# IST7-40 Three-phase UPS 40 kVA, 400 V

VRLA 40 kVA online UPS, 3/3 · 3/1

The IST7-40 is a 40 kVA / 40 kW online double-conversion UPS, the largest of the IST7 10–40 range, in the 300 × 842 × 1250 mm frame. For data rooms, hospitals' technical rooms and industrial lines of 30 to 40 kW, and for parallel systems of up to four units.

**40 kVA / 40 kW** Rating

**300 × 842 × 1250 mm** W × D × H

**102.5 / 249.7 kg** Weight

**± 144 … ± 240 V DC** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=65) [Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST7-40%20(IST7%2010%E2%80%9340)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist7-40/v103/)

Quick answers

## IST7-40: quick answers

**What it is**: The IST7-40 is a 40 kVA / 40 kW online double-conversion UPS, the largest of the IST7 10–40 range, in the 300 × 842 × 1250 mm frame.

**Who it is for**: For data rooms, hospitals' technical rooms and industrial lines of 30 to 40 kW, and for parallel systems of up to four units.

**Supply and configuration**: 3/3 · 3/1 · L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V

**Battery and backup**: ± 144 … ± 240 V DC

**Size and weight**: 300 × 842 × 1250 mm · 102.5 / 249.7 kg

**Ordering code**: IST7-40 · IST7-40-34X60

IST7 10–40

## What sets apart the IST7-40

The IST7-40 shares cabinet and weight with the IST7-30 (102.5 kg standard, 249.7 kg S) but draws 81.7 A per phase in 3/3 and up to 109.6 A from the battery, so it takes a 175 A 3P battery breaker. The catalogue's operating-cost example is built on this model: at 80% load (32 kW) and 96% efficiency the losses are 1.33 kW, about 11,680 kWh a year; in ECO mode at 99% they fall to 0.32 kW.

Up to four IST7-40 units run in parallel with the optional kit, for 160 kVA of capacity or N+1 redundancy. A version with an internal transformer (IST7-40 T) is listed at 222 kg.

- **Against the IST7-30** (one size down): Rated power 40 kVA / 40 kW against 30 kVA / 30 kW.

Planning data

## IST7-40: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-40.

### Two frames, one family

**IST7-40 · Two frames, one family**

| Difference | IST7-30 · 40 |
| --- | --- |
| Ratings · kVA = kW | 30 · 40 |
| Input / output | 3/3 · 3/1 |
| Set on site with | wiring, jumpers, screen, mode connector |
| Cabinet W × D × H | 300 × 842 × 1250 mm |
| Weight standard / S | 102.5 / 249.7 kg |
| Internal batteries (S), 12 V 9 Ah | 2 × 36 or 2 × 40 blocks |
| Battery cells, settable | ±72 … ±120 |
| Charge current | 1–20 A, default 2 A |
| Output distortion, resistive load | ≤ 1% |
| Max. input current, 3/3 | 65.7 A (30) · 81.7 A (40) |
| Max. battery current | 82.2 A (30) · 109.6 A (40) |
| Feet | castors and levelling feet |

### Front, rear and footprint

**IST7-40 · Front, rear and footprint**

| Model | IST7-40 |
| --- | --- |
| W × D × H (mm) | 300 × 842 × 1250 |
| Standard | 102.5 kg |
| S | 249.7 kg |

### Ready for the site, cables and breakers sized

**IST7-40 · Ready for the site, cables and breakers sized**

| Model | IST7-40 |
| --- | --- |
| AC input (A) | 81.7 |
| AC output (A) | 60.6 |
| Battery (A) | 109.6 |
| Input · output breaker | 100 A 3P |
| Battery breaker | 175 A 3P |
| AC cables (mm²) | 16 |
| Battery (mm²) | 2 × 10 |
| PE (mm²) | 16 |

### Single-phase output · 3/1 and 1/1

**IST7-40 · Single-phase output · 3/1 and 1/1**

| Model | IST7-40 |
| --- | --- |
| AC input (A) (3/1) | 81.7 |
| Bypass input (A) | 245.0 |
| AC output (A) | 181.8 |
| Bypass · output breaker | 300 A 1P · 250 A 1P |
| N, bypass, output (mm²) | 2 × 25 |
| PE (mm²) | 25 |

### BB5 to BB8, matched to every IST7

**IST7-40 · BB5 to BB8, matched to every IST7**

| UPS | IST7-30 · 40 |
| --- | --- |
| BB5 | 36–40 × 24 Ah · 30–38 × 40 Ah |
| BB6 | 30–36 × 60 Ah |
| BB7 | 30–36 × 80 / 100 Ah |
| BB8 | 40 / 60 × 80 / 100 Ah |

### One code for the UPS and its batteries

**IST7-40 · One code for the UPS and its batteries**

| Battery | Cabinet | IST7-40 |
| --- | --- | --- |
| Internal 9 Ah · S | — | 72 · 80 (2 strings) |
| Internal 9 Ah + BB5 | BB5 | 200 |
| 24 Ah | BB5 | 36 · 38 · 40 |
| 40 Ah | BB5 | 30\* · 32 – 38 |
| 60 Ah | BB6 | 30\* · 32 – 36 |
| 80 Ah · 100 Ah | BB7 | 30\* · 32 – 36 |
| 80 Ah · 100 Ah | BB8 | 40 · 60\* |

Installation

## Installing the IST7-40: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST7-40 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3 |
| Cable entry | Rear terminals, cables tied down to the bottom | AEC IST7 10–40 user manual |
| Heat at full load | 1.67 kW at 40 kW load, 96 % efficiency | AEC IST7 10–40 user manual p.83 §A; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST7 10–40 user manual p.6 §1.3 |
| Switches and terminals | Input, bypass, battery, output and maintenance bypass breakers on the rear panel; terminals behind the wiring cover. No front door. | AEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3 |
| Units in parallel | Up to 4 units | AEC IST7 10–40 user manual p.71 §4.5.7 |

Size and floor

## How big it is

300 × 842 × 1250 mm · 102.5 / 249.7 kg.

**0.25 m²** footprint

**406–989 kg/m²** floor load

**1.25 m** height

Floor load = weight ÷ footprint: 406 kg/m² at the lowest weight given (102.5 kg), 989 kg/m² at the highest (249.7 kg).

Efficiency

## How efficient is the AEC IST7-40 at your load?

IST7-40, 40 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.48 kW (η 95.4%) · 50%: 0.83 kW (η 96%) · 75%: 1.35 kW (η 95.7%) · 100%: 1.93 kW (η 95.4%). At 50% load, 24/7, it loses about 7,300 kWh a year.

**96** % 50% · Typical curve, derived from the datasheet efficiency of 96% (AEC method)

How the curve is drawn and where each figure comes from: [the IST7 10–40 range page](https://www.aecups.com/en/products/ist7-10-40/#efficiency).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4% | Typical curve, derived from the datasheet efficiency of 96% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Online, double conversion up to 96% · ECO up to 99%.

Drag to turn

In 3D

## Look around the IST7-40

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist7-40/v103/)

Technical data

## Technical data IST7-40

Only this model's values, from the EMEA 2026 catalogue table.

**IST7-40 · Technical data**

|  |  |
| --- | --- |
| General |  |
| Rated power (kVA / kW) | 40 / 40 |
| Input / output configuration | 3/3 · 3/1 |
| Input |  |
| Connection | 3 + N + PE |
| Voltage range | 176–280 V at 100% load · 80–176 V with linear derating |
| Frequency range | 39.5–70.5 Hz |
| Bypass synchronisation range · bypass voltage range | 50 / 60 Hz ± 10% (self-adapting) · 10 / 15 / 20% (default 20%) |
| Power factor · THDi | ≥ 0.99 · ≤ 3% resistive full load, ≤ 5% non-linear full load |
| Battery |  |
| Battery voltage (Vdc) | ± 144 … ± 240 |
| Cells (2 V), settable · default | ± 72 … ± 120 · ± 96 |
| Charge current (A) | 1–20 (default 2) |
| Output |  |
| Connection | 3 + N + PE |
| Voltage | L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V |
| Frequency | tracks the bypass; with bypass absent or out of range 50 ± 0.1 or 60 ± 0.1 Hz (default 50) |
| Waveform · power factor | sine wave · 1 (settable 0.9) |
| Voltage distortion (resistive / non-linear) | ≤ 1% / ≤ 4% |
| Transfer time inverter ↔ bypass | < 1 ms synchronised · < 10 ms not synchronised |
| Inverter overload (PF 1) | < 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · 155–200% 200 ms · > 200% immediate |
| Bypass overload | < 130% continuous · 130–155% 1 min · > 155% 200 ms |
| System |  |
| System efficiency | up to 96% · 99% in ECO mode (single UPS) |
| Parallel | up to 4 units with the optional parallel kit |
| Display · communication | touch screen · RS485 · dry contacts: EPO, 1 input, 5 outputs · optional cards: SNMP, protocol transfer, dry-contact kit |
| DC start · alarms | battery start fitted · battery low voltage, mains abnormal, UPS fault, output overload |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · IP20 · noise < 55 dB (25 °C) · up to 2000 m |
| Dimensions W × D × H | 300 × 842 × 1250 mm |
| Weight standard / S | 102.5 / 249.7 kg |

**IST7-40 · Models**

| Item | IST7-40 |
| --- | --- |
| Rated power (kVA / kW) | 40 / 40 |
| Input / output | 3/3 · 3/1 |
| W × D × H (mm) | 300 × 842 × 1250 |
| Weight standard | 102.5 kg |
| Weight S | 249.7 kg |

20–40 kVA with ±72 … ±90 cells (24–30 blocks): output 75% of rating. S: with internal battery. IST7-40 T (internal transformer): 222 kg. Outer dimensions in mm: 10–20 kVA width 250 (308 with feet), depth 756 (806 overall), height 802 (880 overall); 30–40 kVA width 300 (358 with feet), depth 787 (842 overall), height 1143 (1250 overall). Ratings are kVA = kW at output PF 1; PF 0.9 settable. Battery voltage and capacity set on the screen at commissioning. Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST7-40

**Ordering codes IST7-40**

| Code | Description |
| --- | --- |
| IST7-10 · IST7-20 · IST7-30 · IST7-40 | Standard models, external batteries only (e.g. IST7-30: 30 kVA, external batteries). |
| IST7-40-34X60 | 40 kVA + BB6, 34 × 60 Ah. |
| Parallel kit | Option: built-in card with parallel cables, CAN communication, up to 4 units. |
| SNMP card | Option: network monitoring in an intelligent slot, configured through its web page. |
| Dry-contact kit | Option: 3 outputs and 2 inputs in an intelligent slot. |
| Protocol transfer card | Option: RS485 + RS232 on DB9; RS485 reserved for lithium battery communication. |

Questions

## Questions about the IST7-40

#### How much energy does the IST7-40 lose in a year?

At 80% load (32 kW), 8,760 hours a year, the catalogue gives 1.33 kW of losses and 11,680 kWh a year in double conversion at 96%, and 0.32 kW and 2,830 kWh in ECO mode at 99% (single UPS). Cooling is excluded; the values are indicative.

#### Can four IST7-40 work together?

Yes. With the optional parallel kit (a built-in card with CAN communication and two redundant RJ45 ports) up to four units share the load, in redundant or expand mode. ECO mode is for a single UPS only.

#### What battery cabinet suits a 40 kVA IST7?

BB5 to BB8: the catalogue lists BB5 with 36–40 × 24 Ah or 30–38 × 40 Ah and BB6 with 30–36 × 60 Ah. It also lists BB7 with 30–36 × 80 / 100 Ah and BB8 with 40 or 60 × 80 / 100 Ah. For example IST7-40-34X60, a BB6 with 34 × 60 Ah. Strings of 30 blocks limit the output to 75%.

#### How long does a 40 kVA UPS like the IST7-40 run?

3 to 35 minutes at full load (40 kW), and 6 to 152 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 36 × 12 V 24 Ah (IST7-40-36X24): 3 minutes at 100% and 10 at 50%. For other loads and batteries use the backup-time tool.

#### How big is the AEC IST7-40 and how much does it weigh?

The AEC IST7-40 measures 300 × 842 × 1250 mm; weight: 102.5 / 249.7 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST7-40?

In the EMEA 2026 catalogue the AEC IST7-40 is listed as IST7-40, IST7-40-34X60; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST7 10–40

[The whole range](https://www.aecups.com/en/products/ist7-10-40/)

[**IST7-10** 10 kVA](https://www.aecups.com/en/products/ist7-10-40/ist7-10k/) [**IST7-20** 20 kVA](https://www.aecups.com/en/products/ist7-10-40/ist7-20k/) [**IST7-30** 30 kVA · smaller rating](https://www.aecups.com/en/products/ist7-10-40/ist7-30k/) **IST7-40** 40 kVA

Batteries and cabinets: [BB4](https://www.aecups.com/en/products/battery-cabinets/bb4/) [BB5](https://www.aecups.com/en/products/battery-cabinets/bb5/) [BB6](https://www.aecups.com/en/products/battery-cabinets/bb6/) [BB7](https://www.aecups.com/en/products/battery-cabinets/bb7/) [BB8](https://www.aecups.com/en/products/battery-cabinets/bb8/) [OZ Power 12 V 60 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-60ah/) [OZ Power 12 V 100 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-100ah/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/)

Shared by the whole range, on the IST7 10–40 page: [the display simulator](https://www.aecups.com/en/products/ist7-10-40/#display) · [how the power flows in each mode](https://www.aecups.com/en/products/ist7-10-40/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist7-10-40/#gallery).

Read next: [UPS datasheet explained: every line, with examples](https://www.aecups.com/en/blog/how-to-read-a-ups-datasheet/) [UPS glossary: 87 UPS terms and acronyms explained](https://www.aecups.com/en/blog/ups-glossary/) [Three-phase UPS: configurations, sizing and installation](https://www.aecups.com/en/blog/three-phase-ups/)