title: "12 V 100 Ah AGM VRLA battery for UPS · OZ Power | AEC"
url: https://www.aecups.com/en/products/oz-power-vrla/oz-12v-100ah/
description: "The OZ Power 12 V 100 Ah is a long-life sealed AGM VRLA block, 328 × 172 × 215 mm and 28.5 kg, the largest battery in the standard AEC cabinets."
language: en
---

OZ Power VRLA · Batteries and cabinets

# OZ Power 12 V 100 Ah AGM VRLA battery for UPS

VRLA 100 Ah 12 V AGM VRLA battery

The OZ Power 12 V 100 Ah is a long-life sealed AGM VRLA block, 328 × 172 × 215 mm and 28.5 kg, the largest battery in the standard AEC cabinets. For IST7 60–200 kVA systems with long backup, in BB7 and BB8 cabinets.

**328 × 172 × 215 mm** W × D × H

**28.5 kg** Weight

**100 · 106 Ah** Battery

Technical data [Catalogue (PDF)](https://www.aecups.com/docs/AEC_UPS_Catalogue_EMEA_2026.pdf#page=204) [Contact us](https://www.aecups.com/en/contacts/?interest=Battery%20cabinets%20and%20VRLA%20batteries&msg=About%20the%20AEC%20OZ%20Power%2012%20V%20100%20Ah%20(OZ%20Power%20VRLA)%3A%20%0AQuantity%3A%20#form)

Quick answers

## OZ Power 12 V 100 Ah: quick answers

**What it is**: The OZ Power 12 V 100 Ah is a long-life sealed AGM VRLA block, 328 × 172 × 215 mm and 28.5 kg, the largest battery in the standard AEC cabinets.

**Who it is for**: For IST7 60–200 kVA systems with long backup, in BB7 and BB8 cabinets.

**Supply and configuration**: 12 V

**Battery and backup**: 100 · 106 Ah

**Size and weight**: 328 × 172 × 215 mm · 28.5 kg

**Ordering code**: OZ-12100 (OZ Power 12 V 100 Ah)

OZ Power VRLA

## What sets apart the OZ Power 12 V 100 Ah

The 100 Ah gives 1693 W per block for 15 minutes and 631 W for 1 hour at 1.75 V per cell; the catalogue's 15 kW / 32-block example lasts about 84 minutes. Its internal resistance is the lowest of the cabinet range (≤ 5.5 mΩ) and it takes up to 30.0 A of charge; terminal F12 (M8).

It is the heaviest load on the floor: a BB7 with 36 × 100 Ah reaches 1992 kg/m², a BB8 with 64 × 100 Ah 2215 kg and 1978 kg/m². The catalogue's code IST7-160-64X100 is built on it.

- **Against the OZ Power 12 V 80 Ah** (one size down): Capacity C10 · C20 100 · 106 Ah against 80.0 · 84.8 Ah; Capacity C3 · C5 75.0 · 85.0 Ah against 60.0 · 68.0 Ah; L × W × H 328 × 172 × 215 mm against 260 × 169 × 211 mm; Total height 220 mm against 216 mm; Weight (approx.) 28.5 kg against 22.0 kg.
- **Against the OZ Power 12 V 200 Ah** (one size up): Capacity C10 · C20 100 · 106 Ah against 200 · 212 Ah; Capacity C3 · C5 75.0 · 85.0 Ah against 150 · 170 Ah; L × W × H 328 × 172 × 215 mm against 522 × 240 × 219 mm; Total height 220 mm against 224 mm; Weight (approx.) 28.5 kg against 58.0 kg.

Planning data

## OZ Power 12 V 100 Ah: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the OZ Power 12 V 100 Ah.

### Power when it matters

**OZ Power 12 V 100 Ah · Power when it matters**

| W per 12 V block, 1.75 V/cell | 100 Ah |
| --- | --- |
| 15 min | 1693 |
| 30 min | 1079 |
| 60 min | 631 |

### From load to backup time

**OZ Power 12 V 100 Ah · From load to backup time**

| Battery | Backup time, 15 kW on 32 blocks |
| --- | --- |
| 12 V 100 Ah | ≈ 84 min |

Size and floor

## How big it is

328 × 172 × 215 mm · 28.5 kg.

**0.06 m²** footprint

**0.22 m** height

Technical data

## Technical data OZ Power 12 V 100 Ah

Only this model's values, from the EMEA 2026 catalogue table.

**OZ Power 12 V 100 Ah · Technical data**

|  |  |
| --- | --- |
| OZ Power 12 V |  |
| Capacity C10 · C20 | 100 · 106 Ah |
| Capacity C3 · C5 | 75.0 · 85.0 Ah |
| L × W × H (mm) | 328 × 172 × 215 |
| Total height (mm) | 220 |
| Weight (approx.) | 28.5 kg |
| Internal resistance | ≤ 5.5 mΩ |
| Terminal | F12 (M8) |
| Max. discharge (5 s) | 1000 A |
| Short-circuit current | 2150 A |
| Max. charge current | 30.0 A |
| Design life (float) | 12 years |
| Used in | BB7 · BB8 |

Values at 25 °C, fully charged, from the battery data sheets; C3–C20 = capacity at 3, 5, 10 and 20 h discharge (C3, C5 and C10 to 1.80 V/cell, C20 to 1.75 V/cell). Weight tolerance ± 5%. Terminal: default type, others optional. Specifications are subject to change without notice.

#### **More technical details** range tables, ordering codes

Planning data

## OZ Power VRLA range tables

### 12 V 100 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in BB7 · BB8.

**OZ Power 12 V 100 Ah · constant power, W per 12 V block, 25 °C**

| End V/cell · V/block | 10 min | 15 min | 30 min | 1 h | 2 h | 3 h | 4 h | 5 h | 8 h | 10 h | 20 h |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| 1.60 V · 9.6 V | 2,365 | 1,945 | 1,193 | 689 | 414 | 323 | 256 | 218 | 149 | 124 | 65.4 |
| 1.65 V · 9.9 V | 2,278 | 1,887 | 1,158 | 669 | 403 | 314 | 250 | 214 | 147 | 123 | 64.2 |
| 1.70 V · 10.2 V | 2,135 | 1,793 | 1,118 | 652 | 392 | 307 | 244 | 209 | 145 | 121 | 63.6 |
| 1.75 V · 10.5 V | 1,990 | 1,693 | 1,079 | 631 | 380 | 299 | 238 | 204 | 143 | 120 | 63.0 |
| 1.80 V · 10.8 V | 1,832 | 1,586 | 1,042 | 611 | 368 | 292 | 232 | 199 | 142 | 119 | 62.4 |
| 1.85 V · 11.1 V | 1,525 | 1,334 | 907 | 551 | 339 | 271 | 217 | 187 | 133 | 112 | 59.2 |

### 12 V 100 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 100 Ah block, by end voltage and discharge time.

**OZ Power 12 V 100 Ah · constant current, A, 25 °C**

| End V/cell · V/block | 10 min | 15 min | 30 min | 1 h | 2 h | 3 h | 4 h | 5 h | 8 h | 10 h | 20 h |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| 1.60 V · 9.6 V | 232 | 185 | 110 | 61.1 | 36.4 | 28.2 | 22.2 | 18.9 | 12.7 | 10.5 | 5.52 |
| 1.65 V · 9.9 V | 219 | 177 | 105 | 59.0 | 35.2 | 27.3 | 21.6 | 18.4 | 12.5 | 10.4 | 5.43 |
| 1.70 V · 10.2 V | 202 | 166 | 100 | 57.1 | 34.1 | 26.6 | 21.0 | 17.9 | 12.3 | 10.3 | 5.36 |
| 1.75 V · 10.5 V | 185 | 154 | 96.0 | 55.0 | 32.9 | 25.8 | 20.4 | 17.4 | 12.2 | 10.1 | 5.30 |
| 1.80 V · 10.8 V | 167 | 143 | 91.8 | 52.9 | 31.7 | 25.0 | 19.9 | 17.0 | 12.0 | 10.0 | 5.25 |
| 1.85 V · 11.1 V | 137 | 118 | 79.1 | 47.4 | 29.1 | 23.1 | 18.5 | 15.9 | 11.2 | 9.41 | 4.98 |

Ordering codes

## Ordering codes OZ Power 12 V 100 Ah

**Ordering codes OZ Power 12 V 100 Ah**

| Code | Description |
| --- | --- |
| OZ-1209 · OZ-1224 · OZ-1240 · OZ-1260 · OZ-1280 · OZ-12100 · OZ-12200 | OZ Power 12 V AGM VRLA blocks: 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah |

Questions

## Questions about the OZ Power 12 V 100 Ah

#### What does a cabinet of 100 Ah blocks weigh?

A BB7 weighs 1095 to 1275 kg with 30–36 blocks; a BB8 weighs 1495, 2095 or 2215 kg with 40, 60 or 64 blocks. Check the slab: up to 1992 kg/m².

#### How long does a 32-block string of 100 Ah last at 15 kW?

About 84 minutes in the catalogue's example (95% efficiency assumed, 25 °C, end voltage 1.75 V/cell, new batteries). AEC sizes each project on the real UPS and temperature.

#### How big is the AEC OZ Power 12 V 100 Ah and how much does it weigh?

The AEC OZ Power 12 V 100 Ah measures 328 × 172 × 215 mm; weight: 28.5 kg (EMEA 2026 catalogue).

Related models

## The same range: OZ Power VRLA

[The whole range](https://www.aecups.com/en/products/oz-power-vrla/)

[**OZ Power 12 V 9 Ah** 9 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-9ah/) [**OZ Power 12 V 24 Ah** 24 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-24ah/) [**OZ Power 12 V 40 Ah** 40 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-40ah/) [**OZ Power 12 V 60 Ah** 60 Ah](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-60ah/) [**OZ Power 12 V 80 Ah** 80 Ah · smaller rating](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-80ah/) **OZ Power 12 V 100 Ah** 100 Ah [**OZ Power 12 V 200 Ah** 200 Ah · larger rating](https://www.aecups.com/en/products/oz-power-vrla/oz-12v-200ah/)

Batteries and cabinets: [BB7](https://www.aecups.com/en/products/battery-cabinets/bb7/) [BB8](https://www.aecups.com/en/products/battery-cabinets/bb8/)

Shared by the whole range, on the OZ Power VRLA page: [the catalogue's photos and drawings](https://www.aecups.com/en/products/oz-power-vrla/#gallery).

Read next: [UPS batteries: VRLA vs lithium and how to choose](https://www.aecups.com/en/blog/ups-batteries-vrla-vs-lithium/) [UPS maintenance: batteries, checks and schedule](https://www.aecups.com/en/blog/ups-battery-maintenance/) [Battery room ventilation to EN IEC 62485-2 for VRLA](https://www.aecups.com/en/blog/battery-room-ventilation/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC OZ Power 12 V 100 Ah: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.

[Contact us](https://www.aecups.com/en/contacts/?interest=Battery%20cabinets%20and%20VRLA%20batteries&msg=About%20the%20AEC%20OZ%20Power%2012%20V%20100%20Ah%20(OZ%20Power%20VRLA)%3A%20%0AQuantity%3A%20#form) [+39 02 9415 8991](tel:+390294158991)