title: "Three-phase rack UPS 40 kVA, 3U, 400 V · IST9 | AEC"
url: https://www.aecups.com/en/products/ist9/ist9-40k/
description: "The IST9 40 kVA is a 40 kVA / 40 kW online double-conversion UPS in 3U, the most powerful 19-inch AEC UPS, for 3/3 or 3/1."
language: en
---

IST9 · Three-phase UPS

# IST9 40 kVA Three-phase rack UPS 40 kVA, 3U, 400 V

VRLA 40 kVA online rack UPS, 3U, 3/3 · 3/1

The IST9 40 kVA is a 40 kVA / 40 kW online double-conversion UPS in 3U, the most powerful 19-inch AEC UPS, for 3/3 or 3/1. For data rooms and edge sites that need 40 kW in a rack, or N+1 systems of several IST9 in parallel.

**40 kVA / 40 kW** Rating

**438 × 720 × 130 mm (3U)** W × D × H

**34.2 kg** Weight

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=57) [Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST9%2040%20kVA%20(IST9)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ist9-40/v54/)

Quick answers

## IST9 40 kVA: quick answers

**What it is**: The IST9 40 kVA is a 40 kVA / 40 kW online double-conversion UPS in 3U, the most powerful 19-inch AEC UPS, for 3/3 or 3/1.

**Who it is for**: For data rooms and edge sites that need 40 kW in a rack, or N+1 systems of several IST9 in parallel.

**Supply and configuration**: 3W + N + PE · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L

**Size and weight**: 438 × 720 × 130 mm (3U) · 34.2 kg

**Ordering code**: IST9-40

IST9

## What sets apart the IST9 40 kVA

Forty kilowatts in 130 mm of height is what the IST9 40 kVA brings: 438 × 720 × 130 mm, 34.2 kg. It draws 75 A per phase in 3/3 and up to 111 A from the battery, so the catalogue recommends 100 A 3P AC breakers and a 200 A 3P DC breaker; in 3/1 the single-phase output reaches 182 A on a 250 A 1P breaker.

In low-voltage mode it delivers 20 kVA / 20 kW. With the optional parallel card, units join or leave the system online and share the current (N+1: total load up to N times one unit). The lithium protocol card connects the approved lithium battery system over RS485.

- **Against the IST9 30 kVA** (one size down): Rated power 40 kVA / 40 kW against 30 kVA / 30 kW; Weight 34.2 kg against 34.1 kg.

Planning data

## IST9 40 kVA: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST9 40 kVA.

### Connected, and ready for redundancy

**IST9 40 kVA · Connected, and ready for redundancy**

| Model | Mode | AC input (A) | Bypass input (A) | DC input (A) | AC output (A) |
| --- | --- | --- | --- | --- | --- |
| 40 kVA | 3/3 | 100 × 3P | 100 × 3P | 200 × 3P | 100 × 3P |
| 40 kVA | 3/1 | 100 × 3P | 250 × 1P | 200 × 3P | 250 × 1P |

### Currents, codes and options

**IST9 40 kVA · Currents, codes and options**

| Model | Mode | AC input (A) | Bypass input (A) | DC input (A) | AC output (A) |
| --- | --- | --- | --- | --- | --- |
| 40 kVA | 3/3 | 75 | 61 | 111 | 61 |
| 40 kVA | 3/1 | 75 | 182 | 111 | 182 |

Installation

## Installing the IST9 40 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

**IST9 40 kVA · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Cable entry | At the rear | EMEA 2026 catalogue p.64 |
| Heat at full load | 1.67 kW at 40 kW load, 96 % efficiency | EMEA 2026 catalogue p.64; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C | EMEA 2026 catalogue p.64 |

Size and floor

## How big it is

438 × 720 × 130 mm · 34.2 kg.

**0.32 m²** footprint

**108 kg/m²** floor load

**0.13 m** height

Floor load = weight ÷ footprint (34.2 kg).

Efficiency

## How efficient is the AEC IST9 40 kVA at your load?

IST9 40 kVA, 40 kW at its rating, double conversion, high-voltage mode (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.48 kW (η 95.4%) · 50%: 0.83 kW (η 96%) · 75%: 1.35 kW (η 95.7%) · 100%: 1.93 kW (η 95.4%). At 50% load, 24/7, it loses about 7,300 kWh a year.

**96** % 50% · Typical curve, derived from the datasheet efficiency of 96% (AEC method)

How the curve is drawn and where each figure comes from: [the IST9 range page](https://www.aecups.com/en/products/ist9/#efficiency).

**Load**: —

**Lost as heat**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at € per kWh**: —

The catalogue's examples use €0.20 per kWh.

#### Where each figure comes from

| Mode | Efficiency | Kind | Models | Source |
| --- | --- | --- | --- | --- |
| Double conversion, high-voltage mode | 25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4% | Typical curve, derived from the datasheet efficiency of 96% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| Double conversion, low-voltage mode | 25%: 93.4% · 50%: 94% · 75%: 93.7% · 100%: 93.4% | Typical curve, derived from the datasheet efficiency of 94% (AEC method) | IST9 40 kVA · IST9 10 kVA · IST9 20 kVA | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |  |

EMEA 2026 catalogue figures: Double conversion, high-voltage mode up to 96% · Double conversion, low-voltage mode up to 94% · ECO up to 99%.

Drag to turn

In 3D

## Look around the IST9 40 kVA

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ist9-40/v54/)

Technical data

## Technical data IST9 40 kVA

Only this model's values, from the EMEA 2026 catalogue table.

**IST9 40 kVA · Technical data**

|  |  |
| --- | --- |
| General |  |
| Rated power (kVA / kW, high-voltage mode) | 40 / 40 |
| Rated power (kVA / kW, low-voltage mode) | 20 / 20 |
| Configuration | 3/3 · 3/1 |
| Input |  |
| Connection | 3W + N + PE |
| Voltage range (phase) | high-voltage mode 176–280 V full load, 80–176 V linear derating · low-voltage mode 90–155 V full load, 70–90 V derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load |
| Bypass | 50 / 60 Hz ± 10% · voltage ± 20% |
| Battery |  |
| Voltage | high-voltage mode ± 96 … ± 240 V DC (± 48 … ± 120 cells of 2 V, default ± 96) · low-voltage mode ± 96 … ± 120 V (± 48 … ± 60 cells, default ± 60) |
| Full-load derating by cells | ± 48 … ± 90 cells: 100 × 0.0625 × N / 6 % |
| Charging current | 1–20 A (default 15 A) |
| Output |  |
| Voltage | 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (low-voltage mode 110 / 115 / 120 V); 3W + N + PE, settable 1W + N + PE |
| Frequency | tracks the bypass; 50 ± 0.1 or 60 ± 0.1 Hz in battery mode |
| Waveform · distortion · power factor | sine wave · ≤ 2% resistive full load · 1.0 |
| Transfer inverter ↔ bypass | < 1 ms synchronised · < 10 ms not synchronised |
| Inverter overload | ≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms · > 200% immediate |
| Bypass overload | < 130% continuous · 130–155% 1 min · > 155% 200 ms |
| System |  |
| Efficiency | up to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO |
| Display · cold start | touch screen · battery cold start fitted |
| Communication | RS232 · options: SNMP, RS485 + dry contact, protocol card for the approved lithium system, parallel card |
| Noise (20–25 °C) | ≤ 55 dB half load · ≤ 58 dB 75% · ≤ 60 dB full load |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 2000 m |
| Dimensions (W × D × H) | 438 × 720 × 130 mm (3U) |
| Weight | 34.2 kg |

**IST9 40 kVA · Models**

| Item | IST9 40 kVA |
| --- | --- |
| kVA / kW (high-voltage mode) | 40 / 40 |
| kVA / kW (low-voltage mode) | 20 / 20 |
| Configuration | 3/3 · 3/1 |
| W × D × H (mm) | 438 × 720 × 130 |
| Weight | 34.2 kg |

— not stated in the user manual. Specifications are subject to change without notice.

#### **More technical details** ordering codes

Ordering codes

## Ordering codes IST9 40 kVA

**Ordering codes IST9 40 kVA**

| Code | Description |
| --- | --- |
| IST9-10 · IST9-30 · IST9-40 | Code on request |
| PAR-IST9 | Parallel board |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| BBJ2 | Rack battery cabinet, max. 16 × 12 V 9 Ah, 3U |

Questions

## Questions about the IST9 40 kVA

#### Can several IST9 40 kVA work in parallel?

Yes, with the parallel kit PAR-IST9 (parallel card and 2 m cable, CAN communication). Units are started one by one, then joined; a faulty unit leaves the system with an alarm and can be serviced online.

#### Can the IST9 40 kVA use lithium batteries?

Yes: the battery type is set on the screen, lead-acid or the approved lithium battery system, which talks to the UPS through the optional lithium protocol card (RS485 on RJ45).

#### How big is the AEC IST9 40 kVA and how much does it weigh?

The AEC IST9 40 kVA measures 438 × 720 × 130 mm (3U); weight: 34.2 kg (EMEA 2026 catalogue).

Related models

## The same range: IST9

[The whole range](https://www.aecups.com/en/products/ist9/)

[**IST9 10 kVA** 10 kVA](https://www.aecups.com/en/products/ist9/ist9-10k/) [**IST9 15 kVA** 15 kVA](https://www.aecups.com/en/products/ist9/ist9-15k/) [**IST9 20 kVA** 20 kVA](https://www.aecups.com/en/products/ist9/ist9-20k/) [**IST9 30 kVA** 30 kVA · smaller rating](https://www.aecups.com/en/products/ist9/ist9-30k/) **IST9 40 kVA** 40 kVA

Accessories: [SNMP card](https://www.aecups.com/en/products/snmp-card/) [Dry contact card](https://www.aecups.com/en/products/dry-contact-card/) [External maintenance bypass](https://www.aecups.com/en/products/maintenance-bypass/)

Shared by the whole range, on the IST9 page: [how the power flows in each mode](https://www.aecups.com/en/products/ist9/#diagrams) · [the catalogue's photos and drawings](https://www.aecups.com/en/products/ist9/#gallery).

Read next: [Three-phase UPS: configurations, sizing and installation](https://www.aecups.com/en/blog/three-phase-ups/) [How to choose a UPS: type, runtime, phases and service](https://www.aecups.com/en/blog/how-to-choose-a-ups/) [Single- or three-phase UPS: which does your site need?](https://www.aecups.com/en/blog/single-vs-three-phase-ups/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST9 40 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Three-phase%20UPS&msg=About%20the%20AEC%20IST9%2040%20kVA%20(IST9)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)