Guide

# UPS heat output: BTU/h, cooling and the cost of losses

A UPS's heat output is its losses: load × (1 ÷ efficiency − 1), times 3.412 for BTU/h. A UPS at 94 % gives off about 6.4 % of its load as heat, one at 97.5 % about 2.6 %. Every watt a UPS does not deliver to the load turns into heat in the room, and the cooling has to remove it.

Reviewed by **[Bruno Grosso](https://www.aecups.com/us/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/us/about/#cp-cheng)**, with an associate project engineer, AEC Engineering · Updated November 21, 2026

7 min read

## What is the formula?

- **Losses (kW)** = load (kW) × (1 ÷ efficiency − 1)
- **Heat (BTU/h)** = losses (W) × 3.412
- **Cooling (tons)** = BTU/h ÷ 12,000

## How much heat do AEC models give off at full load?

At each series' top efficiency from the 2026 catalog. Real losses are a little higher at part load and while the battery recharges, so leave margin in the cooling.

| Model | Load | Efficiency | Losses | Heat | Losses in a year |
| --- | --- | --- | --- | --- | --- |
| [LUM1000RT-2U-LI](https://www.aecups.com/us/products/lumina/lum1000rt-2u-li/) | 0.9 kW | 91.7 % | 81 W | 280 BTU/h | 710 kWh |
| [FERSP20000-40X9](https://www.aecups.com/us/products/ferrus-sp/fersp20000-40x9/) | 20 kW | 93 % | 1.5 kW | 5,140 BTU/h | 13,190 kWh |
| [ETH20-3X50A-LI](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) | 20 kW | 94 % | 1.28 kW | 4,360 BTU/h | 11,180 kWh |
| [RAD90-6X15](https://www.aecups.com/us/products/radiant/rad90-6x15/) | 90 kW | 94 % | 5.7 kW | 19,600 BTU/h | 50,320 kWh |
| [CIR600-6X100](https://www.aecups.com/us/products/cirro/cir600-6x100/) | 600 kW | 97 % | 18.6 kW | 63,320 BTU/h | 162,560 kWh |
| [INF15-1500](https://www.aecups.com/us/products/infinite-1-5mw/inf15-1500/) | 1,500 kW | 97.5 % | 38.5 kW | 131,230 BTU/h | 336,920 kWh |

Losses in a year assume full load around the clock (8,760 hours); scale them to your real load. At an assumed $0.12 per kWh, the INF15-1500's losses cost about $40,000 a year, and every point of efficiency on a megawatt system is worth thousands of dollars more, before the cost of the cooling that removes the heat.

## Worked example: the cooling for a 15 kW server room

A server room carries 15 kW of IT load on an ETH20-3X50A-LI at 94 %.

1. **The IT load.** Nearly every watt a server draws ends up as heat: 15,000 W × 3.412 = 51,180 BTU/h.
2. **The UPS losses.** 15 kW × (1 ÷ 0.94 − 1) = 0.96 kW, about 3,270 BTU/h.
3. **The total.** About 54,450 BTU/h, 4.5 tons of cooling, before the lighting, the people and the heat through the walls. The UPS adds 6 % to the room's IT heat; on a 97 % system it would add about 3 %.

Size the cooling with margin, and on redundant units if the room cannot stop: the UPS keeps the servers running in an outage, but if the cooling is on the generator only, the room warms during the generator gap.

## Which units does the cooling engineer use?

| From | To | Multiply by |
| --- | --- | --- |
| W | BTU/h | 3.412 |
| BTU/h | W | 0.293 |
| kW of heat | tons of cooling | 0.284 (1 ton = 12,000 BTU/h = 3.517 kW) |
| Losses in kW | kWh a year | 8,760 at a constant load |

Mechanical engineers often size in kW of cooling rather than tons: the heat in kW is the cooling in kW, before the cooling plant's own efficiency.

## What does silicon carbide change at 600 kW?

At the same 600 kW, the CIR600-6X100 at 97 % loses 18.6 kW; an INFINITE INF-600 at 97.3 % loses 16.7 kW. The 0.3 points of efficiency are 1.9 kW less heat, all day: about 16,700 kWh a year at full load, and 6,500 BTU/h less for the cooling to remove, for the same load.

## Why is part load different?

"Efficiency up to" is the best point of the curve, usually at mid to high load. A UPS has losses that do not shrink with the load: control electronics, fans, the magnetizing current of a transformer. At light load they are a larger share, so efficiency falls and the heat per kW of load rises. A 2N system, where each UPS runs at 50 % or less, or an oversized UPS on a small day-one load, sits on that part of the curve. Read the curve of your series at your load on the [efficiency page](https://www.aecups.com/us/technology/efficiency/) rather than the peak figure.

Two other sources add heat for a while. After an outage the charger recharges the battery, and its own losses add to the UPS's. A UPS with an isolation transformer, such as FERRUS SP (up to 93 %), carries the transformer's losses at every load.

## Why are the big systems more efficient?

Efficiency rises with the power stage: ETHERNO and RADIANT, with 3-level IGBT inverters, reach 94 %; CIRRO, also 3-level IGBT, reaches 97 % in its large frames; INFINITE's silicon-carbide (SiC) stage reaches 97.3 %, and 97.5 % on INFINITE 1.5MW. See the [efficiency curves](https://www.aecups.com/us/technology/efficiency/) for each series at your load.

## How should the room be planned?

Add the UPS heat to the IT load's heat when you size the cooling, and keep the battery area near 77 °F (25 °C): heat shortens battery life (see [how long UPS batteries last](https://www.aecups.com/us/blog/ups-battery-life/)). Every AEC model page gives its own heat figure under Quick answers, and the [room fit tool](https://www.aecups.com/us/tools/room-fit/) checks the clearances, the NEC working space and the way in for the model you pick.

## What mistakes skew the heat estimate?

- Working from the UPS rating instead of the load. A 30 kVA UPS carrying 12 kW gives off the losses of 12 kW, at the efficiency of 40 % load.
- Using the peak efficiency for a UPS that will run at 20 % for its first years.
- Forgetting the battery room. VRLA batteries are rated at 77 °F, and the UPS's heat in the same small room works against them.
- Counting the UPS losses but not the IT load the UPS feeds, which is many times larger.

## Questions people ask

#### How do I calculate the heat output of a UPS?

Losses in kW = load in kW × (1 ÷ efficiency − 1); heat in BTU/h = losses in watts × 3.412. An AEC ETHERNO 20 kVA at 20 kW and 94 % efficiency gives off about 1.28 kW, 4,360 BTU/h.

#### How many BTU does a 20 kVA UPS produce?

About 4,360 BTU/h at full load for an AEC ETH20-3X50A-LI (94 % efficiency) and about 5,140 BTU/h for a FERSP20000-40X9 (93 %). Plan a little more: efficiency is lower at part load and while the battery charges.

#### How many tons of cooling does a server room UPS need?

Add the IT load and the UPS losses, in BTU/h, and divide by 12,000. 15 kW of servers on an AEC ETHERNO at 94 % give about 54,450 BTU/h, 4.5 tons, before lighting, people and walls.

#### Does UPS efficiency matter for the electric bill?

Yes, on large systems most of all. An AEC INF15-1500 at full load loses about 337,000 kWh a year at 97.5 % efficiency; at $0.12 per kWh that is about $40,000, before the cooling.

More guides: [UPS amps: output current from kVA at 120, 208 and 480 V](https://www.aecups.com/us/blog/ups-amps-from-kva/) [N+1 redundancy in modular and parallel UPS, explained](https://www.aecups.com/us/blog/n-plus-1-redundancy-ups/) [What is a UPS? Uninterruptible power supplies explained](https://www.aecups.com/us/blog/what-is-a-ups/) [Lithium UPS: lithium-ion (LiFePO4) vs VRLA, safety, codes and cost](https://www.aecups.com/us/blog/ups-power-supply-lithium-batteries/) [All guides](https://www.aecups.com/us/blog/)

Products in this article

## See them in detail.

### ETHERNO

Lithium

10–30 kVA · 208 V

Online double-conversion UPS for three-phase 208 V loads from 10 to 30 kVA, in a tower cabinet, with hot-swappable 50 Ah lithium modules.

View series

### CIRRO

4-wire · 3P+N VRLA

60–1,600 kVA · 480 V 4-wire · 3P+N

Modular online UPS with N+X redundancy for three-phase 480 V, 4-wire loads from 60 to 1,600 kVA, with an external VRLA battery bank.

View series

### INFINITE

3-wire · Delta Lithium or VRLA

100–600 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 100 to 600 kVA, with external lithium battery cabinets.

View series

## Talk to an engineer

Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.