# UPS for offices, retail and small business

A small office or store usually needs a 1 to 3 kVA UPS at 120 V for its network rack, such as the AEC LUMINA lithium 2U, or a 6 to 20 kVA split-phase FERRUS SP at 120/240 V for a whole sub-panel. It protects what stops the business when it goes down: the network, the server, the point of sale, the phones and the cameras.

Reviewed by **[Bruno Grosso](https://www.aecups.com/us/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/us/about/#cp-cheng)**, with an associate project engineer, AEC Engineering · Updated November 21, 2026

9 min read

## What should go on the UPS?

- **Yes:** router, firewall and switches; the server or NAS; point-of-sale terminals; the phone system; the video recorder of the security cameras; access control.
- **No:** laser printers, space heaters and coffee makers. Their inrush and heating loads would eat the battery for nothing.

## How big a UPS does a small office need?

Add up what goes on it. An example rack in a 20-person office, with figures of the kind a metered PDU shows (measure your own):

| Equipment | Draw |
| --- | --- |
| Internet modem and router | 30 W |
| Firewall | 40 W |
| 24-port PoE switch, feeding the desk phones and Wi-Fi access points | 400 W |
| Small server | 350 W |
| Network storage (NAS) | 120 W |
| Video recorder for the cameras | 80 W |
| Phone system controller | 60 W |
| **Total** | **1,080 W** |

Kept at 80 % of the UPS rating, 1,080 W needs 1,350 W. The [LUM1500RT-2U-LI](https://www.aecups.com/us/products/lumina/lum1500rt-2u-li/) is 1,500 VA / 1,350 W, so the load sits exactly at 80 %, and its catalog table gives 17 minutes there: enough for the server and the NAS to shut down in order. For the phones to stay up through a longer outage, the [LUM2200RT-2U-LI](https://www.aecups.com/us/products/lumina/lum2200rt-2u-li/) (1,980 W) runs at 55 % and gives between 42 and 46 minutes, the table's figures at 60 % and 50 %. The VRLA [FER1500RT-4X9](https://www.aecups.com/us/products/ferrus-rt/fer1500rt-4x9/) (1,500 W) runs at 72 % and gives about 9 minutes on its internal batteries.

## Which 120 V UPS for one rack or a few desks?

| Series | Power | Battery | Receptacles |
| --- | --- | --- | --- |
| [LUMINA](https://www.aecups.com/us/products/lumina/) 2U rack | 1 to 3 kVA, power factor 0.9 | Internal LiFePO4, 12 to 15 years | 8× NEMA 5-15R (1 kVA) to 4× 5-20R + 1× L5-30R (3 kVA) |
| [FERRUS](https://www.aecups.com/us/products/ferrus/) tower | 1 to 3 kVA, power factor 1 | VRLA, up to 4 external packs | 8× NEMA 5-15R (1 kVA) to 6× 5-20R + 1× L5-30R (3 kVA) |
| [FERRUS RT](https://www.aecups.com/us/products/ferrus-rt/) rack/tower | 1 to 3 kVA, power factor 1 | VRLA, up to 4 external packs | 8× NEMA 5-15R (1 kVA) to 6× 5-20R + 1× L5-30R (3 kVA) |

## Which plug, and which circuit?

A 120 V UPS plugs into a receptacle, and its plug decides the circuit the electrician must provide before it arrives:

- **LUM1500RT-2U-LI**: a cord with a NEMA 5-15P plug, the ordinary office receptacle.
- **LUM2000RT-2U-LI and LUM2200RT-2U-LI**: a NEMA 5-20P plug, which needs a 20 A circuit and a 5-20R receptacle (the one with a T-shaped slot).
- **FERRUS 3 kVA, tower and rack**: an attached cord with a NEMA L5-30P twist-lock plug, on a 30 A circuit with an L5-30R receptacle. A 3 kVA UPS at full output delivers 25 A at 120 V, more than a 20 A circuit can carry.

A dedicated circuit is good practice for any UPS, so a heater or a copier on the same breaker cannot trip it.

## Which UPS protects a whole 120/240 V panel?

Many small commercial buildings have a 120/240 V split-phase service. [FERRUS SP](https://www.aecups.com/us/products/ferrus-sp/) (6 to 20 kVA, tower, with an isolation transformer) and [FERRUS SP RT](https://www.aecups.com/us/products/ferrus-sp-rt/) (6 to 10 kVA, rack, with external battery cabinets) protect a whole sub-panel.

FERRUS SP is hardwired to its output terminal block and has a manual maintenance bypass built in, so the sub-panel stays powered while the UPS is serviced. An example: a dental or accounting office puts 7 kW of workstations, network and phones on one sub-panel. A [FERSP10000-16X9](https://www.aecups.com/us/products/ferrus-sp/fersp10000-16x9/) carries it at 70 % and its 16 internal batteries give 5 minutes; with a BB4US cabinet of 32 blocks beside it, the catalog table gives 18.7 minutes, and with 64 blocks 35.2. At 240 V, 10 kVA is 41.7 A on each leg at full output.

## Lithium or VRLA?

VRLA costs less to buy; lithium lasts longer, weighs less and needs fewer replacements. LUMINA's LiFePO4 battery is rated for 12 to 15 years and 3,000 cycles, and carries a five-year warranty with the UPS. The FERRUS family carries three years on the UPS and two on its VRLA batteries, whose life shortens quickly in a warm closet. More in [how long UPS batteries last](https://www.aecups.com/us/blog/ups-battery-life/).

## Where should the UPS go?

In the rack, at the bottom, or on the floor of a ventilated closet, never in a closed cabinet under a desk. A UPS gives off its losses as heat: the LUM1500RT-2U-LI at 1,080 W and its catalog efficiency of 92.5 % loses about 88 W, about 300 BTU/h, on top of the heat of the equipment it feeds. In a small closet with the door shut, that heat shortens battery life. See [UPS heat output](https://www.aecups.com/us/blog/ups-heat-output-btu/).

## How does the UPS shut equipment down by itself?

With a network card the UPS tells servers to save their work and shut down before the battery runs out, and emails the alarm. See [UPS monitoring](https://www.aecups.com/us/technology/monitoring/) and size the load with the [sizing tool](https://www.aecups.com/us/tools/ups-sizing/).

Every LUMINA and FERRUS has RS232, USB and an emergency power off (EPO) input as standard. A USB cable is enough for one server. For several, fit the network card (SNMP-L on LUMINA, SNMP-M on the FERRUS family), and set the order: the server and the NAS shut down first, a few minutes into the outage, while the switch, the router and the phones stay on until the battery is low. A dry-contact relay card sends "on battery", "battery low" and "fault" to an alarm panel.

## What mistakes do small offices make?

- Buying by the VA on the box instead of the watts the UPS delivers.
- Ordering a 3 kVA unit for an office that has only 15 A receptacles.
- Plugging a power strip with its own surge protection into the UPS output, or the UPS into an extension cord.
- Never testing the battery, and finding out at the next outage that it ended its life two summers ago.
- No shutdown software: the UPS runs flat and the server drops anyway, only later.

## Questions people ask

#### What size UPS do I need for a small office?

Add up the watts of the network, server, phones and point of sale, keep the UPS at about 75 to 80 % of its rating, and match the outlets. A rack of network gear usually fits a 1 to 3 kVA unit such as LUMINA or FERRUS.

#### Should a laser printer go on a UPS?

No. Its heating element draws large inrush currents that shorten runtime and can overload a small UPS, so keep it on the utility supply.

#### What receptacles do AEC 120 V UPS units have?

NEMA 5-15R on the 1 kVA models and the LUMINA 1.5 kVA, NEMA 5-20R on the larger ones, plus a 30 A NEMA L5-30R twist-lock receptacle on the 3 kVA models of LUMINA and FERRUS.

#### What UPS protects a 120/240 V panel?

A split-phase UPS such as the FERRUS SP, 6 to 20 kVA, with an isolation transformer.

#### How long will a UPS run an office network?

17 to 46 minutes for an example rack drawing 1,080 W: 17 minutes on an AEC LUMINA 1.5 kVA and 42 to 46 minutes on the LUMINA 2.2 kVA, from their catalog runtime tables. A lighter load runs longer.

#### What circuit does a 3 kVA UPS need?

At 120 V a 3 kVA UPS delivers 25 A at full output, more than a 20 A circuit carries. The AEC FERRUS 3 kVA models come with a NEMA L5-30P plug for a 30 A circuit and an L5-30R receptacle.

More guides: [UPS glossary: the terms in plain English](https://www.aecups.com/us/blog/ups-glossary/) [How long do UPS batteries last? VRLA and lithium](https://www.aecups.com/us/blog/ups-battery-life/) [How to choose a UPS: six questions to one model](https://www.aecups.com/us/blog/choosing-the-right-ups/) [What is a UPS? Uninterruptible power supplies explained](https://www.aecups.com/us/blog/what-is-a-ups/) [All guides](https://www.aecups.com/us/blog/)

Products in this article

## See them in detail.

### LUMINA

Lithium

1–3 kVA · 120 V

Online double-conversion UPS for single-phase 120 V loads from 1 to 3 kVA, in a 19-inch rack, with internal LiFePO4 lithium batteries.

View series

### FERRUS

VRLA

1–3 kVA · 120 V

Online double-conversion UPS for single-phase 120 V loads from 1 to 3 kVA, in a tower cabinet, with internal VRLA batteries.

View series

### FERRUS SP

VRLA

6–20 kVA · 120/240 V

Online double-conversion UPS for split-phase 120/240 V loads from 6 to 20 kVA, in a tower cabinet, with VRLA batteries.

View series