# UPS efficiency: what each point is worth

Efficiency is the share of the input power that reaches the load; the rest is heat. AEC ranges reach 93 % to 98.1 % in double conversion at their best point, and up to 99.2 % in ECO mode; the ladder below compares them at your load.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

Your load

## What a point of efficiency is worth.

Peak efficiency by range, from the EMEA 2026 catalogue, and the energy saved in a year of continuous running at your load.

Semiconductors

## Three-level inverters

**Three-level** inverters split each switching step in two, lowering losses and harmonic content: IST9, IST7 10–40, IST7 60–200 and IST6-120 use them.

**Unity power factor** (kVA = kW) on most ranges means the full rating is usable by modern IT loads.

From the catalogue

## How efficient is each AEC range?

The peak AC/AC efficiency printed in the AEC UPS Catalogue EMEA 2026 for each range, in double conversion and, where the catalogue gives it, in ECO mode. Efficiency is highest near the load the UPS is designed for and falls at light load, so compare ranges at your own load in the ladder above.

**Peak efficiency by AEC range**

| Range | Power | Double conversion, up to | ECO mode, up to |
| --- | --- | --- | --- |
| [IST8](https://www.aecups.com/en/products/ist8/) | 1–3 kVA | 93% (3 kVA) | — |
| [IST9](https://www.aecups.com/en/products/ist9/) | 10–40 kVA | 96% | 99% |
| [IST7 10–40](https://www.aecups.com/en/products/ist7-10-40/) | 10–40 kVA | 96% | 99% |
| [IST7 60–200](https://www.aecups.com/en/products/ist7-60-200/) | 60–200 kVA | 96.5% | 99% |
| [IST6-120](https://www.aecups.com/en/products/ist6-120/) | 30–120 kVA | 97% | 99% |
| [IST6 200–500](https://www.aecups.com/en/products/ist6-200-500/) | 200–500 kVA | 98.1% | ECO and W-ECO modes |
| [IST6 400–1200](https://www.aecups.com/en/products/ist6-400-1200/) | 400–1200 kVA | 98.1% (PLUS modules) | 99.2% |
| [CPSS 10–200](https://www.aecups.com/en/products/cpss-10-200/) | 10–200 kVA | 96% | — |

## How much does one point of efficiency save?

The losses of a UPS are the load times (1 ÷ efficiency − 1). At a steady 100 kW load, running all year (8,760 hours):

**Losses at 100 kW by efficiency**

| Efficiency | Losses | Energy lost per year |
| --- | --- | --- |
| 95% | 5.3 kW | 46,100 kWh |
| 96% | 4.2 kW | 36,500 kWh |
| 97% | 3.1 kW | 27,100 kWh |
| 98.1% | 1.9 kW | 17,000 kWh |
| 99% (ECO) | 1.0 kW | 8,850 kWh |

Every kilowatt lost is also heat the room's cooling has to remove, so the saving counts twice. In ECO mode the load runs on the bypass line and the inverter takes over when the mains leaves its tolerance: the losses fall, but the load sees the mains as it is. Double conversion stays the default for sensitive IT loads; the guide [UPS efficiency and ECO mode](https://www.aecups.com/en/blog/ups-efficiency-eco-mode/) explains when ECO pays.

[Technology **Online double conversion** How an AEC UPS keeps the load on: rectifier, DC bus, inverter, static and maintenance bypass, and the six operating modes on the real display.](https://www.aecups.com/en/technology/online-double-conversion/) [Technology **Lithium LiFePO4 and BMS** Lithium iron phosphate modules, the battery management system, the L6 cabinet opened up, and state of health against lead-acid.](https://www.aecups.com/en/technology/lithium-lifepo4/) [Technology **Modular UPS and N+X** Power modules in a frame, hot-swap, redundancy and parallel systems, from 30 kVA modules to 1.2 MW per cabinet.](https://www.aecups.com/en/technology/modular-ups/) [Technology **Monitoring and communication** Network cards, Modbus, dry contacts and the touch screens, range by range.](https://www.aecups.com/en/technology/monitoring/) [Technology **Isolation transformers** Galvanic isolation, a new neutral, voltage change: what a transformer does in a UPS and when one is needed.](https://www.aecups.com/en/technology/isolation-transformer-ups/)

Standards

## How efficiency is measured

[EN 62040-3](https://webstore.iec.ch/en/publication/60140) sets the method: the efficiency is measured at 25, 50, 75 and 100% of the rated power, in normal mode. The same four load points are the ones the [EU Code of Conduct on UPS](https://www.aecups.com/en/technology/eu-code-of-conduct/) uses for its minimum efficiencies, by performance class (VFI, VI, VFD) and power band.

A datasheet figure without its load and mode says little: a UPS that reaches its peak at 50% may lose a point or more at 25%, where many redundant systems run. The range pages give each AEC curve point by point, with its source: measured where AEC has the table, derived from the datasheet figure elsewhere.

More on technology: [Online double conversion](https://www.aecups.com/en/technology/online-double-conversion/) [Lithium LiFePO4](https://www.aecups.com/en/technology/lithium-lifepo4/) [Modular UPS](https://www.aecups.com/en/technology/modular-ups/) [Isolation transformer](https://www.aecups.com/en/technology/isolation-transformer-ups/) [Monitoring](https://www.aecups.com/en/technology/monitoring/) [EU Code of Conduct](https://www.aecups.com/en/technology/eu-code-of-conduct/) [From thyristor to SiC](https://www.aecups.com/en/technology/power-electronics-history/) [All technology](https://www.aecups.com/en/technology/)