title: "LiFePO4 lithium battery cabinet, 40 Ah modules · L6-40 | AEC"
url: https://www.aecups.com/en/products/l6-lithium/l6-40/
description: "The L6-40 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 40 Ah modules: 41 kWh and 200 kW rated in 600 × 850 × 2000 mm."
language: en
---

L6 Lithium · Batteries and cabinets

# L6-40 LiFePO4 lithium battery cabinet, 40 Ah modules

Lithium 40 Ah LFP lithium battery cabinet

The L6-40 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 40 Ah modules: 41 kWh and 200 kW rated in 600 × 850 × 2000 mm. For AEC IST7 and IST6 UPS that need high power for a short time, 10 to 20 minutes, typically data centres riding through to a generator.

**200 kW per cabinet** Rating

**600 × 850 × 2000 mm** W × D × H

**965 ± 20 kg with 20 modules** Weight

**41 kWh · 20 × 40 Ah** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=165) [Contact us](https://www.aecups.com/en/contacts/?interest=Lithium%20batteries&msg=About%20the%20AEC%20L6-40%20(L6%20Lithium)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/eu-l6/v55/#l6-20x40)

Quick answers

## L6-40: quick answers

**What it is**: The L6-40 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 40 Ah modules: 41 kWh and 200 kW rated in 600 × 850 × 2000 mm.

**Who it is for**: For AEC IST7 and IST6 UPS that need high power for a short time, 10 to 20 minutes, typically data centres riding through to a generator.

**Supply and configuration**: 240 / ±240 / 480 V DC

**Battery and backup**: 41 kWh · 20 × 40 Ah · 10 / 20 min

**Size and weight**: 600 × 850 × 2000 mm · 965 ± 20 kg with 20 modules

**Ordering code**: L6-40 cabinet, M or M1, master or slave · code on request

L6 Lithium

## What sets apart the L6-40

The 40 Ah module uses 6C cells, the highest discharge rate of the three: sixteen LFP cells in series give 51.2 V and 2.05 kWh per module, and each module's DC/DC converter delivers 10 kW. A full cabinet of twenty modules gives 41 kWh and runs 10 minutes at its 200 kW rating. That makes the L6-40 the module for short, high-power backup.

AEC's sizing tables give, for 10 minutes, one module per 10 kW of UPS power up to a full cabinet at 200 kW and four cabinets (80 modules) at 800 kW; for 20 minutes, twice as many. The figures already hold a 10% reserve and 95% battery and inverter efficiency. Version M1, with one battery breaker, is for UPS below 100 kVA and backup within 30 minutes (955 kg full).

- **Against the L6-50** (one size up): Nominal capacity 41 kWh against 58 kWh; Capacity · cell discharge rate 40 Ah · 6C against 50 Ah · 4C; Rated voltage · energy 51.2 V · 2.05 kWh against 57.6 V · 2.88 kWh; Weight 36 ± 1 kg against 37 ± 1 kg; Weight with full modules 965 ± 20 kg (M1: 955) against 985 ± 20 kg (M1: 975).

Planning data

## L6-40: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the L6-40.

### One footprint, two module sizes

**L6-40 · One footprint, two module sizes**

| Module | Energy per cabinet | Rated power per cabinet |
| --- | --- | --- |
| 40 Ah | 41 kWh | 200 kW |

### Two capacities, one drawer size

**L6-40 · Two capacities, one drawer size**

| Item | 40 Ah · 6C |
| --- | --- |
| Cells | LFP, 3.2 V · 18 in series |
| Module voltage | 57.6 V |
| Energy per module | 2.05 kWh |
| Cell discharge rate | 6C |
| DC/DC output | 240 / ±240 / 480 V · 10 kW |
| Current unbalance | ≤ 3% |
| Full cabinet, 20 modules | 41 kWh · 10 min at rated power |
| Size (W × D × H) | 223 × 665 × 152 mm |
| Weight | 36 ± 1 kg |
| Noise | 58 dB |

Installation

## Installing the L6-40: space, cables

Each figure with its source.

**L6-40 · installation**

| Item | Figure | Source |
| --- | --- | --- |
| Clearances | front 800 mm, rear 800 mm, left 0 mm, right 0 mm, top 500 mm | L6 user manual App. A; EMEA 2026 catalogue p.177–178; EMEA 2026 catalogue p.177 |
| Cable entry | DC cables from the top | EMEA 2026 catalogue p.177 |
| Operating temperature | 0 to 40 °C, best 20–30 °C | L6 user manual App. A; EMEA 2026 catalogue p.177 |
| Switches and terminals | Battery breakers behind the front door; 10" touch screen on the master's door. | EMEA 2026 catalogue p.177 |
| Door | One leaf, hinged on the right | EMEA 2026 catalogue p.177 |
| Module withdrawal | 665 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.177–178 |

Size and floor

## How big it is

600 × 850 × 2000 mm · 965 ± 20 kg with 20 modules.

**0.51 m²** footprint

**1,892 kg/m²** floor load

**2 m** height

Floor load = weight ÷ footprint (965 kg).

Backup time

## The backup-time tool reads the catalogue's tables for lithium modules, L6 cabinets and VRLA strings.

[Backup time · L6-40](https://www.aecups.com/en/tools/backup-time/?bat=l6&kw=100)

Drag to turn

In 3D

## Look around the L6-40

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/eu-l6/v55/#l6-20x40)

Technical data

## Technical data L6-40

Only this model's values, from the EMEA 2026 catalogue table.

**L6-40 · Technical data**

|  |  |
| --- | --- |
| Cabinet |  |
| Nominal capacity | 41 kWh |
| Max. modules per cabinet | 20 |
| Rated output power (discharge) | 200 kW |
| Rated output voltage (discharge) | 240 / ±240 / 480 V DC (three output systems) |
| Rated input voltage (charge) | 265 / ±265 / 530 V DC |
| Cell charge current | max. 40 A, default 20 A |
| Discharge overload | 125–135%: 1 min · 135–150%: 30 s · > 150%: 500 ms |
| Current unbalance (module / cabinet) | ≤ 3% |
| Max. cabinets in parallel | 15 |
| SOC · SOH | module SOC accuracy ≥ 95% · SOH estimate accuracy ≥ 90% |
| Functions | discharge SOC balance, battery cold start, self-start after power recovery, EPO, module-level fire control, cell insulation detection |
| Protection | over-temperature, over-current, short circuit, battery over- and under-voltage, low SOC |
| Module |  |
| Capacity · cell discharge rate | 40 Ah · 6C |
| Rated voltage · energy | 51.2 V · 2.05 kWh |
| Cell cycle life | 5,000 cycles at 50% depth of discharge |
| DC/DC output per module | 10 kW |
| Size (W × D × H) | 223 × 665 × 152 mm |
| Weight | 36 ± 1 kg |
| General |  |
| Communication | TCP/IP, RS485 (CAN reserved) |
| Display | 10-inch touch screen (master cabinet) · indicators (slave cabinet) |
| Operating · storage temperature | 0 … +40 °C · −10 … +45 °C |
| Humidity · altitude | 5–95% non-condensing · < 4000 m, derating above 2000 m ([IEC 62040-3](https://webstore.iec.ch/en/publication/60140)) |
| Noise · protection | < 65 dB · IP20 · battery-side overvoltage level 2 |
| Cabinet size (W × D × H) | 600 × 850 × 2000 mm |
| Weight with full modules | 965 ± 20 kg (M1: 955) |

**L6-40 · Models**

| Item | L6-40 |
| --- | --- |
| Module capacity | 40 Ah |
| Cell discharge rate | 6C |
| Modules per cabinet | 20 |
| Energy per cabinet | 41 kWh |
| Rated power per cabinet | 200 kW |
| Typical backup | 10 / 20 min |

Cabinet energy and other cabinet and system data from the L6 user manual; module voltage, energy and DC/DC power from AEC lithium documentation. Specifications are subject to change without notice.

#### **More technical details** range tables, ordering codes

Planning data

## L6 Lithium range tables

### 10 and 20 minutes

Cabinets and modules for each UPS power (cabinets · modules), from the L6 sizing table (2026): new modules, 95% battery and inverter efficiency, the 10% reserve included, never fewer modules than carry the UPS rating.

**L6-40 · 10 and 20 minutes**

| UPS kW | 10 min | 20 min |
| --- | --- | --- |
| ≤ 60 | 1 · 6 | 1 · 12 |
| ≤ 80 | 1 · 8 | 1 · 16 |
| ≤ 100 | 1 · 10 | 1 · 20 |
| ≤ 200 | 1 · 20 | 2 · 40 |
| ≤ 300 | 2 · 30 | 3 · 60 |
| ≤ 400 | 2 · 40 | 4 · 80 |
| ≤ 500 | 3 · 50 | 5 · 100 |
| ≤ 600 | 3 · 60 | 6 · 120 |
| ≤ 800 | 4 · 80 | 8 · 160 |

Ordering codes

## Ordering codes L6-40

**Ordering codes L6-40**

| Code | Description |
| --- | --- |
| L6-40 cabinet | Cabinet for up to 20 × 40 Ah modules, master (touch screen) or slave (indicators), M or M1. Code on request. |
| Modules | 40 Ah · 50 Ah · 100 Ah lithium modules, hot-swappable. Code on request. |
| L6-C-2000 · L6-C-4000 | Combiner cabinet: L6-C-2000 (up to 4 cabinets) · L6-C-4000 (up to 8 cabinets). Code on request. |
| Accessories | Networking device · blank panels · in-row rear frame. Code on request. |

Questions

## Questions about the L6-40

#### How many L6-40 modules for 10 minutes at 100 kW?

From AEC's sizing table: one cabinet with 10 modules for UPS up to 100 kW at 10 minutes, and one cabinet with 20 modules for 20 minutes. The 10% reserve is included; AEC confirms the number for each project.

#### Can L6-40 modules be replaced with the UPS running?

Yes. A faulty module leaves the system on its own and the others keep supplying the UPS; it is replaced online in about 5 minutes. New and old modules work together, so capacity can also be added later.

#### How big is the AEC L6-40 and how much does it weigh?

The AEC L6-40 measures 600 × 850 × 2000 mm; weight: 965 ± 20 kg with 20 modules (EMEA 2026 catalogue).

Related models

## The same range: L6 Lithium

[The whole range](https://www.aecups.com/en/products/l6-lithium/)

**L6-40** 40 Ah [**L6-50** 50 Ah · larger rating](https://www.aecups.com/en/products/l6-lithium/l6-50/) [**L6-100** 100 Ah](https://www.aecups.com/en/products/l6-lithium/l6-100/)

Shared by the whole range, on the L6 Lithium page: [the catalogue's photos and drawings](https://www.aecups.com/en/products/l6-lithium/#gallery).

Read next: [L6 lithium battery sizing: modules, cabinets, room](https://www.aecups.com/en/blog/l6-lithium-battery-sizing/) [UPS backup time: how to estimate and extend runtime](https://www.aecups.com/en/blog/ups-backup-time/) [UPS batteries: VRLA vs lithium and how to choose](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC L6-40: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Lithium%20batteries&msg=About%20the%20AEC%20L6-40%20(L6%20Lithium)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)