# IST7-60 Three-phase online UPS 60 kVA, 400 V

VRLA 60 kVA three-phase online UPS, 400 V

The IST7-60 is a 60 kVA / 60 kW three-phase online double-conversion UPS with a three-level inverter, in a 400 × 960 × 1193 mm cabinet of 153 kg. For data rooms, hospitals, telecom and industrial sites with 40 to 60 kW of critical load on a 400 V supply.

**60 kVA / 60 kW** Rating

**400 × 960 × 1193 mm** W × D × H

**153 kg** Weight

**±192 V** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=80) [Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST7-60%20(IST7%2060%E2%80%93200)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist7-60/v66/)

Quick answers

## IST7-60: quick answers

**What it is**: The IST7-60 is a 60 kVA / 60 kW three-phase online double-conversion UPS with a three-level inverter, in a 400 × 960 × 1193 mm cabinet of 153 kg.

**Who it is for**: For data rooms, hospitals, telecom and industrial sites with 40 to 60 kW of critical load on a 400 V supply.

**Supply and configuration**: 3 phases + N + PE · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L

**Battery and backup**: ±192 V

**Size and weight**: 400 × 960 × 1193 mm · 153 kg

**Ordering code**: IST7-60

IST7 60–200

## What sets apart the IST7-60

The IST7-60 is the entry point of the 60–200 kVA range and the lightest unit, 153 kg on a 0.38 m² footprint. It is the only model of the range that the catalogue pairs with the slim BB5 cabinet (30–38 × 12 V 40 Ah); the others start at BB6. Its default battery is ±192 V, 32 blocks of 12 V, and the string can be set from 28 to 48 blocks.

It has no capacity upgrade: for a load that will grow, the IST7-80 has the IST7-100's hardware and can be raised to 100 or 120 kVA from the display. On battery the IST7-60 draws 163 A nominal and 186 A maximum, on 35 mm² cables (PE 16 mm²).

- **Against the IST7-80** (one size up): Rated power 60 kVA / 60 kW against 80 kVA / 80 kW; Weight 153 kg against 163 kg.

Planning data

## IST7-60: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-60.

### Front, rear and footprint

**IST7-60 · Front, rear and footprint**

| Model | W × D × H (mm) | Weight |
| --- | --- | --- |
| IST7-60 | 400 × 960 × 1193 | 153 kg |

### BB5 to BB8, matched to every IST7

**IST7-60 · BB5 to BB8, matched to every IST7**

| UPS | IST7-60 |
| --- | --- |
| BB5 | 30–38 × 40 Ah |
| BB6 | 30–36 × 60 Ah |
| BB7 | 30–36 × 80 / 100 Ah |
| BB8 | 60 / 64 × 80 / 100 Ah |
| 2 × BB8 | 120 / 128 × 80 / 100 Ah |

### Battery connection by UPS model

**IST7-60 · Battery connection by UPS model**

| UPS | IST7-60 |
| --- | --- |
| I nom. (A) | 163 |
| I max. (A) | 186 |
| +/N/− mm² | 35 |
| PE mm² | 16 |

Installation

## Installing the IST7-60: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST7-60 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | front 800 mm, rear 800 mm, left 800 mm, right 800 mm, top 800 mm | AEC IST7 60–200 user manual p.35 §3.2.3 |
| Cable entry | Bottom, through the base | AEC IST7 60–200 user manual |
| Heat at full load | 2.18 kW at 60 kW load, 96.5 % efficiency | AEC IST7 60–200 user manual p.87 §A; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C, best 20–30 °C | AEC IST7 60–200 user manual p.34–35 §3.2.2 |
| Switches and terminals | Mains, bypass, output and maintenance bypass switches behind the lockable front door; terminals behind the front and rear wiring covers. | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |
| Door | One leaf, hinged on the right | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |

Size and floor

## How big it is

400 × 960 × 1193 mm · 153 kg.

**0.38 m²** footprint

**398 kg/m²** floor load

**1.19 m** height

Floor load = weight ÷ footprint (153 kg).

Efficiency

## How efficient is the AEC IST7-60 at your load?

IST7-60, 60 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.64 kW (η 95.9%) · 50%: 1.09 kW (η 96.5%) · 75%: 1.78 kW (η 96.2%) · 100%: 2.57 kW (η 95.9%). At 50% load, 24/7, it loses about 9,532 kWh a year.

**96.5** % 50% · Typical curve, derived from the datasheet efficiency of 96.5% (AEC method)

How the curve is drawn and where each figure comes from: [the IST7 60–200 range page](https://www.aecups.com/en/products/ist7-60-200/#efficiency).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Online, double conversion | 25%: 95.9% · 50%: 96.5% · 75%: 96.2% · 100%: 95.9% | Typical curve, derived from the datasheet efficiency of 96.5% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Online, double conversion up to 96.5% · ECO up to 99%.

Drag to turn

In 3D

## Look around the IST7-60

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist7-60/v66/)

The turntable shows the IST7-120; the full 3D view opens on the IST7-60.

Technical data

## Technical data IST7-60

Only this model's values, from the EMEA 2026 catalogue table.

**IST7-60 · Technical data**

|  |  |
| --- | --- |
| General |  |
| Rated power (kVA / kW) | 60 |
| Input |  |
| Connection | 3 phases + N + PE |
| Rated voltage | 220 / 230 / 240 V phase (380 / 400 / 415 V line) |
| Voltage range | 187–280 V phase at full power · 80–186 V with linear derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |
| Bypass synchronisation range | 50 / 60 Hz ± 6 Hz |
| Battery |  |
| Nominal DC voltage (default) | ±192 V |
| String length | 28–48 × 12 V blocks, set on site · VRLA or lithium (BMS card) |
| Max. charge current | 30 A |
| Output |  |
| Voltage · frequency | 220 / 230 / 240 V phase · 50 / 60 Hz (± 0.1 Hz on battery) |
| Power factor · THDv | 1 (settable 0.9) · ≤ 1% linear, ≤ 4% non-linear load |
| Transient · unbalance · phase error | ≤ 5% for 0–100–0% step · 100% unbalanced load · ≤ 1° |
| Transfer time inverter ↔ bypass | < 1 ms synchronised · < 15 ms not synchronised |
| Inverter overload | ≤ 105% continuous · ≤ 110% 60 min · ≤ 125% 10 min · ≤ 150% 1 min (IST7-120: > 125% immediate) |
| Bypass overload | ≤ 130% continuous · ≤ 150% 5 min · ≤ 200% 1 s · ≤ 300% 100 ms |
| System |  |
| Efficiency AC/AC | up to 96.5% double conversion · 99% ECO mode |
| Parallel | Up to 8 units, capacity or N+X · BSC dual-bus synchronisation |
| Communication | RS485 · Modbus RTU · RS232 · 4 IN / 3 OUT dry contacts · EPO · SNMP slot · expansion slot |
| Display | Colour touch screen, 5 status LEDs, ambient light bar, 10,000 events and 10,000 user-log entries |
| Environment | −5 … 40 °C · 0–95% RH · IP20 · < 65 dB at 1 m · forced-air cooling |
| Cable entry | bottom (all models) |
| EMC | [IEC 62040-2](https://webstore.iec.ch/en/publication/33696):2016 · category C3 (not for residential use without additional measures) |
| Dimensions W × D × H | 400 × 960 × 1193 mm |
| Weight | 153 kg |

**IST7-60 · Models**

| Item | IST7-60 |
| --- | --- |
| Rated power (kVA / kW) | 60 |
| Capacity upgrade | — |
| Power units | 1 |
| Nominal DC voltage (default) | ±192 V |
| Max. charge current | 30 A |
| W × D × H (mm) | 400 × 960 × 1193 |
| Weight | 153 kg |

Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST7-60

**Ordering codes IST7-60**

| Code | Description |
| --- | --- |
| IST7-60 | 60 kVA / 60 kW |
| PAR-IST7-60/200 | Parallel kit |
| IST7-\[kVA\]-\[n\]X\[Ah\] | UPS with battery cabinet, n × 12 V \[Ah\] (e.g. IST7-160-64X100 = IST7-160 + BB8 with 64 × 12 V 100 Ah) |

Questions

## Questions about the IST7-60

#### Which battery cabinets suit the IST7-60?

BB5 with 30–38 × 40 Ah, BB6 with 30–36 × 60 Ah, BB7 with 30–36 × 80 / 100 Ah, BB8 with 60 / 64 × 80 / 100 Ah and two BB8 with 120 / 128 × 80 / 100 Ah. Lithium cabinets are available on request.

#### How much space does the IST7-60 need?

The cabinet is 400 mm wide and 960 mm deep, with at least 800 mm free at the front, rear and above: air enters at the front and leaves at the rear. Cables come in from below; the unit is positioned on castors and then anchored to the floor.

#### How long does a 60 kVA UPS like the IST7-60 run?

2 to 98 minutes at full load (60 kW), and 8 to 239 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 30 × 12 V 40 Ah (IST7-60-30X40): 2 minutes at 100% and 8 at 50%. For other loads and batteries use the backup-time tool.

#### How big is the AEC IST7-60 and how much does it weigh?

The AEC IST7-60 measures 400 × 960 × 1193 mm; weight: 153 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

#### What is the ordering code of the AEC IST7-60?

In the EMEA 2026 catalogue the AEC IST7-60 is listed as IST7-60; AEC gives the full code, batteries included, from the load and the backup time.

Related models

## The same range: IST7 60–200

[The whole range](https://www.aecups.com/en/products/ist7-60-200/)

**IST7-60** 60 kVA [**IST7-80** 80 kVA · larger rating](https://www.aecups.com/en/products/ist7-60-200/ist7-80k/) [**IST7-100** 100 kVA](https://www.aecups.com/en/products/ist7-60-200/ist7-100k/) [**IST7-120** 120 kVA](https://www.aecups.com/en/products/ist7-60-200/ist7-120k/) [**IST7-160** 160 kVA](https://www.aecups.com/en/products/ist7-60-200/ist7-160k/) [**IST7-200** 200 kVA](https://www.aecups.com/en/products/ist7-60-200/ist7-200k/)

Batteries and cabinets: [BB5](https://www.aecups.com/en/products/battery-cabinets/bb5/) [BB6](https://www.aecups.com/en/products/battery-cabinets/bb6/) [BB7](https://www.aecups.com/en/products/battery-cabinets/bb7/) [BB8](https://www.aecups.com/en/products/battery-cabinets/bb8/) [OZ Power 12 V 40 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-40ah/) [OZ Power 12 V 60 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-60ah/) [L6 Lithium](https://www.aecups.com/en/products/l6-lithium/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/)

Shared by the whole range, on the IST7 60–200 page: [the display simulator](https://www.aecups.com/en/products/ist7-60-200/#display) · [how the power flows in each mode](https://www.aecups.com/en/products/ist7-60-200/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist7-60-200/#gallery).

Read next: [UPS installation clearances: what to check on site](https://www.aecups.com/en/blog/ups-installation-clearances/) [UPS heat output: BTU, cooling and room temperature](https://www.aecups.com/en/blog/ups-heat-output-cooling/) [L6 lithium battery sizing: modules, cabinets, room](https://www.aecups.com/en/blog/l6-lithium-battery-sizing/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST7-60: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST7-60%20(IST7%2060%E2%80%93200)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)