# UPS room fit: will it fit, and where

Pick the AEC configuration and give the room: Room fit places the UPS and its battery cabinets to the millimetre with the manual's clearances, the [HD 60364-7-729](https://webstore.iec.ch/en/publication/1907) operating gangway, door swing, cable entry, floor load, heat and ventilation, and says what fails and how to fix it.

## Room fit

Loading Room fit…

How it works

## The room, checked before the site.

1. **The configuration** The AEC UPS with its battery cabinets, as ordered.
2. **The room** Size, door, windows, obstacles and height.
3. **The layout** UPS and cabinets to the millimetre, with the manual's clearances.
4. **The checks** What does not fit and how to fix it, in plan and 3D.

**7** checks: clearances, gangway, doors, floor, heat, air, cables

**HD 60364-7-729** the operating gangway

**[EN IEC 62485-2](https://webstore.iec.ch/en/publication/7091)** battery ventilation

**mm** to the millimetre, plan and 3D

Questions

## What people ask

#### How much space does a UPS need in front?

What the range's manual asks for, and at least the operating gangway of HD 60364-7-729: 700 mm from the cabinet to the wall, 600 mm from the breaker handles, 500 mm past an open door or a withdrawn module. Room fit draws and checks both.

#### Does the battery room need ventilation?

Yes, with lead-acid batteries: EN IEC 62485-2 gives the air flow from the number of cells and the Ah, and the opening area for natural ventilation. Room fit works it out for the cabinets chosen.

#### Can I get the PDF report or the CAD drawing?

Yes, with the project: ask AEC and an engineer sends the PDF report and the drawing for CAD.