Technology · architecture

# Modular UPS: hot-swap modules and N+X redundancy

A modular UPS is a frame of slots and a set of identical power modules: the modules share the load, any one can be swapped with the system running, and one spare module more than the load needs keeps the load on the inverter if a module stops.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

Cabinets and modules

## Every IST6 cabinet in the catalogue.

Power modules are hot-swappable and slide in from the front; the output power factor is 1 (kVA = kW) as standard.

| Cabinet | Module | Slots | Cabinet power | Battery | Notes |
| --- | --- | --- | --- | --- | --- |
| [**IST6-120**](https://www.aecups.com/en/products/ist6-120/) | 30 kVA | 4 + 1 | 120 kVA | External, lead-acid or lithium (BMS card) | Fifth slot for an N+1 module. 2U power modules, 24 kg. More cabinets in parallel with the parallel kit. |
| [**IST6 200–500**](https://www.aecups.com/en/products/ist6-200-500/) | 50 kVA | 4 | 200 kVA | External, lead-acid or lithium | Cabinet 607 × 860 × 2000 mm, 224 kg without power modules. 3U bypass module. |
| [**IST6 200–500**](https://www.aecups.com/en/products/ist6-200-500/) | 50 kVA | 6 | 300 kVA | External, lead-acid or lithium | Cabinet 607 × 860 × 2000 mm, 236 kg without power modules. 3U bypass module. |
| [**IST6 200–500**](https://www.aecups.com/en/products/ist6-200-500/) | 50 kVA | 8 | 400 kVA | External, lead-acid or lithium | Cabinet 1203 × 864 × 2000 mm, 459 kg without power modules. 3U bypass module. |
| [**IST6 200–500**](https://www.aecups.com/en/products/ist6-200-500/) | 50 kVA | 10 | 500 kVA | External, lead-acid or lithium | Cabinet 1203 × 864 × 2000 mm, 506 kg without power modules. 4.5U bypass module. Up to 8 UPS in parallel. |
| [**IST6 400–1200**](https://www.aecups.com/en/products/ist6-400-1200/) | 100 kVA | 4 | 400 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 345 kg without power modules. 3U bypass module. |
| [**IST6 400–1200**](https://www.aecups.com/en/products/ist6-400-1200/) | 100 kVA | 5 | 500 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 434 kg without power modules. 4.5U bypass module. |
| [**IST6 400–1200**](https://www.aecups.com/en/products/ist6-400-1200/) | 100 kVA | 6 | 600 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 434 kg without power modules. 4.5U bypass module. |
| [**IST6 400–1200**](https://www.aecups.com/en/products/ist6-400-1200/) | 100 kVA | 8 | 800 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 435 kg without power modules. 4.5U bypass module. |
| [**IST6 400–1200**](https://www.aecups.com/en/products/ist6-400-1200/) | 100 kVA | 10 | 1,000 kVA | External, lead-acid or lithium | Cabinet 1201 × 1000 × 2000 mm, 662 kg without power modules. 4.5U bypass module. |
| [**IST6 400–1200**](https://www.aecups.com/en/products/ist6-400-1200/) | 100 kVA | 12 | 1,200 kVA | External, lead-acid or lithium | Cabinet 1201 × 1000 × 2000 mm, 662 kg without power modules. 4.5U bypass module. Up to 98.1% efficiency with PLUS modules; up to 8 UPS in parallel: 9.6 MW. |

Modular UPS, closed

Hot-swap

## Open it, pull a module

In an IST6 each power module carries its own rectifier, inverter and battery converter; the cabinet holds the centralised bypass module, the control cards, the switches and the display. Pulling a module out leaves the others sharing the load, so service happens with the load on the inverter, as long as the remaining modules can carry it.

N + X

## Redundancy you can count

N modules carry the load; X are spare. With 90 kVA of load on 30 kVA modules, N is 3: fit 4 and any one module can fail (N+1), fit 5 and two can (N+2). The display shows the state.

Large modular UPS, closed

[Technology **Online double conversion** How an AEC UPS keeps the load on: rectifier, DC bus, inverter, static and maintenance bypass, and the six operating modes on the real display.](https://www.aecups.com/en/technology/online-double-conversion/) [Technology **Lithium LiFePO4 and BMS** Lithium iron phosphate modules, the battery management system, the L6 cabinet opened up, and state of health against lead-acid.](https://www.aecups.com/en/technology/lithium-lifepo4/) [Technology **Efficiency** Each range's peak efficiency from the catalogue, the three-level inverter, and what a point of efficiency is worth.](https://www.aecups.com/en/technology/efficiency/) [Technology **Monitoring and communication** Network cards, Modbus, dry contacts and the touchscreens, range by range.](https://www.aecups.com/en/technology/monitoring/) [Technology **Isolation transformers** Galvanic isolation, a new neutral, voltage change: what a transformer does in a UPS and when one is needed.](https://www.aecups.com/en/technology/isolation-transformer-ups/)

Standards

## Standards for a modular system

A modular UPS is classed and tested as one UPS: [IEC 62040-3](https://webstore.iec.ch/en/publication/60140) sets how its performance is stated and measured (online double conversion is its VFI class), [IEC 62040-1](https://webstore.iec.ch/en/publication/80573) its safety and [IEC 62040-2](https://webstore.iec.ch/en/publication/33696) its electromagnetic compatibility. The AEC catalogue gives the derating above 2000 m of altitude of the IST6-120 per IEC 62040-3.

Redundancy is counted in modules: with N modules carrying the load, one more (N+1) keeps the load on the inverter if a module fails, and the failed one is pulled with the system running.

More on technology: [Online double conversion](https://www.aecups.com/en/technology/online-double-conversion/) [Lithium LiFePO4](https://www.aecups.com/en/technology/lithium-lifepo4/) [Isolation transformer](https://www.aecups.com/en/technology/isolation-transformer-ups/) [Efficiency](https://www.aecups.com/en/technology/efficiency/) [Monitoring](https://www.aecups.com/en/technology/monitoring/) [EU Code of Conduct](https://www.aecups.com/en/technology/eu-code-of-conduct/) [From thyristor to SiC](https://www.aecups.com/en/technology/power-electronics-history/) [All technology](https://www.aecups.com/en/technology/)