# Lithium LiFePO4 batteries and the BMS in AEC UPS

AEC lithium is lithium iron phosphate: the chemistry chosen for stationary power because it is thermally stable, lasts thousands of cycles and keeps its capacity for years. Every module is watched by a battery management system.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

**50 Ah** per L6-50 LiFePO4 module; 40 and 100 Ah modules too

**2.88 kWh** per 50 Ah module

**58 kWh** one L6 cabinet with 20 × 50 Ah modules

**5,000** cell cycles at 50% depth of discharge

**3 layers** of BMS: module, cabinet and system

Inside the module

## Open the 40, 50 and 100 Ah modules: their cells, their BMS and why every module works on its own, in parallel.

[Open the module](https://www.aecups.com/en/products/l6-lithium/)

L6 lithium cabinet, closed: touch screen and BMS on the door

L6 lithium cabinet

## Open the cabinet

- AEC L6 modular lithium battery cabinet: up to 20 hot-swappable LiFePO4 modules of 40 or 50 Ah, or 12 modules of 100 Ah.
- 10-inch touch screen on the master cabinet, three-layer BMS (module, cabinet, system), a bidirectional DC/DC converter in every module, physical isolation between the modules and the UPS, and module-level fire control.
- 5,000 cell cycles at 50% depth of discharge. For AEC IST7 and IST6 UPS, 6–1200 kVA.
- Specifications: cabinet 600 × 850 × 2000 mm; 41, 58 or 69 kWh with 40, 50 or 100 Ah modules; 36, 37 or 52 kg per module; IP20, < 65 dB.

Up to 15 cabinets work in parallel as master and slaves, joined through a combiner cabinet: model L6-C-2000 (up to 4 cabinets, 2000 A, 120 kg) or L6-C-4000 (up to 8 cabinets, 4000 A, 140 kg); both 400 × 850 × 2000 mm, top or bottom wiring.

[L6 cabinets and modules](https://www.aecups.com/en/products/l6-lithium/) [IST6 with lithium](https://www.aecups.com/en/products/ist6-400-1200/)

Battery management system

## How the BMS keeps it safe.

From the L6 catalogue pages. Click to open each diagram.

**BMS wiring**Every module reports to the cabinet BMS; the cabinet reports to the UPS.

**A fault stays in one module**A faulty module leaves the system; the bus keeps the other modules working.

**State of health**Cabinets of different ages (SOH 88%, 91%, 95%) work together through adaptive SOC management.

**Every cell in view**The master cabinet's touch screen shows the voltage and temperature of every cell.

See it

## The L6 system touch screen, cell by cell: the health of every module, cell voltages and temperatures, charge and discharge curves.

[The BMS display](https://www.aecups.com/en/products/l6-lithium/)

[Technology **Online double conversion** How an AEC UPS keeps the load on: rectifier, DC bus, inverter, static and maintenance bypass, and the six operating modes on the real display.](https://www.aecups.com/en/technology/online-double-conversion/) [Technology **Modular UPS and N+X** Power modules in a cabinet, hot-swap, redundancy and parallel systems, from 30 kVA modules to 1.2 MW per cabinet.](https://www.aecups.com/en/technology/modular-ups/) [Technology **Efficiency** Each range's peak efficiency from the catalogue, the three-level inverter, and what a point of efficiency is worth.](https://www.aecups.com/en/technology/efficiency/) [Technology **Monitoring and communication** Network cards, Modbus, dry contacts and the touchscreens, range by range.](https://www.aecups.com/en/technology/monitoring/) [Technology **Isolation transformers** Galvanic isolation, a new neutral, voltage change: what a transformer does in a UPS and when one is needed.](https://www.aecups.com/en/technology/isolation-transformer-ups/)

Standards

## Standards for the battery side

The AEC catalogue gives [IEC/EN 62040-1](https://webstore.iec.ch/en/publication/80573) and [EN IEC 62485-2](https://webstore.iec.ch/en/publication/7091) for the battery cabinets: IEC 62040-1 is the safety part of the UPS standard, and IEC 62485-2 sets the safety requirements of stationary batteries and battery installations, ventilation included. For the L6 lithium cabinets the data give the derating above 2000 m of altitude per [IEC 62040-3](https://webstore.iec.ch/en/publication/60140), as for the UPS.

More on technology: [Online double conversion](https://www.aecups.com/en/technology/online-double-conversion/) [Modular UPS](https://www.aecups.com/en/technology/modular-ups/) [Isolation transformer](https://www.aecups.com/en/technology/isolation-transformer-ups/) [Efficiency](https://www.aecups.com/en/technology/efficiency/) [Monitoring](https://www.aecups.com/en/technology/monitoring/) [EU Code of Conduct](https://www.aecups.com/en/technology/eu-code-of-conduct/) [From thyristor to SiC](https://www.aecups.com/en/technology/power-electronics-history/) [All technology](https://www.aecups.com/en/technology/)

## Size a lithium system

Tell us the UPS, the load and the minutes: we size the modules and cabinets.

[Send your project](https://www.aecups.com/en/contacts/) [+39 02 9415 8991](tel:+390294158991)