400H, 4 × 100 kVA and how much does it weigh?

The AEC IST6-400H, 4 × 100 kVA measures 801 × 1000 × 2000 mm; weight: 345 kg without modules (EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST6-400H, 4 × 100 kVA?

In the EMEA 2026 catalogue the AEC IST6-400H, 4 × 100 kVA is listed as IST6-400H; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST6 400–1200

[The whole range](https://www.aecups.com/en/products/ist6-400-1200/)

**IST6-400H, 4 × 100 kVA** 400 kVA [**IST6-500H, 5 × 100 kVA** 500 kVA · larger rating](https://www.aecups.com/en/products/ist6-400-1200/ist6-500k-5x100/) [**IST6-600H, 6 × 100 kVA** 600 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-600k-6x100/) [**IST6-800, 8 × 100 kVA** 800 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-800k-8x100/) [**IST6-1000, 10 × 100 kVA** 1000 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-1000k-10x100/) [**IST6-1200, 12 × 100 kVA** 1200 kVA](https://www.aecups.com/en/products/ist6-400-1200/ist6-1200k-12x100/)

Batteries and cabinets: [L6 Lithium](https://www.aecups.com/en/products/l6-lithium/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/)

Shared by the whole range, on the IST6 400–1200 page: [the display simulator](https://www.aecups.com/en/products/ist6-400-1200/#display) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist6-400-1200/#gallery).

Read next: [UPS efficiency and ECO mode: losses and energy savings](https://www.aecups.com/en/blog/ups-efficiency-eco-mode/) [L6 lithium battery sizing: modules, cabinets, room](https://www.aecups.com/en/blog/l6-lithium-battery-sizing/) [UPS installation clearances: what to check on site](https://www.aecups.com/en/blog/ups-installation-clearances/)