---
title: "AEC IST3-J 6–10 kVA operating guide: start-up, shutdown"
url: https://www.aecups.com/en/support/operating-guides/ist3-j-6-10/
description: "IST3-J 6–10 kVA: 5 procedures step by step from the AEC user manual (start-up, shutdown, battery test, battery care), the real display screens and the alarms."
language: en
---

Operating guide

# IST3-J 6–10 kVA operating guide

The 6 and 10 kVA rack IST3-J and its LCD: three keys, the load and battery bars, and what each beep means. Every step names the manual's section and page.

Procedures Try the display [User manual (PDF)](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf)

The display

## The display, page by page.

The real screens, recorded from AEC's display simulator. Tap a screen to enlarge it. Keys and icons as in section 2.2.2 of the manual (page 9).

**Output voltage** Mains (normal) mode: the mains, inverter and load icons are lit and the LCD reads the output voltage. The battery icon's bars show the charge.

**Output frequency** Output frequency: one press of the scroll key moves to the next reading.

**Input voltage** Input voltage of the mains. A value outside the input range sends the UPS to battery.

**Battery voltage** Battery voltage, in V DC. Check it during routine maintenance.

**Load** Load in per cent of the rating; the load icon shows the same in four bars, and all four flash on overload.

**Mains failure: on battery** Battery mode: the mains icon is off and the battery feeds the inverter without a break. The buzzer sounds; hold ON for 3 s to silence it.

### Keys and controls

**ON, held 1 s**: UPS off: switches it on.

**ON, held 3 s**: Mains mode: runs a battery test. Battery mode: silences the mains-failure alarm.

**OFF, held 1 s**: UPS on: switches it off.

**Function key**: Each press shows the next reading: output voltage and frequency, input voltage and frequency, battery voltage, internal temperature, load, fault information. Held 5 s it opens the setting page.

**Function key, held 5 s**: Setting page: a short press picks a setting, a long press confirms it.

Passwords are not printed here: the settings pages need the administrator access that AEC technical service gives.

Procedures

## Start-up, shutdown, battery test, battery care.

From the AEC-UM-IST3J-6-10 Rev. 01 user manual. The link on each procedure opens the PDF on its page.

#### Checks before start-up Wiring, earth and load, before the first start. Manual §4.1 · p. 20 · 4 steps

Check that the cable connections are tight and the AC wire colours follow the standard.

Check that the UPS is earthed and the voltage between neutral and earth is below 5 V AC.

Long-backup models: check the wiring between the UPS and the battery box.

Check that the output has no short circuit and the load is within the UPS rating.

[Manual §4.1, p. 20](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf#page=20)

#### Start-up Mains in, ON for 1 s, then the loads. Manual §4.2 · p. 20 · 3 steps

Plug the UPS into the mains socket or switch on its mains input breaker.

On the display: Output voltage

Press the ON key on the panel for 1 s to start the UPS.

About 10 s later, when the UPS runs steadily, switch on the loads.

**Caution** Switch on the loads from the largest to the smallest, so as not to trigger the overload protection.

[Manual §4.2, p. 20](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf#page=20)

#### Shutdown Loads off, 10 minutes to cool, OFF for 1 s. Manual §4.3 · p. 20 · 3 steps

Switch off the loads and let the UPS run without load for about 10 minutes to cool down.

Press the OFF key for 1 s.

Unplug the UPS or switch off the mains input breaker.

[Manual §4.3, p. 20](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf#page=20)

#### Battery test and buzzer Two holds of the ON key. Manual §2.2.2 · p. 9 · 3 steps

Mains mode: hold ON for 3 s to start a battery test.

On the display: Battery voltage

Battery mode: hold ON for 3 s to mute the mains-failure alarm.

Replace batteries that show a reduced backup time or fail the battery test; replacement is for authorised, qualified personnel (§4.5).

[Manual §2.2.2, p. 9](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf#page=9)

#### Battery care First charge, periodic discharge, long storage. Manual §4.5 · p. 21 · 3 steps

Charge the battery for 10 hours before first use.

Every 4 to 6 months run the UPS on battery until the low-battery shutdown, then recharge fully; every 2 months in hot climates.

If the UPS is not used for a long time, charge the battery for more than 10 hours every three months. Battery life is generally 3 to 5 years.

[Manual §4.5, p. 21](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf#page=21)

Alarms

## Alarms and what to check.

From Table 4-2 of the manual, page 22. If an alarm stays, or the cause is inside the UPS, call AEC service.

**IST3-J 6–10 kVA: Alarms and what to check.**

| Shown | Buzzer | Meaning and what to check |
| --- | --- | --- |
| EPO | Long beep | Emergency power off active (if fitted): bypass and inverter outputs are off. |
| BUS | Long beep | DC bus voltage fault: the inverter output is off. |
| TMP | Long beep | Over-temperature protection: the inverter output is off. Check the cooling fans and that the vents are free. |
| FAN | Rapid beep (every 0.5 s) | Fan fault alarm: the inverter output is about to shut down for protection. Check the cooling fans. |
| FAN | Long beep | Fan fault protection: the inverter output is off. |
| OUT | Long beep | Output fault: check the output for a short circuit or too much load. |
| BAT | Long beep | Battery fault: battery voltage too low or too high (protection). |
| Load bars 25–100 % and overload flicker | Rapid beep (every 0.5 s) | Overload alarm: the output will switch off shortly. Reduce the load. |
| Load bar "overload" lit | Long beep | Overload protection: the output has been switched off. |
| Load bar "short circuit" lit | Long beep | Output short circuit: the output has been switched off. |
| Battery bars and over-voltage flicker | Slow beep (every 2 s) | Battery voltage too high: check the battery and the charger. |
| Battery bar "under-voltage" flickers | Rapid beep (every 0.5 s) | Battery almost exhausted: save your data and shut down the loads. |

[Manual, Table 4-2, p. 22](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf#page=22)

### Common symptoms.

Table 4-1 of the manual, page 21: simple checks before you call service.

#### Mains present, the UPS runs on battery and beeps intermittently

Check the plug, socket and input wiring for a poor contact, and whether the input voltage or frequency on the LCD is outside the UPS input range. Check whether the over-current protector on the rear panel has tripped; press it to reset.

#### The output stops as soon as the load is switched on

Severe overload or a short circuit on the output (often a faulty power strip or load). Or the loads were not started largest first: restart the UPS and, once it runs steadily, switch on the largest load first.

#### Long beep, fault icon on, UPS on bypass

Output overload: reduce the load. A short transfer to bypass when a load starts, with a return on its own, is normal. Or over-temperature: check that the air inlets and outlets are free and the room within its limits.

#### At a mains failure there is no output, or the UPS shuts down soon on low battery

Aged batteries with lost capacity, a charger fault, or a battery cable loose or not connected. Replacement is for authorised personnel.

Practice

## The IST3-J 6–10 kVA display simulator.

The same display, before you stand in front of the UPS: the operating states and the main pages.

UPS state

IST3-J 6–10 kVA · the real display

### Output voltage

**Main pages**

Related: [IST3-J range](https://www.aecups.com/en/products/ist3-j/) [User manual (PDF)](https://www.aecups.com/docs/AEC_IST3-J_6-10kVA_User_Manual_EN.pdf)Manuale d'uso (IT)[All display simulators](https://www.aecups.com/en/tools/simulators/) [All operating guides](https://www.aecups.com/en/support/operating-guides/) [Downloads](https://www.aecups.com/en/downloads/)

Operating guides: [IST3 1–10 kVA](https://www.aecups.com/en/support/operating-guides/ist3-1-10/) [IST3-J 1–3 kVA](https://www.aecups.com/en/support/operating-guides/ist3-j-1-3/) [IST8 1–3 kVA](https://www.aecups.com/en/support/operating-guides/ist8-1-3/) [IST7 10–40 kVA](https://www.aecups.com/en/support/operating-guides/ist7-10-40/) [IST7 60–200 / IST6 30–120 kVA](https://www.aecups.com/en/support/operating-guides/ist7-60-200-ist6-30-120/) [IST6 200–1200 kVA](https://www.aecups.com/en/support/operating-guides/ist6-200-1200/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.

[Contact us](https://www.aecups.com/en/contacts/#form) [+39 02 9415 8991](tel:+390294158991)
