description: "The IST7-10 is a 10 kVA / 10 kW online double-conversion UPS in the small IST7 frame, 250 mm wide."
language: en
---

IST7 10–40 · Three-phase UPS

# IST7-10 Three-phase UPS 10 kVA, 400 V

VRLA 10 kVA online UPS, 3/3 · 3/1 · 1/1

The IST7-10 is a 10 kVA / 10 kW online double-conversion UPS in the small IST7 frame, 250 mm wide. For server rooms, network cabinets and small plants that need three-phase or single-phase output and want the battery inside the UPS.

**10 kVA / 10 kW** Rating

**250 × 806 × 880 mm** W × D × H

**64 / 95 kg** Weight

**± 96 … ± 240 V DC** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=65) [Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST7-10%20(IST7%2010%E2%80%9340)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist7-10/v99/)

Quick answers

## IST7-10: quick answers

**What it is**: The IST7-10 is a 10 kVA / 10 kW online double-conversion UPS in the small IST7 frame, 250 mm wide.

**Who it is for**: For server rooms, network cabinets and small plants that need three-phase or single-phase output and want the battery inside the UPS.

**Supply and configuration**: 3/3 · 3/1 · 1/1 · L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V

**Battery and backup**: ± 96 … ± 240 V DC

**Size and weight**: 250 × 806 × 880 mm · 64 / 95 kg

**Ordering code**: IST7-10 · IST7-10-32X9 · IST7-10-150X9

IST7 10–40

## What sets apart the IST7-10

The IST7-10 is the only IST7 that runs at full power from 16 batteries: its string can be set from 16 to 40 blocks of 12 V (±48 to ±120 cells, ±96 to ±240 V DC), where the 20–40 kVA models need at least 24 and reach full power from 32. That makes it the simplest IST7 to fit with an internal battery: the S model takes 16, 24, 30, 32, 36 or 40 blocks of 9 Ah inside the same 250 × 806 × 880 mm cabinet.

It accepts all three wiring configurations: 3/3, 3/1 and 1/1. In 1/1 the input current rises to 58.6 A on a 16 mm² cable, against 19.5 A per phase in 3/3: check which supply the site has before choosing. With 64 kg (standard) or 95 kg (S) it stands on castors and is moved by two people.

- **Against the IST7-20** (one size up): Rated power 10 kVA / 10 kW against 20 kVA / 20 kW; Battery voltage ± 96 … ± 240 V DC against ± 144 … ± 240 V DC; Cells (2 V), settable · default ± 48 … ± 120 · ± 48 against ± 72 … ± 120 · ± 96; Weight standard / S 64 / 95 kg against 64 / 137.6 kg.

Planning data

## IST7-10: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-10.

### Two frames, one family

**IST7-10 · Two frames, one family**

| Difference | IST7-10 · 20 |
| --- | --- |
| Ratings · kVA = kW | 10 · 20 |
| Input / output | 3/3 · 3/1 · 1/1 |
| Set on site with | wiring, connector jumpers, screen |
| Cabinet W × D × H | 250 × 806 × 880 mm |
| Weight standard / S | 64 / 95 kg (10) · 64 / 137.6 kg (20) |
| Internal batteries (S), 12 V 9 Ah | 16 – 40 blocks (10) · 36 or 40 (20) |
| Battery cells, settable | ±48 … ±120 (10) · ±72 … ±120 (20) |
| Charge current | 1–10 A, default 1 A |
| Output distortion, resistive load | ≤ 2% |
| Max. input current, 3/3 | 19.5 A (10) · 35.5 A (20) |
| Max. battery current | 54.8 A |
| Feet | castors |

### Front, rear and footprint

**IST7-10 · Front, rear and footprint**

| Model | IST7-10 |
| --- | --- |
| W × D × H (mm) | 250 × 806 × 880 |
| Standard | 64 kg |
| S | 95 kg |

### Ready for the site, cables and breakers sized

**IST7-10 · Ready for the site, cables and breakers sized**

| Model | IST7-10 |
| --- | --- |
| AC input (A) | 19.5 |
| AC output (A) | 15.2 |
| Battery (A) | 54.8 |
| Input · output breaker | 32 A 3P |
| Battery breaker | 100 A 3P |
| AC cables (mm²) | 4 |
| Battery (mm²) | 10 |
| PE (mm²) | 4 |

### Single-phase output · 3/1 and 1/1

**IST7-10 · Single-phase output · 3/1 and 1/1**

| Model | IST7-10 |
| --- | --- |
| AC input (A) (3/1) | 19.5 |
| Bypass input (A) | 58.6 |
| AC output (A) | 45.6 |
| Bypass · output breaker | 80 A 1P · 80 A 1P |
| N, bypass, output (mm²) | 16 |
| PE (mm²) | 2 × 10 |

### BB5 to BB8, matched to every IST7

**IST7-10 · BB5 to BB8, matched to every IST7**

| UPS | IST7-10 · 20 |
| --- | --- |
| BB5 | 30–40 × 24 Ah · 30–38 × 40 Ah |
| BB6 | 30–36 × 60 Ah |
| BB7 | 30–36 × 80 / 100 Ah |
| BB8 | 40 / 60 × 80 / 100 Ah |

### One code for the UPS and its batteries

**IST7-10 · One code for the UPS and its batteries**

| Battery | Cabinet | IST7-10 |
| --- | --- | --- |
| Internal 9 Ah · S | — | 16 · 24 · 30 · 32 · 36 · 40 |
| Internal 9 Ah + BB5 | BB5 | 150 · 160 |
| 24 Ah | BB5 | 30 – 40 |
| 40 Ah | BB5 | 30 – 38 |
| 60 Ah | BB6 | 30 – 36 |
| 80 Ah · 100 Ah | BB7 | 30 – 36 |
| 80 Ah · 100 Ah | BB8 | 40 · 60 |

Installation

## Installing the IST7-10: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST7-10 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3 |
| Cable entry | Rear terminals, cables tied down to the bottom | AEC IST7 10–40 user manual |
| Heat at full load | 0.42 kW at 10 kW load, 96 % efficiency | AEC IST7 10–40 user manual p.83 §A; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST7 10–40 user manual p.6 §1.3 |
| Switches and terminals | Input, bypass, battery, output and maintenance bypass breakers on the rear panel; terminals behind the wiring cover. No front door. | AEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3 |
| Units in parallel | Up to 4 units | AEC IST7 10–40 user manual p.71 §4.5.7 |

Size and floor

## How big it is

250 × 806 × 880 mm · 64 / 95 kg.

**0.2 m²** footprint

**318–471 kg/m²** floor load

**0.88 m** height

Floor load = weight ÷ footprint: 318 kg/m² at the lowest weight given (64 kg), 471 kg/m² at the highest (95 kg).

Efficiency

## How efficient is the AEC IST7-10 at your load?

IST7-10, 10 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.12 kW (η 95.4%) · 50%: 0.21 kW (η 96%) · 75%: 0.34 kW (η 95.7%) · 100%: 0.48 kW (η 95.4%). At 50% load, 24/7, it loses about 1,825 kWh a year.

**96** % 50% · Typical curve, derived from the datasheet efficiency of 96% (AEC method)

How the curve is drawn and where each figure comes from: [the IST7 10–40 range page](https://www.aecups.com/en/products/ist7-10-40/#efficiency).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4% | Typical curve, derived from the datasheet efficiency of 96% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Online, double conversion up to 96% · ECO up to 99%.

Drag to turn

In 3D

## Look around the IST7-10

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist7-10/v99/)

The turntable shows the IST7-20; the full 3D view opens on the IST7-10.

Technical data

## Technical data IST7-10

Only this model's values, from the EMEA 2026 catalogue table.

**IST7-10 · Technical data**

|  |  |
| --- | --- |
| General |  |
| Rated power (kVA / kW) | 10 / 10 |
| Input / output configuration | 3/3 · 3/1 · 1/1 |
| Input |  |
| Connection | 3 + N + PE (settable 1 + N + PE) |
| Voltage range | 176–280 V at 100% load · 80–176 V with linear derating |
| Frequency range | 39.5–70.5 Hz |
| Bypass synchronisation range · bypass voltage range | 50 / 60 Hz ± 10% (self-adapting) · 10 / 15 / 20% (default 20%) |
| Power factor · THDi | ≥ 0.99 · ≤ 3% resistive full load, ≤ 5% non-linear full load |
| Battery |  |
| Battery voltage (Vdc) | ± 96 … ± 240 |
| Cells (2 V), settable · default | ± 48 … ± 120 · ± 48 |
| Charge current (A) | 1–10 (default 1) |
| Output |  |
| Connection | 3 + N + PE (settable 1 + N + PE) |
| Voltage | L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V |
| Frequency | tracks the bypass; with bypass absent or out of range 50 ± 0.1 or 60 ± 0.1 Hz (default 50) |
| Waveform · power factor | sine wave · 1 (settable 0.9) |
| Voltage distortion (resistive / non-linear) | ≤ 2% / ≤ 4% |
| Transfer time inverter ↔ bypass | < 1 ms synchronised · < 10 ms not synchronised |
| Inverter overload (PF 1) | < 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · 155–200% 200 ms · > 200% immediate |
| Bypass overload | < 130% continuous · 130–155% 1 min · > 155% 200 ms |
| System |  |
| System efficiency | up to 96% · 99% in ECO mode (single UPS) |
| Parallel | up to 4 units with the optional parallel kit |
| Display · communication | touch screen · RS485 · dry contacts: EPO, 1 input, 5 outputs · optional cards: SNMP, protocol transfer, dry-contact kit |
| DC start · alarms | battery start fitted · battery low voltage, mains abnormal, UPS fault, output overload |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · IP20 · noise < 55 dB (25 °C) · up to 2000 m |
| Dimensions W × D × H | 250 × 806 × 880 mm |
| Weight standard / S | 64 / 95 kg |

**IST7-10 · Models**

| Item | IST7-10 |
| --- | --- |
| Rated power (kVA / kW) | 10 / 10 |
| Input / output | 3/3 · 3/1 · 1/1 |
| W × D × H (mm) | 250 × 806 × 880 |
| Weight standard | 64 kg |
| Weight S | 95 kg |

S: with internal battery. Outer dimensions in mm: 10–20 kVA width 250 (308 with feet), depth 756 (806 overall), height 802 (880 overall); 30–40 kVA width 300 (358 with feet), depth 787 (842 overall), height 1143 (1250 overall). Ratings are kVA = kW at output PF 1; PF 0.9 settable. Battery voltage and capacity set on the screen at commissioning. Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST7-10

**Ordering codes IST7-10**

| Code | Description |
| --- | --- |
| IST7-10 · IST7-20 · IST7-30 · IST7-40 | Standard models, external batteries only (e.g. IST7-30: 30 kVA, external batteries). |
| IST7-10-32X9 | 10 kVA S model, 32 × 12 V 9 Ah inside. |
| IST7-10-150X9 | 10 kVA, 30 × 9 Ah inside + 120 in BB5. |
| Parallel kit | Option: built-in card with parallel cables, CAN communication, up to 4 units. |
| SNMP card | Option: network monitoring in an intelligent slot, configured through its web page. |
| Dry-contact kit | Option: 3 outputs and 2 inputs in an intelligent slot. |
| Protocol transfer card | Option: RS485 + RS232 on DB9; RS485 reserved for lithium battery communication. |

Questions

## Questions about the IST7-10

#### Can the IST7-10 run from a single-phase supply?

Yes. The IST7-10 is set to 1/1 (single-phase in and out) through the wiring, the connector jumpers and the screen; it also works 3/3 and 3/1. In 1/1 the catalogue gives 58.6 A at the bypass input and 45.6 A at the output.

#### How many internal batteries can the IST7-10 hold?

The S model holds 16, 24, 30, 32, 36 or 40 batteries of 12 V 9 Ah (code IST7-10-32X9, for example). For longer backup the S model also takes a BB5 cabinet: IST7-10-150X9 is 30 blocks inside plus 120 in the BB5.

#### Which breakers does the IST7-10 need?

In 3/3 the catalogue recommends 32 A 3P at input and output and a 100 A 3P battery breaker, with 4 mm² AC cables and 10 mm² battery cables for about 5 m. In 3/1 and 1/1 bypass and output take 80 A 1P breakers.

#### How long does a 10 kVA UPS like the IST7-10 run?

2 to 400 minutes at full load (10 kW), and 5 to 958 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 16 × 12 V 9 Ah (IST7-10-16X9): 2 minutes at 100% and 5 at 50%. For other loads and batteries use the backup-time tool.

#### How big is the AEC IST7-10 and how much does it weigh?

The AEC IST7-10 measures 250 × 806 × 880 mm; weight: 64 / 95 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST7-10?

In the EMEA 2026 catalogue the AEC IST7-10 is listed as IST7-10, IST7-10-32X9, IST7-10-150X9; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST7 10–40

[The whole range](https://www.aecups.com/en/products/ist7-10-40/)

**IST7-10** 10 kVA [**IST7-20** 20 kVA · larger rating](https://www.aecups.com/en/products/ist7-10-40/ist7-20k/) [**IST7-30** 30 kVA](https://www.aecups.com/en/products/ist7-10-40/ist7-30k/) [**IST7-40** 40 kVA](https://www.aecups.com/en/products/ist7-10-40/ist7-40k/)

Batteries and cabinets: [BB4](https://www.aecups.com/en/products/battery-cabinets/bb4/) [BB5](https://www.aecups.com/en/products/battery-cabinets/bb5/) [BB6](https://www.aecups.com/en/products/battery-cabinets/bb6/) [OZ Power 12 V 9 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-9ah/) [OZ Power 12 V 40 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-40ah/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/)

Shared by the whole range, on the IST7 10–40 page: [the display simulator](https://www.aecups.com/en/products/ist7-10-40/#display) · [how the power flows in each mode](https://www.aecups.com/en/products/ist7-10-40/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist7-10-40/#gallery).

Read next: [UPS datasheet explained: every line, with examples](https://www.aecups.com/en/blog/how-to-read-a-ups-datasheet/) [UPS glossary: 87 UPS terms and acronyms explained](https://www.aecups.com/en/blog/ups-glossary/) [Three-phase UPS: configurations, sizing and installation](https://www.aecups.com/en/blog/three-phase-ups/)