VRLA 15 kVA online rack UPS, 3U, 3/3 · 3/1 · 1/1

The IST9 15 kVA is a 15 kVA / 15 kW online double-conversion UPS in the 3U chassis of the 10 and 20 kVA, 18.4 kg, for 3/3, 3/1 or 1/1. For loads of 10 to 15 kW in a 19-inch rack: the step between the 10 and the 20 kVA, with more headroom than the first and a lighter battery than the second.

**15 kVA / 15 kW** Rating

**438 × 535 × 130 mm (3U)** W × D × H

**18.4 kg** Weight

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=57) [Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST9%2015%20kVA%20(IST9)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist9-15/v47/)

Quick answers

## IST9 15 kVA: quick answers

**What it is**: The IST9 15 kVA is a 15 kVA / 15 kW online double-conversion UPS in the 3U chassis of the 10 and 20 kVA, 18.4 kg, for 3/3, 3/1 or 1/1.

**Who it is for**: For loads of 10 to 15 kW in a 19-inch rack: the step between the 10 and the 20 kVA, with more headroom than the first and a lighter battery than the second.

**Supply and configuration**: 3W + N + PE (settable 1W + N + PE) · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L

**Size and weight**: 438 × 535 × 130 mm (3U) · 18.4 kg

**Ordering code**: IST9-15-\[n\]X9

IST9

## What sets apart the IST9 15 kVA

Same body, same electronics family as the 10 and 20 kVA: the touch screen that turns with the unit, the connector jumpers for 3/3, 3/1 or 1/1, the 1–10 A charger and the ±96 to ±240 V DC battery string. AEC orders it as IST9-15 with the power distribution box and maintenance breaker, or IST9-15-\[n\]X9 with 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (32 to 160 × 12 V 9 Ah).

Backup at full load in AEC's product data: 3 minutes with 32 batteries, 9 with 64, 17 with 96, 26 with 128 and 34 with 160 (12 V 9 Ah, new batteries, 25 °C); at half load 9, 26, 45, 58 and 86 minutes.

- **Against the IST9 10 kVA** (one size down): Rated power 15 kVA / 15 kW against 10 kVA / 10 kW; Rated power (kVA / kW, low-voltage mode) not published against 10 kVA / 10 kW.
- **Against the IST9 20 kVA** (one size up): Rated power 15 kVA / 15 kW against 20 kVA / 20 kW; Rated power (kVA / kW, low-voltage mode) not published against 10 kVA / 10 kW.

Installation

## Installing the IST9 15 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST9 15 kVA · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Cable entry | At the rear | EMEA 2026 catalogue p.64 |
| Heat at full load | 0.63 kW at 15 kW load, 96 % efficiency | EMEA 2026 catalogue p.64; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C | EMEA 2026 catalogue p.64 |

Size and floor

## How big it is

438 × 535 × 130 mm · 18.4 kg.

**0.23 m²** footprint

**79 kg/m²** floor load

**0.13 m** height

Floor load = weight ÷ footprint (18.4 kg).

Drag to turn

In 3D

## Look around the IST9 15 kVA

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist9-15/v47/)

The turntable shows the IST9 20 kVA; the full 3D view opens on the IST9 15 kVA.

Technical data

## Technical data IST9 15 kVA

Only this model's values, from the EMEA 2026 catalogue table.

**IST9 15 kVA · Technical data**

|  |  |
| --- | --- |
| General |  |
| Rated power (kVA / kW, high-voltage mode) | 15 / 15 |
| Rated power (kVA / kW, low-voltage mode) | not published |
| Configuration | 3/3 · 3/1 · 1/1 |
| Input |  |
| Connection | 3W + N + PE (settable 1W + N + PE) |
| Voltage range (phase) | high-voltage mode 176–280 V full load, 80–176 V linear derating · low-voltage mode 90–155 V full load, 70–90 V derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load |
| Bypass | 50 / 60 Hz ± 10% · voltage ± 20% |
| Battery |  |
| Voltage | high-voltage mode ± 96 … ± 240 V DC (± 48 … ± 120 cells of 2 V, default ± 96) · low-voltage mode ± 96 … ± 120 V (± 48 … ± 60 cells, default ± 60) |
| Charging current | 1–10 A (default 4 A) |
| Output |  |
| Voltage | 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (low-voltage mode 110 / 115 / 120 V); 3W + N + PE, settable 1W + N + PE |
| Frequency | tracks the bypass; 50 ± 0.1 or 60 ± 0.1 Hz in battery mode |
| Waveform · distortion · power factor | sine wave · ≤ 2% resistive full load · 1.0 |
| Transfer inverter ↔ bypass | < 1 ms synchronised · < 10 ms not synchronised |
| Inverter overload | ≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms · > 200% immediate |
| Bypass overload | < 130% continuous · 130–155% 1 min · > 155% 200 ms |
| System |  |
| Efficiency | up to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO |
| Display · cold start | touch screen · battery cold start fitted |
| Communication | RS232 · options: SNMP, RS485 + dry contact, protocol card for the approved lithium system, parallel card |
| Noise (20–25 °C) | ≤ 50 dB half load · ≤ 55 dB 75% and full load |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 2000 m |
| Dimensions (W × D × H) | 438 × 535 × 130 mm (3U) |
| Weight | 18.4 kg |

**IST9 15 kVA · Models**

| Item | IST9 15 kVA |
| --- | --- |
| kVA / kW (high-voltage mode) | 15 / 15 |
| kVA / kW (low-voltage mode) | not published |
| Configuration | 3/3 · 3/1 · 1/1 |
| W × D × H (mm) | 438 × 535 × 130 |
| Weight | 18.4 kg |

— not stated in the user manual. Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST9 15 kVA

**Ordering codes IST9 15 kVA**

| Code | Description |
| --- | --- |
| IST9-10-\[n\]X9 · IST9-15-\[n\]X9 | IST9 10 or 15 kVA in the same way: power distribution box, maintenance breaker and 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (AEC EMEA product data) |
| PAR-IST9 | Parallel board |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| BBJ2 | Rack battery cabinet, max. 16 × 12 V 9 Ah, 3U |

Questions

## Questions about the IST9 15 kVA

#### Is the IST9 15 kVA bigger than the 10 kVA?

No. The 10, 15 and 20 kVA share one chassis: 438 × 535 × 130 mm (3U) and 18.4 kg. Only the 30 and 40 kVA are deeper (720 mm).

#### How long does the IST9 15 kVA run on battery?

At 15 kW: 3 to 34 minutes with 2 to 10 BBJ2 cabinets (32 to 160 × 12 V 9 Ah). At 7.5 kW: 9 to 86 minutes. AEC sizes every system for the real load.

#### How big is the AEC IST9 15 kVA and how much does it weigh?

The AEC IST9 15 kVA measures 438 × 535 × 130 mm (3U); weight: 18.4 kg (EMEA 2026 catalogue).

Related models

## The same range: IST9

[The whole range](https://www.aecups.com/en/products/ist9/)

[**IST9 10 kVA** 10 kVA · smaller rating](https://www.aecups.com/en/products/ist9/ist9-10k/) **IST9 15 kVA** 15 kVA [**IST9 20 kVA** 20 kVA · larger rating](https://www.aecups.com/en/products/ist9/ist9-20k/) [**IST9 30 kVA** 30 kVA](https://www.aecups.com/en/products/ist9/ist9-30k/) [**IST9 40 kVA** 40 kVA](https://www.aecups.com/en/products/ist9/ist9-40k/)

Batteries and cabinets: [BBJ2](https://www.aecups.com/en/products/battery-cabinets/bbj2/) [OZ Power 12 V 9 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-9ah/) Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/) [External maintenance bypass](https://www.aecups.com/en/products/maintenance-bypass/)

Shared by the whole range, on the IST9 page: [how the power flows in each mode](https://www.aecups.com/en/products/ist9/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist9/#gallery).

Read next: [Three-phase UPS: configurations, sizing and installation](https://www.aecups.com/en/blog/three-phase-ups/) [How to choose a UPS: type, runtime, phases and service](https://www.aecups.com/en/blog/how-to-choose-a-ups/) [Single- or three-phase UPS: which does your site need?](https://www.aecups.com/en/blog/single-vs-three-phase-ups/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST9 15 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.