title: "LiFePO4 lithium battery cabinet, 100 Ah modules · L6-100 | AEC"
url: https://www.aecups.com/en/products/l6-lithium/l6-100/
description: "The L6-100 is a lithium iron phosphate battery cabinet for up to twelve hot-swappable 100 Ah modules: 69 kWh and 60 kW of rated output."
language: en
---

L6 Lithium · Batteries and cabinets

# L6-100 LiFePO4 lithium battery cabinet, 100 Ah modules

Lithium 100 Ah LFP lithium battery cabinet

The L6-100 is a lithium iron phosphate battery cabinet for up to twelve hot-swappable 100 Ah modules: 69 kWh and 60 kW of rated output, for backup of one to four hours. For telecom, security, public buildings and smaller UPS (up to 40 kW) that need hours, not minutes, of backup.

**60 kW per cabinet** Rating

**600 × 850 × 2000 mm** W × D × H

**810 ± 24 kg with 12 modules** Weight

**69 kWh · 12 × 100 Ah** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=165) [Contact us](https://www.aecups.com/en/contacts/?interest=Lithium%20batteries&msg=About%20the%20AEC%20L6-100%20(L6%20Lithium)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/eu-l6/v55/#l6-12x100)

Quick answers

## L6-100: quick answers

**What it is**: The L6-100 is a lithium iron phosphate battery cabinet for up to twelve hot-swappable 100 Ah modules: 69 kWh and 60 kW of rated output, for backup of one to four hours.

**Who it is for**: For telecom, security, public buildings and smaller UPS (up to 40 kW) that need hours, not minutes, of backup.

**Supply and configuration**: 240 / ±240 / 480 V DC

**Battery and backup**: 69 kWh · 12 × 100 Ah · 1 / 2 / 4 h

**Size and weight**: 600 × 850 × 2000 mm · 810 ± 24 kg with 12 modules

**Ordering code**: L6-100 cabinet, master or slave · code on request

L6 Lithium

## What sets apart the L6-100

The 100 Ah module uses 1C cells in a wider 440 mm drawer: 57.6 V, 5.76 kWh, 52 ± 1 kg, with a 5 kW DC/DC output. Twelve of them fill the cabinet in one column for 69 kWh, close to an hour (57 minutes) at the 60 kW rating. The full cabinet weighs 810 ± 24 kg, less than the 40 / 50 Ah versions, and has one battery breaker.

The L6 long-backup sizing starts small: a 6 kW UPS needs two modules for 1 hour (never fewer than carry its power), three for 2 hours and six for 4 hours; a 20 kW UPS needs five, nine or seventeen (two cabinets). At 40 kW: nine modules for 1 hour, two cabinets (17) for 2 hours, three cabinets (34) for 4 hours.

- **Against the L6-50** (one size down): Nominal capacity 69 kWh against 58 kWh; Max. modules per cabinet 12 against 20; Rated output power (discharge) 60 kW against 200 kW; Capacity · cell discharge rate 100 Ah · 1C against 50 Ah · 4C; Rated voltage · energy 57.6 V · 5.76 kWh against 57.6 V · 2.88 kWh.

Planning data

## L6-100: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the L6-100.

### One footprint, two module sizes

**L6-100 · One footprint, two module sizes**

| Module | Energy per cabinet | Rated power per cabinet |
| --- | --- | --- |
| 100 Ah | 69 kWh | 60 kW |

### Long backup, in a wider drawer

**L6-100 · Long backup, in a wider drawer**

| Item | 100 Ah · 1C |
| --- | --- |
| Cells | LFP, 3.2 V · 18 in series · 1C |
| Module voltage · energy | 57.6 V · 5.76 kWh |
| DC/DC output | 240 / ±240 / 480 V · 5 kW |
| Current unbalance | ≤ 3% |
| Full cabinet, 12 modules | 69 kWh · 57 min at rated power |
| Size (W × D × H) | 440 × 665 × 132 mm |
| Weight · noise | 52 ± 1 kg · 58 dB |

Installation

## Installing the L6-100: space, cables

Each figure with its source.

**L6-100 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | front 800 mm, rear 800 mm, left 0 mm, right 0 mm, top 500 mm | L6 user manual App. A; EMEA 2026 catalogue p.177–178; EMEA 2026 catalogue p.177 |
| Cable entry | DC cables from the top | EMEA 2026 catalogue p.177 |
| Operating temperature | 0 to 40 °C, best 20–30 °C | L6 user manual App. A; EMEA 2026 catalogue p.177 |
| Switches and terminals | Battery breakers behind the front door; 10" touch screen on the master's door. | EMEA 2026 catalogue p.177 |
| Door | One leaf, hinged on the right | EMEA 2026 catalogue p.177 |
| Module withdrawal | 665 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.177–178 |

Size and floor

## How big it is

600 × 850 × 2000 mm · 810 ± 24 kg with 12 modules.

**0.51 m²** footprint

**1,588 kg/m²** floor load

**2 m** height

Floor load = weight ÷ footprint (810 kg).

Backup time

## The backup-time tool reads the catalogue's tables for lithium modules, L6 cabinets and VRLA strings.

[Backup time · L6-100](https://www.aecups.com/en/tools/backup-time/?bat=l6&kw=100)

Drag to turn

In 3D

## Look around the L6-100

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/eu-l6/v55/#l6-12x100)

Technical data

## Technical data L6-100

Only this model's values, from the EMEA 2026 catalogue table.

**L6-100 · Technical data**

|  |  |
| --- | --- |
| Cabinet |  |
| Nominal capacity | 69 kWh |
| Max. modules per cabinet | 12 |
| Rated output power (discharge) | 60 kW |
| Rated output voltage (discharge) | 240 / ±240 / 480 V DC (three output systems) |
| Rated input voltage (charge) | 265 / ±265 / 530 V DC |
| Cell charge current | max. 40 A, default 20 A |
| Discharge overload | 125–135%: 1 min · 135–150%: 30 s · > 150%: 500 ms |
| Current unbalance (module / cabinet) | ≤ 3% |
| Max. cabinets in parallel | 15 |
| SOC · SOH | module SOC accuracy ≥ 95% · SOH estimate accuracy ≥ 90% |
| Functions | discharge SOC balance, battery cold start, self-start after power recovery, EPO, module-level fire control, cell insulation detection |
| Protection | over-temperature, over-current, short circuit, battery over- and under-voltage, low SOC |
| Module |  |
| Capacity · cell discharge rate | 100 Ah · 1C |
| Rated voltage · energy | 57.6 V · 5.76 kWh |
| Cell cycle life | 5,000 cycles at 50% depth of discharge |
| DC/DC output per module | 5 kW |
| Size (W × D × H) | 440 × 665 × 132 mm |
| Weight | 52 ± 1 kg |
| General |  |
| Communication | TCP/IP, RS485 (CAN reserved) |
| Display | 10-inch touch screen (master cabinet) · indicators (slave cabinet) |
| Operating · storage temperature | 0 … +40 °C · −10 … +45 °C |
| Humidity · altitude | 5–95% non-condensing · < 4000 m, derating above 2000 m ([IEC 62040-3](https://webstore.iec.ch/en/publication/60140)) |
| Noise · protection | < 65 dB · IP20 · battery-side overvoltage level 2 |
| Cabinet size (W × D × H) | 600 × 850 × 2000 mm |
| Weight with full modules | 810 ± 24 kg |

**L6-100 · Models**

| Item | L6-100 |
| --- | --- |
| Module capacity | 100 Ah |
| Cell discharge rate | 1C |
| Modules per cabinet | 12 |
| Energy per cabinet | 69 kWh |
| Rated power per cabinet | 60 kW |
| Typical backup | 1 / 2 / 4 h |

Cabinet energy and other cabinet and system data from the L6 user manual; module voltage, energy and DC/DC power from AEC lithium documentation. Specifications are subject to change without notice.

#### **More technical details** range tables, ordering codes

Planning data

## L6 Lithium range tables

### 1, 2 and 4 hours

Cabinets and modules for each UPS power (cabinets · modules), from the L6 sizing table (2026): new modules, 95% battery and inverter efficiency, the 10% reserve included, never fewer modules than carry the UPS rating.

**L6-100 · 1, 2 and 4 hours**

| UPS kW | 1 h | 2 h | 4 h |
| --- | --- | --- | --- |
| ≤ 6 | 1 · 2 | 1 · 3 | 1 · 6 |
| ≤ 10 | 1 · 3 | 1 · 5 | 1 · 9 |
| ≤ 15 | 1 · 4 | 1 · 7 | 2 · 13 |
| ≤ 20 | 1 · 5 | 1 · 9 | 2 · 17 |
| ≤ 40 | 1 · 9 | 2 · 17 | 3 · 34 |

Ordering codes

## Ordering codes L6-100

**Ordering codes L6-100**

| Code | Description |
| --- | --- |
| L6-100 cabinet | Cabinet for up to 12 × 100 Ah modules, master or slave. Code on request. |
| Modules | 40 Ah · 50 Ah · 100 Ah lithium modules, hot-swappable. Code on request. |
| L6-C-2000 · L6-C-4000 | Combiner cabinet: L6-C-2000 (up to 4 cabinets) · L6-C-4000 (up to 8 cabinets). Code on request. |
| Accessories | Networking device · blank panels · in-row rear frame. Code on request. |

Questions

## Questions about the L6-100

#### How many L6-100 modules for 2 hours at 10 kW?

Five modules in one cabinet, from the L6 sizing table (10 kW: 3 modules for 1 h, 5 for 2 h, 9 for 4 h, the 10% reserve included). AEC sizes every project.

#### Why is the L6-100 cabinet rated only 60 kW?

Each 100 Ah module delivers 5 kW through its DC/DC converter and the cabinet holds twelve: 60 kW. The 40 / 50 Ah modules deliver 10 kW each, twenty per cabinet, for 200 kW, but store less energy per module.

#### How big is the AEC L6-100 and how much does it weigh?

The AEC L6-100 measures 600 × 850 × 2000 mm; weight: 810 ± 24 kg with 12 modules (EMEA 2026 catalogue).

Related models

## The same range: L6 Lithium

[The whole range](https://www.aecups.com/en/products/l6-lithium/)

[**L6-40** 40 Ah](https://www.aecups.com/en/products/l6-lithium/l6-40/) [**L6-50** 50 Ah · smaller rating](https://www.aecups.com/en/products/l6-lithium/l6-50/) **L6-100** 100 Ah

Shared by the whole range, on the L6 Lithium page: [the catalogue's photos and drawings](https://www.aecups.com/en/products/l6-lithium/#gallery).

Read next: [L6 lithium battery sizing: modules, cabinets, room](https://www.aecups.com/en/blog/l6-lithium-battery-sizing/) [UPS backup time: how to estimate and extend runtime](https://www.aecups.com/en/blog/ups-backup-time/) [UPS batteries: VRLA vs lithium and how to choose](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC L6-100: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Lithium%20batteries&msg=About%20the%20AEC%20L6-100%20(L6%20Lithium)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)