---
title: "Sizing an L6 lithium battery for an INFINITE UPS | AEC"
url: https://www.aecups.com/us/blog/l6-lithium-cabinet-sizing/
description: "One 50 Ah L6 module per 10 kW for 15 minutes: modules and cabinets for INFINITE and INFINITE 1.5MW, weights, floor load and the room around them."
language: en-US
---

Guide

# Sizing an L6 lithium battery for an INFINITE UPS

**An L6 lithium battery is counted in modules: each 50 Ah module is rated 10 kW for 15 minutes, so a load needs one module per 10 kW for 15 minutes and two for 30.** A 200 kW load takes 20 modules, one full L6 cabinet, for 15 minutes, and 40 modules in two cabinets for 30.

Reviewed by **[Bruno Grosso](https://www.aecups.com/us/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/us/about/#cp-cheng)**, with an associate project engineer, AEC Engineering · Updated November 21, 2026

7 min read

## What does one L6 module give?

| L6-MOD-50LI | Value |
| --- | --- |
| Cells | 18 × 3.2 V LiFePO4, 57.6 V |
| Capacity, energy | 50 Ah, 2.88 kWh nominal |
| Output (its own DC/DC converter) | 10 kW |
| Rating used for runtime | 10 kW for 15 minutes, about 2.5 kWh to the load |
| Size, weight | 8.8 × 26.2 × 6.0 in, 81.6 lb |
| Per cabinet | up to 20 modules: 58 kWh nominal, 200 kW |

Two numbers set the count, the 10 kW and the 2.5 kWh. Dividing the energy you need by the nominal 2.88 kWh gives too few modules: a module delivers about 2.5 kWh in a 15-minute discharge. [Lithium LiFePO4](https://www.aecups.com/us/technology/lithium-lifepo4/) explains why.

## How many modules for your load and minutes?

The L6 manual gives the rule: **modules = the larger of load kW ÷ 10 and load kWh ÷ 2.5**, rounded up, with the kWh at the load being kW × minutes ÷ 60. Then 20 modules to a cabinet.

| Load | 15 min: modules | Cabinets | 30 min: modules | Cabinets |
| --- | --- | --- | --- | --- |
| 50 kW | 5 | 1 | 10 | 1 |
| 100 kW | 10 | 1 | 20 | 1 |
| 150 kW | 15 | 1 | 30 | 2 |
| 200 kW | 20 | 1 | 40 | 2 |
| 300 kW | 30 | 2 | 60 | 3 |
| 400 kW | 40 | 2 | 80 | 4 |
| 600 kW | 60 | 3 | 120 | 6 |

Below 15 minutes the power count wins: 200 kW for 10 minutes is still 20 modules, because 20 modules are what deliver 200 kW. A cabinet's 20 modules are therefore also a ceiling of 200 kW: a 400 kW load cannot run on one cabinet, however short the runtime asked.

## Which INFINITE bundles does the catalog list?

The 2026 catalog sells the INFINITE with its L6 cabinets as one model. Their runtimes follow the same 10 kW rating, at the start of battery life:

| Model | L6 modules | At full load | At half load | Weight |
| --- | --- | --- | --- | --- |
| [INF-100+L6-CAB-10x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) | 10 | 15 min at 100 kW | 30 min | 1,808 lb |
| [INF-100+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/) | 20 | 30 min at 100 kW | 60 min | 2,623.8 lb |
| [INF-200+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/) | 20 | 15 min at 200 kW | 30 min | 2,762.9 lb |
| [INF-400+2xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-400-2xl6-cab-20x50li/) | 40 | 15 min at 400 kW | 30 min | 5,525.7 lb |
| [INF-600+3xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-600-3xl6-cab-20x50li/) | 60 | 15 min at 600 kW | 30 min | 8,597.2 lb |

The N+1 versions, INF-100+1 and INF-200+1 with one 20-module cabinet, keep the same minutes: the spare power module adds no energy. INFINITE 1.5MW works with 4, 6 or 8 L6 cabinets, 80, 120 or 160 modules: 4 cabinets carry up to 800 kW and 6 up to 1,200 kW.

## How does the battery grow later?

Module by module, with the load on. The [INF-100+L6-CAB-10x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) ships its cabinet half full: ten more 50 Ah modules in the same cabinet double its runtime, from 15 to 30 minutes at 100 kW, with no new floor space. New modules work beside old ones, each on its own DC/DC converter, and cabinets share current within 3 %. Past one cabinet, up to 15 cabinets form one system: a master with the touchscreen and up to 14 slaves.

## What does the room need?

| Item | L6 cabinet |
| --- | --- |
| Size (W × D × H) | 23.6 × 33.5 × 78.7 in (600 × 850 × 2000 mm) |
| Weight | 2,171.6 lb with 20 modules, 1,355.8 lb with 10, 540 lb empty |
| Floor load, full | about 395 lb/ft² on its 5.5 ft² |
| Clearances | 31.5 in in front and behind, 19.7 in above; cabinets bolt side by side |
| Floor | concrete or another non-combustible floor |
| Cables | from the top only |
| Temperature | 32–104 °F, best 68–86 °F (20–30 °C) |

- **Working space.** Keep the NEC 110.26 working space in front of the cabinets as well as the 31.5 in clearance: the breakers and the modules are behind the front door.
- **Delivery.** The cabinet travels empty, 540 lb, and each module in its own carton. A module is 81.6 lb: two people, and a lifting platform above 3.3 ft.
- **DC cables.** With the INFINITE, connect +, − and PE and leave the N busbar unconnected: the INFINITE is a 3-wire UPS. The manual sizes + and − at 2 × 250 kcmil each for runs up to 16 ft; for longer runs or loads near the cabinet's rating, ask AEC.
- **Several cabinets.** One cabinet wires straight to the INFINITE; several go through the L6-COMBINER, 15.7 × 33.5 × 78.7 in and 308.6 lb, for up to 8 cabinets and 4,000 A.

## What mistakes come up most?

- **Dividing by 2.88 kWh.** At 15 minutes a module gives about 2.5 kWh: 200 kW for 15 minutes is 20 modules, not 18.
- **One cabinet for a large load.** A cabinet delivers at most 200 kW, whatever the minutes.
- **Forgetting the floor.** A full cabinet loads the floor at about 395 lb/ft²: check the slab, or the stand on a raised floor.
- **Sizing for the UPS today.** If the INFINITE will gain a module or a frame, plan the free slots and the cable route for the final kW.

For the choice between lithium and lead-acid, read [lithium vs VRLA](https://www.aecups.com/us/blog/ups-power-supply-lithium-batteries/). The [L6 lithium page](https://www.aecups.com/us/products/lithium-batteries/) has the module and cabinet in detail, and the [room fit tool](https://www.aecups.com/us/tools/room-fit/) places the cabinets beside the UPS in your room.

## Questions people ask

#### How many L6 lithium modules do I need?

One 50 Ah module per 10 kW of load for 15 minutes, two for 30 minutes: the larger of load kW ÷ 10 and load kWh ÷ 2.5, rounded up. 200 kW for 15 minutes is 20 modules, one full cabinet.

#### How long does one L6 cabinet run an INFINITE?

A full cabinet of 20 modules gives 15 minutes at 200 kW and 30 minutes at 100 kW, at the start of battery life. The INF-200+L6-CAB-20x50LI runs 15 minutes at full load and 30 at half load.

#### How much does an L6 lithium cabinet weigh?

2,171.6 lb with 20 modules, 1,355.8 lb with 10, and 540 lb empty, on a 23.6 × 33.5 in footprint. Each 50 Ah module weighs 81.6 lb and ships in its own carton.

#### Can I add L6 modules later?

Yes, with the load on. A half-full cabinet such as the INF-100+L6-CAB-10x50LI doubles its runtime with ten more modules, and up to 15 cabinets form one system.

More guides: [UPS generator sizing: input, recharge and other loads](https://www.aecups.com/us/blog/ups-generator-sizing/) [Growing a modular UPS: frames, modules and N+1](https://www.aecups.com/us/blog/modular-ups-growth-planning/) [What is a UPS? Uninterruptible power supplies explained](https://www.aecups.com/us/blog/what-is-a-ups/) [Lithium UPS: lithium-ion (LiFePO4) vs VRLA, safety, codes and cost](https://www.aecups.com/us/blog/ups-power-supply-lithium-batteries/) [All guides](https://www.aecups.com/us/blog/)

Products in this article

## See them in detail.

### INFINITE

3-wire · Delta Lithium or VRLA

100–600 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 100 to 600 kVA, with external lithium battery cabinets.

View series

### INFINITE 1.5MW

3-wire · Delta Lithium or VRLA

750–1,500 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 750 to 1,500 kVA, with external lithium battery cabinets.

View series

## Talk to an engineer

Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.

[Send your project](https://www.aecups.com/us/contacts/#form) [+1 786 553 2100](tel:+17865532100)
