# Online double conversion: how an AEC UPS rebuilds its output

Every AEC UPS rebuilds its output from scratch: the mains is rectified to DC, the inverter makes a new, clean sine wave, and the battery sits on the DC bus, so a mains failure changes nothing at the output.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

Six operating modes

## Pick a mode. Watch the power move.

The diagram follows the power; beside it, a real AEC UPS touchscreen in that mode, with a note on what is happening.

**Mains inverter output (normal)**

Mains → rectifier → inverter → output, the battery charged at the same time. Tap any block of the diagram for its readings.

SS: static switch. M.BYP: external maintenance bypass. Screens: an AEC UPS touchscreen, one per mode.

From the catalogue

## Diagrams, explained.

Click any diagram to open it large.

**Power flow block**The power path, block by block: rectifier, DC bus with the battery, inverter and static bypass.

**Frequency converter**Frequency-converter operation: the output runs at its own set frequency and the bypass is not used.

**Maintenance bypass**The maintenance bypass feeds the load straight from the mains while the UPS is serviced.

**Short-circuit protection**How the UPS reacts to a short circuit on its output.

**Power walk-in**Power walk-in: when the mains returns, the rectifier takes the load back gradually.

**Generator compatibility**The UPS working with a generator set.

**Peak shaving**Peak shaving: the battery covers part of the load at peak times to limit what is drawn from the grid.

Why online

## Zero transfer time, by design

Because the inverter is always the source of the output, there is nothing to switch when the mains fails: the battery is already on the DC bus. The output voltage and frequency are the UPS's own, whatever the mains does: sags, surges, frequency drift and noise stay on the input side.

The static bypass is the safety net: on an overload or an inverter fault the static switch moves the load to the bypass in a few milliseconds, and back once the inverter is ready. Every AEC range works this way, from the single-phase [IST3](https://www.aecups.com/en/products/ist3/) to the modular [IST6](https://www.aecups.com/en/products/ist6-400-1200/).

| Mode | Load fed by | Battery |
| --- | --- | --- |
| **Normal** | Rectifier → inverter | Charging |
| **Mains failure** | Battery → inverter | Discharging |
| **Static bypass** | Bypass line | Charging |
| **ECO** | Bypass, inverter ready | Charging |
| **Frequency converter** | Rectifier → inverter, bypass off | Charging |
| **Maintenance bypass** | Mains, UPS isolated | Off |

[Technology **Lithium LiFePO4 and BMS** Lithium iron phosphate modules, the battery management system, the L6 cabinet opened up, and state of health against lead-acid.](https://www.aecups.com/en/technology/lithium-lifepo4/) [Technology **Modular UPS and N+X** Power modules in a cabinet, hot-swap, redundancy and parallel systems, from 30 kVA modules to 1.2 MW per cabinet.](https://www.aecups.com/en/technology/modular-ups/) [Technology **Efficiency** Each range's peak efficiency from the catalogue, the three-level inverter, and what a point of efficiency is worth.](https://www.aecups.com/en/technology/efficiency/) [Technology **Monitoring and communication** Network cards, Modbus, dry contacts and the touchscreens, range by range.](https://www.aecups.com/en/technology/monitoring/) [Technology **Isolation transformers** Galvanic isolation, a new neutral, voltage change: what a transformer does in a UPS and when one is needed.](https://www.aecups.com/en/technology/isolation-transformer-ups/)

Standards

## Which standard classes it

The UPS standard has four parts: [IEC 62040-1](https://webstore.iec.ch/en/publication/80573) sets the general and safety requirements, [IEC 62040-2](https://webstore.iec.ch/en/publication/33696) the electromagnetic compatibility (EMC), [IEC 62040-3](https://webstore.iec.ch/en/publication/60140) how performance is specified and tested, and [IEC 62040-4](https://webstore.iec.ch/en/publication/6346) the environmental aspects. In Europe they are published as EN 62040.

IEC 62040-3 sorts UPS by how the output depends on the input: VFD (voltage and frequency dependent, the standby UPS), VI (voltage independent, the line-interactive UPS) and VFI (voltage and frequency independent). Online double conversion is the VFI class: the output voltage and frequency are the inverter's, whatever the mains does.

What the AEC catalogue states for the ranges: the IST7-T to EN/IEC 62040-1 (safety) and EN/IEC 62040-2 (EMC, category C3); the IST7 60–200 EMC to IEC 62040-2:2016, category C3, which is not for residential use without additional measures; the derating above 2000 m of altitude of the IST7 10–40, IST6-120, All-in-One and L6 follows IEC 62040-3.

More on technology: [Lithium LiFePO4](https://www.aecups.com/en/technology/lithium-lifepo4/) [Modular UPS](https://www.aecups.com/en/technology/modular-ups/) [Isolation transformer](https://www.aecups.com/en/technology/isolation-transformer-ups/) [Efficiency](https://www.aecups.com/en/technology/efficiency/) [Monitoring](https://www.aecups.com/en/technology/monitoring/) [EU Code of Conduct](https://www.aecups.com/en/technology/eu-code-of-conduct/) [From thyristor to SiC](https://www.aecups.com/en/technology/power-electronics-history/) [All technology](https://www.aecups.com/en/technology/)