# Backup time

How long your load runs on All-in-One lithium modules, L6 cabinets or OZ Power VRLA batteries: lithium from the catalogue's tables, VRLA with AEC's own calculator, the one AEC's portal uses. AEC's engineers check every system.

[First, find your UPS](https://www.aecups.com/en/tools/ups-finder/)

Backup time

## How many minutes, on which battery.

Battery, load and string: lithium from the EMEA 2026 catalogue's tables, VRLA with AEC's calculator.

**Battery**

**UPS load 10 kW**

1 10 100 800 kW

**VRLA stringModules and cabinets**

For lithium the catalogue gives the backup time by number of modules: nothing to choose here.

## A worked example: 10 kW on an IST7-20

1. The load: 10 kW, half of the 20 kW of the [AEC IST7-20](https://www.aecups.com/en/products/ist7-10-40/ist7-20k/) (power factor 1: 20 kVA = 20 kW).
2. With 36 × 12 V 9 Ah (code IST7-20-36X9) the backup time is 6 minutes; at full load, 20 kW, it falls to 2 minutes.
3. With 40 × 12 V 80 Ah (code IST7-20-40X80) the same 10 kW run for 167 minutes, 60 at full load.
4. Doubling the load more than halves the minutes: a battery gives less in a fast discharge. So the sum starts from the real kW, not from the UPS rating.

Minutes AEC publishes for these ordering codes, new batteries at 25 °C. The tool above uses the same method as AEC's portal (the maker's constant-power table read on a straight line, 1.70 V/cell, 96% efficiency): on another string than the code's, or after rounding, it can differ by a minute.

Questions

## Questions people ask

#### How is UPS backup time calculated?

You need the load in kW (not kVA), the battery (type, capacity in Ah, blocks per string and strings) and the end-of-discharge voltage. For VRLA batteries AEC's calculator reads the power per block in the battery maker's constant-power table, at 1.70 V/cell and 96% efficiency, as AEC's portal does.

#### Why is the backup time more than double at half load?

Because a battery gives more in a slow discharge. In the example the AEC IST7-20 with 36 × 12 V 9 Ah runs 2 minutes at full load and 6 at half load.

#### Do the minutes hold for the whole battery life?

No: the tables give minutes with new batteries at 25 °C. Capacity falls with age and with higher temperatures, so a system is sized with a margin. AEC's engineers check every sizing.

#### Lithium or VRLA: how does the tool work them out?

For lithium (All-in-One modules and L6 cabinets) the tool reads the EMEA 2026 catalogue's tables; for OZ Power VRLA batteries it uses AEC's calculator. One L6 cabinet with 100 Ah modules stores 69 kWh.