# Lithium UPS: IST8, All-in-One 20 kVA and L6 cabinets

A lithium UPS stores its backup energy in lithium-ion cells instead of lead-acid blocks. AEC's lithium ranges for EMEA all use LFP cells: [IST8](https://www.aecups.com/en/products/ist8/), 1 to 3 kVA single-phase, with the battery in the 2U chassis; the [All-in-One](https://www.aecups.com/en/products/all-in-one/), a 20 kVA three-phase UPS with the lithium in the same cabinet; [L6](https://www.aecups.com/en/products/l6-lithium/) cabinets of 41, 58 or 69 kWh for IST7 and IST6 up to 1,200 kVA.

Every configuration [Battery sets over 15 years](https://www.aecups.com/en/tools/lithium-vs-vrla/) [UPS finder](https://www.aecups.com/en/tools/ups-finder/)

EMEA 2026 data

## Every AEC lithium configuration

Figures from each range's EMEA 2026 data; where a value is not published, the table says so.

**AEC lithium configurations, EMEA**

| Range, model | Power | Voltage, phases | Where the battery sits | Chemistry, energy | Backup time | Recharge | Life, cycles | Warranty | Footprint, weight |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| [IST8-1, IST8-2, IST8-3](https://www.aecups.com/en/products/ist8/) | 1 / 2 / 3 kVA, 1,000 / 2,000 / 3,000 W | single-phase 208 / 220 / 230 / 240 V | built in, 2U rack or tower | LFP | 12 min at full load, 42 at half load (AEC data; the catalogue prints 11 min without a load) | not published (4 A charge) | up to 8 years, up to 1,000 cycles | 3 years UPS, 5 years lithium battery | 438 × 423 × 86 mm (1 kVA), 438 × 570 × 87 mm (2–3 kVA); 8.9 / 13.6 / 16.1 kg |
| [All-in-One, 50 Ah modules](https://www.aecups.com/en/products/all-in-one/) | 20 kVA / 20 kW (IST9 20 kVA, 3U rack, inside) | three-phase 380 / 400 / 415 V, output 3/3 or 3/1 | in the same cabinet, 2 to 8 modules | LFP, 5.76–23.0 kWh | 15–60 min at 20 kW | not published (10 A charger) | cells: more than 10 years, 5,000 cycles at 50% DoD | 3 years UPS, 5 years lithium modules | cabinet 600 × 1000 × 1110 mm on castors; system 232 to 460 kg |
| [All-in-One, 100 Ah modules](https://www.aecups.com/en/products/all-in-one/) | 20 kVA / 20 kW | three-phase 380 / 400 / 415 V, output 3/3 or 3/1 | in the cabinet, 4 modules | LFP, 23.0 kWh | 60 min at 20 kW, 200 min at 6 kW | not published | cells: more than 10 years, 5,000 cycles at 50% DoD | 3 years UPS, 5 years lithium modules | 600 × 1000 × 1110 mm; 352 kg |
| [L6-40](https://www.aecups.com/en/products/l6-lithium/) | up to 200 kW discharge | 240 / ±240 / 480 V DC, for IST7 and IST6 | external cabinet, 20 × 40 Ah modules | LFP, 41 kWh | 10 min at rated power | not published | 5,000 cycles at 50% DoD | 5 years | 600 × 850 × 2000 mm; 965 kg |
| [L6-50](https://www.aecups.com/en/products/l6-lithium/) | up to 200 kW discharge | 240 / ±240 / 480 V DC, for IST7 and IST6 | external cabinet, 20 × 50 Ah modules | LFP, 58 kWh | 14 min at rated power | not published | 5,000 cycles at 50% DoD | 5 years | 600 × 850 × 2000 mm; 985 kg |
| [L6-100](https://www.aecups.com/en/products/l6-lithium/) | up to 60 kW discharge | 240 / ±240 / 480 V DC, for IST7 and IST6 | external cabinet, 12 × 100 Ah modules | LFP, 69 kWh | 57 min at rated power | not published | 5,000 cycles at 50% DoD | 5 years | 600 × 850 × 2000 mm; 810 kg |

DoD: depth of discharge. L6 backup times are at the cabinet's rated discharge power; for your own load use the [backup time tool](https://www.aecups.com/en/tools/backup-time/).

By load

## Which one carries your load?

Up to 3 kW single-phase in a rack: IST8. 20 kW three-phase with the lithium inside, on castors: the All-in-One. Above that, an IST7 or IST6 three-phase or modular UPS with L6 cabinets. The [UPS finder](https://www.aecups.com/en/tools/ups-finder/) proposes the range and the rating; the "[Lithium or VRLA](https://www.aecups.com/en/tools/lithium-vs-vrla/)" tool counts the battery sets over the years of service you plan.

### 20 kVA three-phase with the lithium built in

The All-in-One is a 600 × 1000 × 1110 mm cabinet holding the IST9 20 kVA (3/3 or 3/1), the distribution with maintenance bypass and the LFP modules. With 2 × 50 Ah the system weighs 232 kg, with 8 it weighs 460; with 4 × 100 Ah it gives 200 minutes at 6 kW. Efficiency up to 96% in double conversion, 99% in ECO.

Rack

### Lithium in a 19-inch rack

IST8 carries its LFP battery in the same 2U chassis, 1 to 3 kVA, AC/AC efficiency up to 93%. It runs from 0 to 60 °C (best 0–40 °C).

Three-phase and modular

### L6 cabinets beside IST7 and IST6

L6 takes 40, 50 or 100 Ah modules, hot-swappable, with a three-layer BMS; up to 15 cabinets in parallel. These AEC UPS also work with external lithium batteries, as their data state:

**AEC UPS ready for external lithium**

| Range | Power | Battery, from the range's data |
| --- | --- | --- |
| [IST9](https://www.aecups.com/en/products/ist9/) | 10–40 kVA | lead-acid or the approved lithium system, through the RS485 protocol card |
| [IST7 10–40](https://www.aecups.com/en/products/ist7-10-40/) | 10–40 kVA | RS485 reserved for lithium battery communication |
| [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/) | 60–200 kVA | VRLA or lithium with the BMS card |
| [IST7-T](https://www.aecups.com/en/products/ist7-t/) | 100–200 kVA | VRLA or lithium; with lithium also an energy-storage UPS |
| [IST6-120](https://www.aecups.com/en/products/ist6-120/) | 30–120 kVA | lead-acid or lithium with the BMS card |
| [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/) | 200–500 kVA | lithium with the BMS card, ±256 V nominal |
| [IST6 400–1200](https://www.aecups.com/en/products/ist6-400-1200/) | 400–1,200 kVA | lithium with the BMS card, 512 V nominal |

The room

## What changes in the room

**Weight.** A full L6-50 cabinet weighs 985 kg on 600 × 850 mm, about 1,931 kg/m² over its footprint: the figure for the structural engineer. The L6-100 weighs 810.

**Temperature.** The L6 cabinet runs from 0 to 40 °C; the All-in-One's batteries from 0 to 40 °C, 15–30 °C recommended; IST8 from 0 to 60 °C.

**Fire safety and ventilation.** The rules for lithium batteries in a room depend on the country and its authorities: this page does not interpret them. [Battery room ventilation](https://www.aecups.com/en/blog/battery-room-ventilation/) and [UPS installation clearances](https://www.aecups.com/en/blog/ups-installation-clearances/) have their own guides.

Further reading

## The lithium guides

[UPS batteries: VRLA or lithium](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/) · [sizing L6 lithium batteries](https://www.aecups.com/en/blog/l6-lithium-battery-sizing/) · [UPS backup time](https://www.aecups.com/en/blog/ups-backup-time/) · [UPS sizing](https://www.aecups.com/en/blog/ups-sizing/) · [LiFePO4 lithium](https://www.aecups.com/en/technology/lithium-lifepo4/)

The ranges

## The lithium ranges

### IST8

Lithium

1–3 kVA

Online UPS, lithium, rack / tower, 1–3 kVA

Details

### All-in-One

Lithium

20 kVA

UPS and lithium battery in one cabinet, 20 kVA

Details

### L6 Lithium

Lithium

40 · 50 · 100 Ah

Modular lithium battery system, 40 · 50 · 100 Ah

Details

Questions

## Questions people ask

#### What is a lithium UPS?

A UPS that stores its backup energy in lithium-ion cells instead of lead-acid blocks. AEC's lithium UPS use lithium iron phosphate cells (LFP, LiFePO4) with their battery management: inside the UPS on IST8, in the same cabinet on the All-in-One, in external L6 cabinets with IST7 and IST6.

#### Is there a 20 kVA three-phase UPS with the lithium built in?

Yes: the All-in-One, one 600 × 1000 mm cabinet on castors holding the IST9 20 kVA, the distribution breakers and 2 to 8 lithium modules of 50 Ah, or 4 of 100 Ah. It gives 15 to 60 minutes at 20 kW with the 50 Ah modules.

#### Which single-phase lithium UPS fits a rack?

IST8, 1 to 3 kVA in 2U, with the LFP battery inside: 12 minutes of backup at full load and 42 at half load in AEC's data, and an output of 208, 220, 230 or 240 V set from the panel.

#### How long do the lithium batteries last?

The EMEA 2026 data give IST8 up to 8 years and up to 1,000 cycles, the All-in-One cells more than 10 years and 5,000 cycles at 50% depth of discharge, the L6 cells 5,000 cycles at 50% DoD. No life in years is given for L6.

#### Do L6 cabinets fit my UPS?

They are designed for AEC IST7 and IST6 UPS, 6 to 1,200 kVA, with up to 15 cabinets in parallel. New and old modules work together, so capacity can be added over the years.

#### What warranty do they carry?

3 years on the UPS electronics and 5 years on the lithium batteries of IST8 and the All-in-One; 5 years on the L6 cabinets.

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.

[Contact us](https://www.aecups.com/en/contacts/#form) [+39 02 9415 8991](tel:+390294158991)