title: "480 V UPS, 3-wire or 4-wire: the neutral explained | AEC"
url: https://www.aecups.com/us/blog/480v-ups-3-wire-vs-4-wire/
description: "Does a 480 V UPS need a neutral? 3-wire and 4-wire UPS compared: 277 V loads, neutral size, unswitched neutrals and the battery midpoint."
language: en-US
---

Guide

# 480 V UPS, 3-wire or 4-wire: the neutral explained

**A 4-wire 480/277 V UPS takes a neutral from its supply and passes it to its loads, so it can feed 277 V circuits; a 3-wire 480 V UPS has no neutral, so 277 V and 120 V loads behind it need a transformer.** AEC CIRRO and CIRRO-IB are 4-wire; INFINITE and INFINITE 1.5MW are 3-wire plus ground.

Reviewed by **[Bruno Grosso](https://www.aecups.com/us/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/us/about/#cp-cheng)**, with an associate project engineer, AEC Engineering · Updated November 21, 2026

7 min read

## Which AEC UPS is 3-wire and which is 4-wire?

| Series | Supply | Neutral | Battery (DC bus) |
| --- | --- | --- | --- |
| [ETHERNO](https://www.aecups.com/us/products/etherno/), [AUREON](https://www.aecups.com/us/products/aureon/) | 208Y/120 V, 4-wire | Carried through; sized for non-linear loads, up to 1.73 × the phase current on ETHERNO | 240 V |
| [RADIANT](https://www.aecups.com/us/products/radiant/), [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/) | 208Y/120 V, 4-wire | Carried through, not switched; main and bypass inputs share one neutral | ±120 V (240 V) with a midpoint |
| [CIRRO-IB](https://www.aecups.com/us/products/cirro-ib/) | 480Y/277 V, 4-wire | Carried through, not switched; rated 1.7 × the output current | ±240 V (480 V), internal |
| [CIRRO](https://www.aecups.com/us/products/cirro/) | 480Y/277 V, 4-wire | Carried through, not switched; neutral-to-ground at the input 5 V or less | 480 V with a center tap, ±240 V |
| [INFINITE](https://www.aecups.com/us/products/infinite/), [INFINITE 1.5MW](https://www.aecups.com/us/products/infinite-1-5mw/) | 480 V, 3-wire + ground | None at the input or output | 480 V or 600 V, no midpoint |

Every one of these UPS takes three-pole breakers. Where there is a neutral, it is a solid conductor through the UPS, never opened by a breaker inside it.

## Does a 480 V UPS need a neutral?

Only if something behind it needs 277 V. In many 480 V buildings the IT loads run at 208Y/120 V from a transformer near them, often inside a power distribution unit (PDU), whose wye secondary creates a new neutral. A UPS upstream of that transformer has no use for a neutral, and a 3-wire UPS fits that layout.

A 4-wire UPS earns its neutral where 277 V loads must ride through: lighting circuits, some HVAC controls, equipment built for 277 V. On AEC's 4-wire UPS the output neutral is the supply's neutral carried through, not switched, and the static bypass connects the output to the input, so the UPS needs a 4-wire supply.

## How big must the neutral be?

Larger than the phases, when the loads are power supplies. Single-phase IT loads draw currents rich in the third harmonic, and in a wye system these add in the neutral instead of cancelling. AEC's manuals size for it:

- **ETHERNO:** the neutral can carry up to 1.73 × the phase current with non-linear loads; size it for that.
- **RADIANT, RADIANT-IB:** neutral 1.5 to 1.7 × the phase conductor for mainly non-linear loads; the output neutral is rated 170 %. On a 100 kVA RADIANT-IB that is 471 A against 277 A per phase.
- **CIRRO-IB:** neutral rated 1.7 × the output current: up to 306 A at 150 kVA, against 180 A per phase.

A 3-wire UPS moves the problem to the transformer: the PDU transformer's secondary neutral carries those currents, and the transformer is chosen for non-linear loads. The [isolation transformer](https://www.aecups.com/us/technology/isolation-transformer-ups/) page explains how to size one after a UPS.

## Should the neutral be switched?

Inside an AEC UPS, no: every AC breaker in the RADIANT, RADIANT-IB, CIRRO-IB and CIRRO manuals is three-pole, with the neutral not switched. Upstream, the choice between a 3-pole and a 4-pole transfer switch follows the building's grounding and its ground-fault protection, and belongs to the engineer of record. If a 4-pole switch opens the neutral during a transfer, the UPS loses its neutral reference for that moment; tell AEC how the neutral is switched before commissioning. Two points from the manuals hold either way:

- Main and bypass inputs share the same neutral (RADIANT, RADIANT-IB, CIRRO-IB, and every cabinet of a parallel system).
- The manuals advise against ground-fault (residual-current) breakers on the UPS feeds. Where ground-fault protection is required, the RADIANT manual places it upstream of the common neutral bonding point.

## What happens on the battery side?

The DC bus has its own midpoint question. CIRRO runs 40 blocks of 12 V as ±240 V with a center tap, so its external battery breaker has one pole per conductor: +, N and −. CIRRO-IB and RADIANT-IB carry their split battery inside. INFINITE has no midpoint: with lead-acid it takes 30 to 50 blocks across + and −, and with AEC L6 lithium cabinets only +, − and ground are connected, the cabinet's N busbar left unconnected and set to "without midline". [Sizing an L6 lithium battery](https://www.aecups.com/us/blog/l6-lithium-cabinet-sizing/) covers the rest of that connection.

## Worked example: 277 V lighting and IT on one 480 V UPS

1. **The loads.** 60 kW of IT at 208Y/120 V and 10 kW of 277 V lighting, both to ride through an outage.
2. **With a 4-wire UPS.** A [CIRRO-IB with three 30 kVA modules](https://www.aecups.com/us/products/cirro-ib/cirib150-3x30/) carries 70 kW plus margin. The lighting panel connects to its 480Y/277 V output directly; the IT goes through a PDU transformer to 208Y/120 V. The neutral is run from the supply; inside the UPS it is rated 1.7 × the output current.
3. **With a 3-wire UPS.** An [INFINITE](https://www.aecups.com/us/products/infinite/) feeds the IT through the same PDU, and the lighting through a second transformer with a 480Y/277 V secondary. No neutral is run to the UPS at all.
4. **The trade.** The 4-wire route saves the lighting transformer and its losses; the 3-wire route keeps the neutral, its harmonics and its size out of the 480 V feeders.

## What mistakes come up with 3-wire and 4-wire UPS?

- **Feeding 277 V loads from a 3-wire UPS.** INFINITE has no neutral terminal: 277 V and 120 V loads need a transformer after it.
- **Running a 4-wire UPS from a 3-wire supply.** The bypass passes the supply's neutral to the output; without one the 277 V loads have no return.
- **Sizing the neutral like a phase.** With IT loads it can carry 1.7 × the phase current.
- **Bonding neutral to ground at the wrong place.** Bonding points decide where ground-fault protection can sit; agree them with the engineer of record before the UPS is wired.
- **Connecting the L6 midline to an INFINITE.** Leave the cabinet's N busbar unconnected.

[208 V or 480 V](https://www.aecups.com/us/blog/208v-vs-480v-ups/) covers the choice of supply, [UPS amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) the currents, and the [UPS sizing tool](https://www.aecups.com/us/tools/ups-sizing/) lists the models for each.

## Questions people ask

#### Does a 480 V UPS need a neutral?

Only if it feeds 277 V loads. A 4-wire 480/277 V UPS such as AEC CIRRO or CIRRO-IB takes and gives a neutral; a 3-wire UPS such as INFINITE has none, so 277 V and 120 V loads need a transformer after it.

#### Can a 480 V UPS feed 277 V lighting directly?

Yes, if it is 4-wire: CIRRO-IB and CIRRO give 480Y/277 V at their output. A 3-wire UPS like INFINITE needs a transformer with a 480Y/277 V secondary.

#### How big should the neutral be on a UPS feeding IT loads?

Larger than a phase: AEC's manuals ask for 1.5 to 1.73 times the phase current with non-linear loads. A 150 kVA CIRRO-IB's neutral is rated 306 A against 180 A per phase.

#### Does an AEC UPS switch the neutral?

No. The AC breakers in the RADIANT, RADIANT-IB, CIRRO-IB and CIRRO manuals are three-pole and the neutral is not switched; main and bypass inputs share one neutral.

More guides: [Modular vs monolithic UPS, 208 V: space, N+1, service](https://www.aecups.com/us/blog/modular-vs-monolithic-ups/) [ECO mode vs double conversion: what the load gives up](https://www.aecups.com/us/blog/ups-eco-mode/) [Data center UPS: modular, 480 V and lithium](https://www.aecups.com/us/blog/data-center-ups/) [N+1 redundancy in modular and parallel UPS, explained](https://www.aecups.com/us/blog/n-plus-1-redundancy-ups/) [All guides](https://www.aecups.com/us/blog/)

Products in this article

## See them in detail.

### CIRRO-IB

4-wire · 3P+N VRLA

30–150 kVA · 480 V 4-wire · 3P+N

Modular online UPS with N+X redundancy for three-phase 480 V, 4-wire loads from 30 to 150 kVA, with internal hot-swappable VRLA battery trays.

View series

### CIRRO

4-wire · 3P+N VRLA

60–1,600 kVA · 480 V 4-wire · 3P+N

Modular online UPS with N+X redundancy for three-phase 480 V, 4-wire loads from 60 to 1,600 kVA, with an external VRLA battery bank.

View series

### INFINITE

3-wire · Delta Lithium or VRLA

100–600 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 100 to 600 kVA, with external lithium battery cabinets.

View series