---
title: "Three-phase transformer UPS 120 kVA · IST7T-120 | AEC"
url: https://www.aecups.com/en/products/ist7-t/ist7t-120k/
description: "The IST7T-120 is a 120 kVA / 108 kW three-phase online UPS with built-in output isolation transformer, 1000 mm wide and 780 kg."
language: en
---

IST7-T · Three-phase UPS

# IST7T-120 Three-phase transformer UPS 120 kVA

VRLA 120 kVA online UPS with isolation transformer

The IST7T-120 is a 120 kVA / 108 kW three-phase online UPS with built-in output isolation transformer, 1000 mm wide and 780 kg. For industrial sites and medical buildings of 90 to 108 kW, alone, in parallel or in dual-bus systems.

**120 kVA / 108 kW** Rating

**1000 × 800 × 2000 mm** W × D × H

**780 kg** Weight

**348–480 V DC** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=94) [Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST7T-120%20(IST7-T)%3A%20%0AQuantity%3A%20#form)

Quick answers

## IST7T-120: quick answers

**What it is**: The IST7T-120 is a 120 kVA / 108 kW three-phase online UPS with built-in output isolation transformer, 1000 mm wide and 780 kg.

**Who it is for**: For industrial sites and medical buildings of 90 to 108 kW, alone, in parallel or in dual-bus systems.

**Supply and configuration**: 3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz · 380 / 400 / 415 V L-L · 220 / 230 / 240 V L-N

**Battery and backup**: 348–480 V DC

**Size and weight**: 1000 × 800 × 2000 mm · 780 kg

**Ordering code**: IST7T-120

IST7-T

## What sets apart the IST7T-120

The IST7T-120 adds 20 kVA to the 100 kVA in the same 1000 × 800 × 2000 mm cabinet for 60 kg more (780 kg). It draws 216 A AC and 333 A from the battery, within the 2 × 150 mm² cable maximums of the cabinet.

For loads with two power inputs, two systems A and B (single units or parallel systems, two or four UPS) can be phase- and frequency-synchronised through the optional LBS interface, and a common battery pack can serve a parallel system.

- **Against the IST7T-100** (one size down): Rated power 120 kVA / 108 kW against 100 kVA / 90 kW; AC input / output current 216 A against 180 A; Battery current 333 A against 278 A; Weight 780 kg against 720 kg.
- **Against the IST7T-200** (one size up): Rated power 120 kVA / 108 kW against 200 kVA / 180 kW; AC input / output current 216 A against 355 A; Battery current 333 A against 499 A; Weight 780 kg against 1280 kg.

Planning data

## IST7T-120: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7T-120.

### One cabinet, 1000 × 800 × 2000 mm

**IST7T-120 · One cabinet, 1000 × 800 × 2000 mm**

| kVA | 120 |
| --- | --- |
| AC in/out (A) | 216 |
| mm² max | 2 × 150 |
| Battery (A) | 333 |
| mm² max | 2 × 150 |

Size and floor

## How big it is

1000 × 800 × 2000 mm · 780 kg.

**0.8 m²** footprint

**975 kg/m²** floor load

**2 m** height

Floor load = weight ÷ footprint (780 kg).

Efficiency

## AEC IST7T-120 efficiency

The IST7-T pages of the EMEA 2026 catalogue give no efficiency figure.

Technical data

## Technical data IST7T-120

Only this model's values, from the EMEA 2026 catalogue table.

**IST7T-120 · Technical data**

|  |  |
| --- | --- |
| General |  |
| Rated power (kVA / kW) | 120 / 108 |
| Rectifier input |  |
| Technology | current-type IGBT rectifier, three-phase PFC · input EMI filter and input contactor |
| Rated voltage · range | 380 / 400 / 415 V L-L · ± 25% (full load from −20% to +25%; −25 … −20% current-limited) |
| Connection · frequency | 3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz |
| Power factor · THDi | ≥ 0.99 · < 5% |
| AC input / output current (A) | 216 |
| Bypass input |  |
| Rated voltage · connection | 380 / 400 / 415 V L-L · 3Φ4W + PE · separate bypass input as standard (jumper for single input) |
| Synchronisation range | 50 Hz ± 10% (± 5% optional) |
| Static bypass | SCR static switch · manual maintenance bypass built in |
| Battery |  |
| Battery converter | bidirectional buck / boost DC/DC on the DC bus · VRLA or lithium |
| Battery voltage (V DC) | 348–480 |
| Number of 12 V batteries | 29–40 (default 32) |
| Battery current (A) | 333 |
| Battery management | patented smart charging · equalise / float · temperature compensation · hibernation · standard, depth and constant-current tests · cell data with BMS |
| Energy functions | backfeed to grid during the battery test · energy-storage UPS with lithium (plan curve, 8 periods, or EMS over Modbus) |
| Output |  |
| Voltage · power factor | 220 / 230 / 240 V L-N (380 / 400 / 415 V L-L) · 0.9 (kW / kVA) |
| Waveform · frequency | sine wave, THDv < 1% (linear load) · tracks the bypass in normal mode · 50 Hz ± 0.2% in battery mode |
| Isolation | Δ/Y output transformer built in, between inverter and inverter static switch |
| Transfer time | 0 ms mains → battery · 1 ms inverter → bypass |
| Overload (inverter mode) | 101–105% alarm, continuous · 106–130% 10 min · 131–155% 1 min · > 155% 1 s, then bypass |
| Unbalanced · non-linear load | 100% three-phase unbalanced · full kVA at 100% non-linear load |
| Operating modes | normal · battery · bypass · ECO (inverter in cold standby) · maintenance bypass · self-load test |
| Output connection | copper busbar |
| System |  |
| Control · display | fully digital DSP · touch screen, power-on password, user and administrator levels · 10,000 events, user log |
| Communication | RS232 / RS485 Modbus RTU · 8 output and 4 input dry contacts (24 V DC / 1 A) · SNMP card, serial server TCP/IP optional |
| Parallel · systems | master-slave adaptive digital parallel, N+x warning, online exit and add · series hot standby · dual bus with LBS (optional) |
| Protections | battery undervoltage, overload, short circuit, over-temperature, input over- and undervoltage |
| Standards | CE · EN / [IEC 62040-1](https://webstore.iec.ch/en/publication/80573) (safety) · EN / [IEC 62040-2](https://webstore.iec.ch/en/publication/33696) (EMC), category C3 |
| Environment and mechanics |  |
| Temperature · humidity | −5 … 40 °C operating · −20 … 55 °C storage · 0–95% RH non-condensing |
| Altitude without derating · noise | 1500 m · < 70 dB |
| Protection degree | IP20 (IP21 with optional top cover) |
| Dimensions (W × D × H) | 1000 × 800 × 2000 mm |
| Weight (kg ± 5%) | 780 |

**IST7T-120 · Models**

| Item | IST7T-120 |
| --- | --- |
| kVA / kW | 120 / 108 |
| W × D × H (mm) | 1000 × 800 × 2000 |
| kg ± 5% | 780 |

Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST7T-120

**Ordering codes IST7T-120**

| Code | Description |
| --- | --- |
| IST7T-100 · -120 · -200 | IST7-T online UPS with output isolation transformer, 100 / 120 / 200 kVA, 1000 mm cabinet, external battery |

Questions

## Questions about the IST7T-120

#### Can two IST7T-120 feed a dual-bus system?

Yes. With the optional LBS interface two independent systems A and B are kept in phase and frequency, so dual-corded loads can be fed from both. Each side can be a single unit or a parallel system.

#### What currents does the IST7T-120 draw?

216 A on the AC input and output and 333 A on the battery, with cables up to 2 × 150 mm² in the catalogue table. A bipolar disconnect switch is required on the external DC circuit.

#### How big is the AEC IST7T-120 and how much does it weigh?

The AEC IST7T-120 measures 1000 × 800 × 2000 mm; weight: 780 kg (EMEA 2026 catalogue).

Related models

## The same range: IST7-T

[The whole range](https://www.aecups.com/en/products/ist7-t/)

[**IST7T-100** 100 kVA · smaller rating](https://www.aecups.com/en/products/ist7-t/ist7t-100k/) **IST7T-120** 120 kVA [**IST7T-200** 200 kVA · larger rating](https://www.aecups.com/en/products/ist7-t/ist7t-200k/)

Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/)

Shared by the whole range, on the IST7-T page: [how the power flows in each mode](https://www.aecups.com/en/products/ist7-t/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist7-t/#gallery).

Read next: [Isolation transformer UPS: when you need one](https://www.aecups.com/en/blog/isolation-transformer-ups/) [UPS for hospitals and healthcare facilities](https://www.aecups.com/en/blog/ups-for-hospitals/) [Industrial UPS: protecting PLCs, motors and processes](https://www.aecups.com/en/blog/ups-for-industry/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST7T-120: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST7T-120%20(IST7-T)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)
