---
title: "Power electronics in UPS: from SCR to SiC | AEC"
url: https://www.aecups.com/en/technology/power-electronics-history/
description: "From the thyristor to silicon carbide: how the UPS power switch changed, and what the IST7, IST6 and CPSS ranges of AEC's EMEA catalogue use today."
language: en
---

Technology · Power electronics

# From thyristor to silicon carbide

Seventy years of the power switch inside a UPS: SCR, bipolar transistors, MOSFET, IGBT, 3-level IGBT and silicon carbide. What each one changed in a typical UPS of its time (input power factor, current distortion, efficiency), and what AEC UPS use today.

Reviewed by **[Bruno Grosso](https://www.aecups.com/en/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/en/about/#cp-cheng)**, with an associate project engineer, AEC Engineering · Published 4 November 2026

**1957** the first thyristor

**3.26 eV** SiC band gap

**98.1%** IST6 200–500, double conversion

The eras Generations compared On film

The eras

## Seven switches, one story.

Tap an era, or use the arrow keys.

Thyristor (SCR)

1957 · Thyristor (SCR)

### The thyristor: the first silicon power switch

General Electric brought out the silicon-controlled rectifier (SCR) in 1957. A gate pulse turns it on, but it turns off only when its current falls to zero. The first static UPS used it as a 6- or 12-pulse rectifier and, with extra commutation circuits, as an inverter driving a heavy output transformer.

Typical UPS of the time: input power factor around 0.8, input current distortion around 30% on a 6-pulse bridge, efficiency in the high 80s.

**AEC** 1968: Allis Electric is founded in Taipei, building switchboards, motor control and industrial controls.

Side by side

## What each generation gained.

The faster and cleaner the switching, the higher the efficiency and the smaller the filters and transformers.

**Typical figures per generation, industry-wide (not AEC data)**

| Generation | Years | Switching, kHz | Input PF | THDi | Efficiency |
| --- | --- | --- | --- | --- | --- |
| Thyristor rectifier and inverter, transformer | 1960s–80s | 0.05–1 | ≈0.8 | ≈30% | 85–90% |
| Thyristor rectifier, BJT PWM inverter | 1970s–80s | 1–5 | ≈0.8 | ≈30% | 88–91% |
| IGBT inverter with output transformer | 1990s | 2–10 | 0.9–0.95 | 8–10% | 90–93% |
| IGBT rectifier and inverter, transformerless | 2000s | 10–20 | 0.99 | < 5% | 93–95% |
| 3-level IGBT | 2010s | 10–20 | 0.99 | < 3% | 96–97% |
| Silicon carbide (SiC) | 2020s | 20–100 | 0.99 | < 3% | 97.5–99% |
| **IST6 200–500** (AEC) | today | — | — | — | **98.1%** |

The heat

## Every point of efficiency is heat you do not make.

Losses = load × (1 ÷ efficiency − 1), at the middle of each generation's typical band, with a steady 100 kW load.

**Thyristor rectifier and inverter, transformer** 87.5%

heat **14.3**

kW lost per 100 kW of load, about 125 MWh a year

**Thyristor rectifier, BJT PWM inverter** 89.5%

heat **11.7**

kW lost per 100 kW of load, about 103 MWh a year

**IGBT inverter with output transformer** 91.5%

heat **9.3**

kW lost per 100 kW of load, about 81 MWh a year

**IGBT rectifier and inverter, transformerless** 94%

heat **6.4**

kW lost per 100 kW of load, about 56 MWh a year

**3-level IGBT** 96.5%

heat **3.6**

kW lost per 100 kW of load, about 32 MWh a year

**Silicon carbide (SiC)** 98.3%

heat **1.8**

kW lost per 100 kW of load, about 16 MWh a year

[AEC ranges' efficiency, curve by curve](https://www.aecups.com/en/technology/efficiency/)

Did you know?

## Notes from power electronics.

The word thyristor joins thyratron, the gas-filled tube it replaced, and transistor.

Silicon carbide was first made in 1891 by Edward Acheson, as an abrasive he called carborundum. Henri Moissan found it in nature, in a meteorite, in 1893: the mineral is named moissanite after him.

In 1907 Henry Round saw a silicon carbide crystal glow under voltage: the first light-emitting diode, a hundred years before SiC reached the UPS.

At 90% a 1 MW load wastes about 111 kW as heat; at 99%, about 10 kW. The difference is about 885,000 kWh a year, before the air conditioning that removes the heat.

A 3-level inverter's output already looks like a staircase: the filter only has to smooth half the step of a 2-level one.

AEC is the UPS brand of the AEC Group, which began with switchboards and motor control in 1968; the group's transformers today reach 36 kV and 15,000 kVA.

Films

## Power electronics on film.

Our own films, with sound: press play.

**Why a 3-level sine wave is cleaner** Two levels against three, drawn live. AEC · 0:13

Questions

## Questions people ask

#### What is the difference between an IGBT and a MOSFET?

Both are driven by a voltage on the gate. A MOSFET conducts like a resistor and switches faster, but its resistance rises steeply with the voltage it blocks; an IGBT conducts like a bipolar transistor, with low losses at high voltage and current, which is why it is the switch of a three-phase UPS's power stages.

#### What does a 3-level inverter change?

Each switch blocks half the DC bus voltage and the output has three levels instead of two: lower switching losses, half the ripple and a smaller filter. Double conversion goes from the typical 93–95% of 2-level designs to 96–97%.

#### Why does silicon carbide raise UPS efficiency?

SiC has a band gap of 3.26 eV and a critical field about ten times silicon's: it blocks high voltage in a thin chip, conducts with little resistance and switches fast with low losses. Double-conversion UPS with SiC reach 98–99%.

#### Are thyristors still used in UPS?

Yes, where a rugged switch at line frequency is needed: the static bypass of every online UPS is a pair of thyristors in anti-parallel, which moves the load to the utility without a break.

More on technology: [Online double conversion](https://www.aecups.com/en/technology/online-double-conversion/) [Lithium LiFePO4](https://www.aecups.com/en/technology/lithium-lifepo4/) [Modular UPS](https://www.aecups.com/en/technology/modular-ups/) [Isolation transformer](https://www.aecups.com/en/technology/isolation-transformer-ups/) [Efficiency](https://www.aecups.com/en/technology/efficiency/) [Monitoring](https://www.aecups.com/en/technology/monitoring/) [EU Code of Conduct](https://www.aecups.com/en/technology/eu-code-of-conduct/) [All technology](https://www.aecups.com/en/technology/)

## Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.

[Contact us](https://www.aecups.com/en/contacts/#form) [+39 02 9415 8991](tel:+390294158991)
