# Battery runtime

A VRLA bank's backup time is worked out by the [IEEE 485](https://standards.ieee.org/standard/485-2020.html) method: the load divided by the inverter efficiency and the number of blocks gives the watts per block, which the block's constant-power discharge table turns into minutes at 1.70 V per cell; at end of life an ageing factor of 1.25 applies. For the AEC models with their batteries, the [backup-time tool](https://www.aecups.com/en/tools/backup-time/).

Battery block

Loading the battery data…

Constant power from the battery: the UPS load divided by the inverter efficiency, shared by every cell of the bank, read on the block's constant-power table (watts per cell to the end voltage, 25 °C) interpolated on log scales between the maker's published points. AEC's OZ Power blocks carry the same tables as the [backup-time tool](https://www.aecups.com/en/tools/backup-time/), which reads between the points on a straight line: the two can differ by a few tenths of a minute. Below 25 °C, the temperature factor of IEEE 485 Table 1. End of life: 80 % of the capacity (ageing factor 1.25). A block known only by its 15-minute rating borrows the average shape of the published high-rate curves and is marked as an estimate. A figure for sizing, not a guarantee.

How it works

## From the block to the minutes, in four steps.

1. **The block** An AEC OZ Power block, or any 12 V battery's model number.
2. **The bank** Blocks per string and strings, or the UPS's DC bus.
3. **The load** kW, inverter efficiency and the room temperature.
4. **The minutes** With new batteries and at end of life, at 80 % capacity.

**1.70 V** per cell, the starting end voltage

**25 °C** the makers' tables

**× 1.25** ageing factor at end of life

**IEEE 485** the method