 "name": "AEC UPS USA: UPS models and specifications",
 "source": "AEC UPS catalog 2026",
 "publisher": "AEC UPS USA LLC",
 "url": "https://www.aecups.com/us/data/aec-ups-models.json",
 "updated": "2026-11-24",
 "license": "Free to use with credit to AEC UPS USA; check the datasheet before you specify",
 "models": 91,
 "items": [
  {
   "sku": "LUM1000RT-2U-LI",
   "series": "LUMINA",
   "description": "1kVA Rack 2U, Lithium (LFP), rails included, 120 V",
   "url": "https://www.aecups.com/us/products/lumina/lum1000rt-2u-li/",
   "kva": 1,
   "kw": 0.9,
   "power_factor": "0.9",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 2U",
   "efficiency_max_pct": 91.7,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 24,
   "width_in": 17.24,
   "depth_in": 16.54,
   "height_in": 3.43,
   "width_mm": 438,
   "depth_mm": 420,
   "height_mm": 87,
   "net_weight_lb": 19.6,
   "net_weight_kg": 8.9,
   "warranty": "5 years incl. lithium batteries",
   "runtime_min_at_load_pct": {
    "10": 125,
    "20": 66,
    "25": 55,
    "30": 44,
    "40": 33,
    "50": 27,
    "60": 24,
    "70": 21,
    "75": 19,
    "80": 17,
    "90": 14,
    "100": 11
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "LUM2000RT-2U-LI",
   "series": "LUMINA",
   "description": "2kVA Rack 2U, Lithium (LFP), rails included, 120 V",
   "url": "https://www.aecups.com/us/products/lumina/lum2000rt-2u-li/",
   "kva": 2,
   "kw": 1.8,
   "power_factor": "0.9",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 2U",
   "efficiency_max_pct": 92.5,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 48,
   "width_in": 17.24,
   "depth_in": 22.44,
   "height_in": 3.43,
   "width_mm": 438,
   "depth_mm": 570,
   "height_mm": 87,
   "net_weight_lb": 30,
   "net_weight_kg": 13.6,
   "warranty": "5 years incl. lithium batteries",
   "runtime_min_at_load_pct": {
    "10": 125,
    "20": 66,
    "25": 55,
    "30": 44,
    "40": 33,
    "50": 27,
    "60": 24,
    "70": 21,
    "75": 19,
    "80": 17,
    "90": 14,
    "100": 11
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "LUM2200RT-2U-LI",
   "series": "LUMINA",
   "description": "2.2kVA Rack 2U, Lithium (LFP), extended runtime 23 min at full load",
   "url": "https://www.aecups.com/us/products/lumina/lum2200rt-2u-li/",
   "kva": 2.2,
   "kw": 1.98,
   "power_factor": "0.9",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 2U",
   "efficiency_max_pct": 92.6,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 72,
   "width_in": 17.24,
   "depth_in": 24.21,
   "height_in": 3.43,
   "width_mm": 438,
   "depth_mm": 615,
   "height_mm": 87,
   "net_weight_lb": 42.1,
   "net_weight_kg": 19.1,
   "warranty": "5 years incl. lithium batteries",
   "runtime_min_at_load_pct": {
    "10": 236,
    "20": 118,
    "25": 98,
    "30": 78,
    "40": 59,
    "50": 46,
    "60": 42,
    "70": 37,
    "75": 34.5,
    "80": 32,
    "90": 28,
    "100": 23
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "LUM3000RT-2U-LI",
   "series": "LUMINA",
   "description": "3kVA Rack 2U, Lithium (LFP), rails included, 120 V",
   "url": "https://www.aecups.com/us/products/lumina/lum3000rt-2u-li/",
   "kva": 3,
   "kw": 2.7,
   "power_factor": "0.9",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 2U",
   "efficiency_max_pct": 92.5,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 72,
   "width_in": 17.24,
   "depth_in": 22.44,
   "height_in": 3.43,
   "width_mm": 438,
   "depth_mm": 570,
   "height_mm": 87,
   "net_weight_lb": 37.7,
   "net_weight_kg": 17.1,
   "warranty": "5 years incl. lithium batteries",
   "runtime_min_at_load_pct": {
    "10": 125,
    "20": 66,
    "25": 55,
    "30": 44,
    "40": 33,
    "50": 27,
    "60": 24,
    "70": 21,
    "75": 19,
    "80": 17,
    "90": 14,
    "100": 11
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "LUM1500RT-2U-LI",
   "series": "LUMINA",
   "description": "1.5kVA Rack 2U, Lithium (LFP), rails included, 120 V",
   "url": "https://www.aecups.com/us/products/lumina/lum1500rt-2u-li/",
   "kva": 1.5,
   "kw": 1.35,
   "power_factor": "0.9",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 2U",
   "efficiency_max_pct": 92.5,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 48,
   "width_in": 17.2,
   "depth_in": 22.6,
   "height_in": 3.4,
   "width_mm": 437,
   "depth_mm": 574,
   "height_mm": 86,
   "net_weight_lb": 32.4,
   "net_weight_kg": 14.7,
   "warranty": "5 years incl. lithium batteries",
   "runtime_min_at_load_pct": {
    "10": 125,
    "20": 66,
    "25": 55,
    "30": 44,
    "40": 33,
    "50": 27,
    "60": 24,
    "70": 21,
    "75": 19,
    "80": 17,
    "90": 14,
    "100": 11
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FER1000-2X9",
   "series": "FERRUS",
   "description": "Tower 1kVA",
   "url": "https://www.aecups.com/us/products/ferrus/fer1000-2x9/",
   "kva": 1,
   "kw": 1,
   "power_factor": "1.0",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 24,
   "width_in": 5.6,
   "depth_in": 8.6,
   "height_in": 13.9,
   "width_mm": 142,
   "depth_mm": 218,
   "height_mm": 353,
   "net_weight_lb": 16.5,
   "net_weight_kg": 7.5,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 74.6,
    "20": 31.3,
    "25": 25.1,
    "30": 18.9,
    "40": 13.2,
    "50": 10,
    "60": 7.9,
    "70": 6.5,
    "75": 6,
    "80": 5.5,
    "90": 4.8,
    "100": 4.2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FER2000-4X9",
   "series": "FERRUS",
   "description": "Tower 2kVA",
   "url": "https://www.aecups.com/us/products/ferrus/fer2000-4x9/",
   "kva": 2,
   "kw": 2,
   "power_factor": "1.0",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 48,
   "width_in": 7.48,
   "depth_in": 12.56,
   "height_in": 15.75,
   "width_mm": 190,
   "depth_mm": 319,
   "height_mm": 400,
   "net_weight_lb": 36.3,
   "net_weight_kg": 16.5,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 74.6,
    "20": 31.3,
    "25": 25.1,
    "30": 18.9,
    "40": 13.2,
    "50": 10,
    "60": 7.9,
    "70": 6.5,
    "75": 6,
    "80": 5.5,
    "90": 4.8,
    "100": 4.2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FER3000-6X9",
   "series": "FERRUS",
   "description": "Tower 3kVA",
   "url": "https://www.aecups.com/us/products/ferrus/fer3000-6x9/",
   "kva": 3,
   "kw": 3,
   "power_factor": "1.0",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 72,
   "width_in": 7.48,
   "depth_in": 12.56,
   "height_in": 15.75,
   "width_mm": 190,
   "depth_mm": 319,
   "height_mm": 400,
   "net_weight_lb": 45.2,
   "net_weight_kg": 20.5,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 74.6,
    "20": 31.3,
    "25": 25.1,
    "30": 18.9,
    "40": 13.2,
    "50": 10,
    "60": 7.9,
    "70": 6.5,
    "75": 6,
    "80": 5.5,
    "90": 4.8,
    "100": 4.2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FER1000RT-2X9",
   "series": "FERRUS RT",
   "description": "Rack 1kVA",
   "url": "https://www.aecups.com/us/products/ferrus-rt/fer1000rt-2x9/",
   "kva": 1,
   "kw": 1,
   "power_factor": "1.0",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 19\"",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 24,
   "width_in": 17.3,
   "depth_in": 17.3,
   "height_in": 3.4,
   "width_mm": 439,
   "depth_mm": 439,
   "height_mm": 86,
   "net_weight_lb": 41.8,
   "net_weight_kg": 19,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 74.6,
    "20": 31.3,
    "25": 25.1,
    "30": 18.9,
    "40": 13.2,
    "50": 10,
    "60": 7.9,
    "70": 6.5,
    "75": 6,
    "80": 5.5,
    "90": 4.8,
    "100": 4.2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FER1500RT-4X9",
   "series": "FERRUS RT",
   "description": "Rack 1.5kVA",
   "url": "https://www.aecups.com/us/products/ferrus-rt/fer1500rt-4x9/",
   "kva": 1.5,
   "kw": 1.5,
   "power_factor": "1.0",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 19\"",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 48,
   "width_in": 17.3,
   "depth_in": 17.3,
   "height_in": 3.4,
   "width_mm": 439,
   "depth_mm": 439,
   "height_mm": 86,
   "net_weight_lb": 48.5,
   "net_weight_kg": 22,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 106.8,
    "20": 44.9,
    "25": 36,
    "30": 27.1,
    "40": 18.9,
    "50": 14.3,
    "60": 11.4,
    "70": 9.4,
    "75": 8.7,
    "80": 7.9,
    "90": 6.9,
    "100": 6
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FER2000RT-4X9",
   "series": "FERRUS RT",
   "description": "Rack 2kVA",
   "url": "https://www.aecups.com/us/products/ferrus-rt/fer2000rt-4x9/",
   "kva": 2,
   "kw": 2,
   "power_factor": "1.0",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 19\"",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 48,
   "width_in": 17.3,
   "depth_in": 17.8,
   "height_in": 3.4,
   "width_mm": 439,
   "depth_mm": 452,
   "height_mm": 86,
   "net_weight_lb": 51.8,
   "net_weight_kg": 23.5,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 74.6,
    "20": 31.3,
    "25": 25.1,
    "30": 18.9,
    "40": 13.2,
    "50": 10,
    "60": 7.9,
    "70": 6.5,
    "75": 6,
    "80": 5.5,
    "90": 4.8,
    "100": 4.2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FER3000RT-6X9",
   "series": "FERRUS RT",
   "description": "Rack 3kVA",
   "url": "https://www.aecups.com/us/products/ferrus-rt/fer3000rt-6x9/",
   "kva": 3,
   "kw": 3,
   "power_factor": "1.0",
   "supply": "120 V single-phase",
   "voltage": "120V",
   "phase": "1Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Rack 19\"",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 72,
   "width_in": 17.3,
   "depth_in": 22.8,
   "height_in": 3.4,
   "width_mm": 439,
   "depth_mm": 579,
   "height_mm": 86,
   "net_weight_lb": 61.7,
   "net_weight_kg": 28,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 74.6,
    "20": 31.3,
    "25": 25.1,
    "30": 18.9,
    "40": 13.2,
    "50": 10,
    "60": 7.9,
    "70": 6.5,
    "75": 6,
    "80": 5.5,
    "90": 4.8,
    "100": 4.2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FERSP10000-16X9",
   "series": "FERRUS SP",
   "description": "SP Tower 10kVA internal VRLA",
   "url": "https://www.aecups.com/us/products/ferrus-sp/fersp10000-16x9/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "120/240 V split-phase",
   "voltage": "120/240V",
   "phase": "1Ph Split",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 192,
   "width_in": 9.9,
   "depth_in": 23.6,
   "height_in": 29,
   "width_mm": 252,
   "depth_mm": 599,
   "height_mm": 738,
   "net_weight_lb": 235.9,
   "net_weight_kg": 107,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 56.4,
    "20": 23.7,
    "25": 19,
    "30": 14.3,
    "40": 10,
    "50": 7.5,
    "60": 6,
    "70": 5,
    "75": 4.6,
    "80": 4.2,
    "90": 3.6,
    "100": 3.2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FERSP20000-40X9",
   "series": "FERRUS SP",
   "description": "SP Tower 20kVA internal VRLA",
   "url": "https://www.aecups.com/us/products/ferrus-sp/fersp20000-40x9/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "120/240 V split-phase",
   "voltage": "120/240V",
   "phase": "1Ph Split",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 15.8,
   "depth_in": 28.7,
   "height_in": 38.7,
   "width_mm": 401,
   "depth_mm": 729,
   "height_mm": 983,
   "net_weight_lb": 452,
   "net_weight_kg": 205,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 74.6,
    "20": 31.3,
    "25": 25.1,
    "30": 18.9,
    "40": 13.2,
    "50": 10,
    "60": 7.9,
    "70": 6.5,
    "75": 6,
    "80": 5.5,
    "90": 4.8,
    "100": 3
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FERSP6000-16X9",
   "series": "FERRUS SP",
   "description": "SP Tower 6kVA internal VRLA",
   "url": "https://www.aecups.com/us/products/ferrus-sp/fersp6000-16x9/",
   "kva": 6,
   "kw": 6,
   "power_factor": "1.0",
   "supply": "120/240 V split-phase",
   "voltage": "120/240V",
   "phase": "1Ph Split",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 192,
   "width_in": 9.9,
   "depth_in": 23.6,
   "height_in": 29,
   "width_mm": 252,
   "depth_mm": 599,
   "height_mm": 738,
   "net_weight_lb": 196.2,
   "net_weight_kg": 89,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 106.8,
    "20": 44.9,
    "25": 36,
    "30": 27.1,
    "40": 18.9,
    "50": 14.3,
    "60": 11.4,
    "70": 9.4,
    "75": 8.7,
    "80": 7.9,
    "90": 6.9,
    "100": 6
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "FERSPRT10000-16X9",
   "series": "FERRUS SP RT",
   "description": "10kVA/10kW frame RT NO BATT",
   "url": "https://www.aecups.com/us/products/ferrus-sp-rt/fersprt10000-16x9/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "120/240 V split-phase",
   "voltage": "120/240V",
   "phase": "1Ph Split",
   "topology": "Online Double Conversion",
   "form_factor": "Rack/tower, 19-inch rack",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "3U rack cabinet with 16 × 12 V 9 Ah VRLA, included (UPS 5U + cabinet 3U, 8U in all); more cabinets can be added",
   "battery_dc_bus_v": 192,
   "width_in": 17.3,
   "depth_in": 22.8,
   "height_in": 8.5,
   "width_mm": 439,
   "depth_mm": 579,
   "height_mm": 216,
   "net_weight_lb": 143,
   "net_weight_kg": 64.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "FERSPRT6000-16X9",
   "series": "FERRUS SP RT",
   "description": "6kVA/6kW frame RT NO BATT",
   "url": "https://www.aecups.com/us/products/ferrus-sp-rt/fersprt6000-16x9/",
   "kva": 6,
   "kw": 6,
   "power_factor": "1.0",
   "supply": "120/240 V split-phase",
   "voltage": "120/240V",
   "phase": "1Ph Split",
   "topology": "Online Double Conversion",
   "form_factor": "Rack/tower, 19-inch rack",
   "efficiency_max_pct": 93,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "3U rack cabinet with 16 × 12 V 9 Ah VRLA, included (UPS 4U + cabinet 3U, 7U in all); more cabinets can be added",
   "battery_dc_bus_v": 192,
   "width_in": 17.3,
   "depth_in": 22.8,
   "height_in": 6.7,
   "width_mm": 439,
   "depth_mm": 579,
   "height_mm": 170,
   "net_weight_lb": 128,
   "net_weight_kg": 58.1,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "ETH10",
   "series": "ETHERNO",
   "description": "10kVA, no batteries included",
   "url": "https://www.aecups.com/us/products/etherno/eth10/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "208 V three-phase",
   "voltage": null,
   "phase": null,
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Not included, ordered separately",
   "battery_configuration": "Lithium modules inside, ordered separately",
   "battery_dc_bus_v": null,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 216,
   "net_weight_kg": 98,
   "warranty": "5 years",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "ETH20",
   "series": "ETHERNO",
   "description": "20kVA, no batteries included",
   "url": "https://www.aecups.com/us/products/etherno/eth20/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "208 V three-phase",
   "voltage": null,
   "phase": null,
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Not included, ordered separately",
   "battery_configuration": "Lithium modules inside, ordered separately",
   "battery_dc_bus_v": null,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 227,
   "net_weight_kg": 103,
   "warranty": "5 years",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "ETH30",
   "series": "ETHERNO",
   "description": "30kVA, no batteries included",
   "url": "https://www.aecups.com/us/products/etherno/eth30/",
   "kva": 30,
   "kw": 30,
   "power_factor": "1.0",
   "supply": "208 V three-phase",
   "voltage": null,
   "phase": null,
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Not included, ordered separately",
   "battery_configuration": "Lithium modules inside, ordered separately",
   "battery_dc_bus_v": null,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 240.2,
   "net_weight_kg": 109,
   "warranty": "5 years",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "ETH10-1X50A-LI",
   "series": "ETHERNO",
   "description": "10kVA Lithium x1",
   "url": "https://www.aecups.com/us/products/etherno/eth10-1x50a-li/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 297.6,
   "net_weight_kg": 135,
   "warranty": "5 years",
   "runtime_min_at_load_pct": {
    "10": 133,
    "20": 66,
    "25": 55,
    "30": 44,
    "40": 33,
    "50": 27,
    "60": 23,
    "70": 18,
    "75": 17.5,
    "80": 17,
    "90": 15,
    "100": 14
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "ETH10-2X50A-LI",
   "series": "ETHERNO",
   "description": "10kVA Lithium x2",
   "url": "https://www.aecups.com/us/products/etherno/eth10-2x50a-li/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 379.2,
   "net_weight_kg": 172,
   "warranty": "5 years",
   "runtime_min_at_load_pct": {
    "10": 265,
    "20": 133,
    "25": 111,
    "30": 89,
    "40": 66,
    "50": 55,
    "60": 46,
    "70": 36,
    "75": 35,
    "80": 34,
    "90": 30,
    "100": 27
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "ETH10-3X50A-LI",
   "series": "ETHERNO",
   "description": "10kVA Lithium x3",
   "url": "https://www.aecups.com/us/products/etherno/eth10-3x50a-li/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 460.8,
   "net_weight_kg": 209,
   "warranty": "5 years",
   "runtime_min_at_load_pct": {
    "10": 398,
    "20": 199,
    "25": 166,
    "30": 133,
    "40": 100,
    "50": 82,
    "60": 68,
    "70": 55,
    "75": 53,
    "80": 51,
    "90": 46,
    "100": 41
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "ETH20-2X50A-LI",
   "series": "ETHERNO",
   "description": "20kVA Lithium x2",
   "url": "https://www.aecups.com/us/products/etherno/eth20-2x50a-li/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 390.2,
   "net_weight_kg": 177,
   "warranty": "5 years",
   "runtime_min_at_load_pct": {
    "10": 133,
    "20": 66,
    "25": 55,
    "30": 44,
    "40": 33,
    "50": 27,
    "60": 23,
    "70": 18,
    "75": 17.5,
    "80": 17,
    "90": 15,
    "100": 14
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "ETH20-3X50A-LI",
   "series": "ETHERNO",
   "description": "20kVA Lithium x3",
   "url": "https://www.aecups.com/us/products/etherno/eth20-3x50a-li/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 471.8,
   "net_weight_kg": 214,
   "warranty": "5 years",
   "runtime_min_at_load_pct": {
    "10": 199,
    "20": 100,
    "25": 84,
    "30": 68,
    "40": 51,
    "50": 41,
    "60": 34,
    "70": 27,
    "75": 26.5,
    "80": 26,
    "90": 23,
    "100": 20
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "ETH30-3X50A-LI",
   "series": "ETHERNO",
   "description": "30kVA Lithium x3",
   "url": "https://www.aecups.com/us/products/etherno/eth30-3x50a-li/",
   "kva": 30,
   "kw": 30,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 12.6,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 320,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 485,
   "net_weight_kg": 220,
   "warranty": "5 years",
   "runtime_min_at_load_pct": {
    "10": 133,
    "20": 66,
    "25": 55,
    "30": 44,
    "40": 33,
    "50": 27,
    "60": 23,
    "70": 18,
    "75": 17.5,
    "80": 17,
    "90": 15,
    "100": 14
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "AUR-10",
   "series": "AUREON",
   "description": "AUREON 10kVA Frame — NO BATTERIES INCLUDED (accepts up to 80x 12V/9Ah)",
   "url": "https://www.aecups.com/us/products/aureon/aur-10/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 231,
   "net_weight_kg": 104.8,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "AUR-20",
   "series": "AUREON",
   "description": "AUREON 20kVA Frame — NO BATTERIES INCLUDED (accepts up to 80x 12V/9Ah)",
   "url": "https://www.aecups.com/us/products/aureon/aur-20/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 258,
   "net_weight_kg": 117,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "AUR-30",
   "series": "AUREON",
   "description": "AUREON 30kVA Frame — NO BATTERIES INCLUDED (accepts up to 80x 12V/9Ah)",
   "url": "https://www.aecups.com/us/products/aureon/aur-30/",
   "kva": 30,
   "kw": 30,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 282,
   "net_weight_kg": 127.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "AUR10-40X9A",
   "series": "AUREON",
   "description": "10kVA internal VRLA 40x9",
   "url": "https://www.aecups.com/us/products/aureon/aur10-40x9a/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 465,
   "net_weight_kg": 210.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 190,
    "20": 85,
    "25": 70,
    "30": 55,
    "40": 38,
    "50": 25,
    "60": 18,
    "70": 14,
    "75": 12.5,
    "80": 11,
    "90": 9,
    "100": 7
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "AUR10-80X9A",
   "series": "AUREON",
   "description": "10kVA internal VRLA 80x9",
   "url": "https://www.aecups.com/us/products/aureon/aur10-80x9a/",
   "kva": 10,
   "kw": 10,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 699,
   "net_weight_kg": 317.1,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 380,
    "20": 175,
    "25": 145,
    "30": 115,
    "40": 85,
    "50": 60,
    "60": 45,
    "70": 35,
    "75": 31.5,
    "80": 28,
    "90": 24,
    "100": 20
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "AUR20-60X9A",
   "series": "AUREON",
   "description": "20kVA internal VRLA 60x9",
   "url": "https://www.aecups.com/us/products/aureon/aur20-60x9a/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 609,
   "net_weight_kg": 276.2,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 134,
    "20": 54.5,
    "25": 38,
    "30": 28,
    "40": 18,
    "50": 13.5,
    "60": 10.5,
    "70": 8.5,
    "75": 7.5,
    "80": 6.5,
    "90": 5,
    "100": 4.5
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "AUR20-80X9A",
   "series": "AUREON",
   "description": "20kVA internal VRLA 80x9",
   "url": "https://www.aecups.com/us/products/aureon/aur20-80x9a/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 726,
   "net_weight_kg": 329.3,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 175,
    "20": 85,
    "25": 60,
    "30": 45,
    "40": 28,
    "50": 20,
    "60": 15.5,
    "70": 13,
    "75": 11.5,
    "80": 10.5,
    "90": 9,
    "100": 7.5
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "AUR30-80X9A",
   "series": "AUREON",
   "description": "30kVA internal VRLA 80x9",
   "url": "https://www.aecups.com/us/products/aureon/aur30-80x9a/",
   "kva": 30,
   "kw": 30,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online Double Conversion",
   "form_factor": "Tower",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal",
   "battery_dc_bus_v": 240,
   "width_in": 14.9,
   "depth_in": 39.1,
   "height_in": 49.2,
   "width_mm": 378,
   "depth_mm": 993,
   "height_mm": 1250,
   "net_weight_lb": 750,
   "net_weight_kg": 340.2,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 120,
    "20": 50,
    "25": 40,
    "30": 30,
    "40": 20,
    "50": 14,
    "60": 10,
    "70": 8,
    "75": 7,
    "80": 6,
    "90": 5,
    "100": 4
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "RAD90-1X15",
   "series": "RADIANT",
   "description": "15kVA (frame + 1 PM)",
   "url": "https://www.aecups.com/us/products/radiant/rad90-1x15/",
   "kva": 15,
   "kw": 15,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular Rack 19\"",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 240,
   "width_in": 17.4,
   "depth_in": 33.07,
   "height_in": 59.45,
   "width_mm": 442,
   "depth_mm": 840,
   "height_mm": 1510,
   "net_weight_lb": 238,
   "net_weight_kg": 108,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "RAD90-2X15",
   "series": "RADIANT",
   "description": "30kVA (frame + 2 PM)",
   "url": "https://www.aecups.com/us/products/radiant/rad90-2x15/",
   "kva": 30,
   "kw": 30,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular Rack 19\"",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 240,
   "width_in": 17.4,
   "depth_in": 33.07,
   "height_in": 59.45,
   "width_mm": 442,
   "depth_mm": 840,
   "height_mm": 1510,
   "net_weight_lb": 268.5,
   "net_weight_kg": 121.8,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "RAD90-3X15",
   "series": "RADIANT",
   "description": "45kVA (frame + 3 PM)",
   "url": "https://www.aecups.com/us/products/radiant/rad90-3x15/",
   "kva": 45,
   "kw": 45,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular Rack 19\"",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 240,
   "width_in": 17.4,
   "depth_in": 33.07,
   "height_in": 59.45,
   "width_mm": 442,
   "depth_mm": 840,
   "height_mm": 1510,
   "net_weight_lb": 299,
   "net_weight_kg": 135.7,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "RAD90-4X15",
   "series": "RADIANT",
   "description": "60kVA (frame + 4 PM)",
   "url": "https://www.aecups.com/us/products/radiant/rad90-4x15/",
   "kva": 60,
   "kw": 60,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular Rack 19\"",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 240,
   "width_in": 17.4,
   "depth_in": 33.07,
   "height_in": 59.45,
   "width_mm": 442,
   "depth_mm": 840,
   "height_mm": 1510,
   "net_weight_lb": 329.5,
   "net_weight_kg": 149.5,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "RAD90-5X15",
   "series": "RADIANT",
   "description": "75kVA (frame + 5 PM)",
   "url": "https://www.aecups.com/us/products/radiant/rad90-5x15/",
   "kva": 75,
   "kw": 75,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular Rack 19\"",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 240,
   "width_in": 17.4,
   "depth_in": 33.07,
   "height_in": 59.45,
   "width_mm": 442,
   "depth_mm": 840,
   "height_mm": 1510,
   "net_weight_lb": 360,
   "net_weight_kg": 163.4,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "RAD90-6X15",
   "series": "RADIANT",
   "description": "90kVA (frame + 6 PM)",
   "url": "https://www.aecups.com/us/products/radiant/rad90-6x15/",
   "kva": 90,
   "kw": 90,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular Rack 19\"",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 240,
   "width_in": 17.4,
   "depth_in": 33.07,
   "height_in": 59.45,
   "width_mm": 442,
   "depth_mm": 840,
   "height_mm": 1510,
   "net_weight_lb": 390.5,
   "net_weight_kg": 177.2,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "RADIB100-1X20",
   "series": "RADIANT-IB",
   "description": "20kVA (frame+1PM+240pcs)",
   "url": "https://www.aecups.com/us/products/radiant-ib/radib100-1x20/",
   "kva": 20,
   "kw": 20,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 240,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 1998,
   "net_weight_kg": 906.3,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 480,
    "20": 220,
    "25": 185,
    "30": 145,
    "40": 110,
    "50": 85,
    "60": 65,
    "70": 55,
    "75": 50,
    "80": 45,
    "90": 38,
    "100": 32
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "RADIB100-2X20",
   "series": "RADIANT-IB",
   "description": "40kVA (frame+2PM+240pcs)",
   "url": "https://www.aecups.com/us/products/radiant-ib/radib100-2x20/",
   "kva": 40,
   "kw": 40,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 240,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2042,
   "net_weight_kg": 926.2,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "5": 480,
    "10": 220,
    "15": 145,
    "20": 110,
    "25": 85,
    "30": 65,
    "35": 55,
    "40": 45,
    "45": 38,
    "50": 32,
    "60": 30,
    "70": 24,
    "75": 21.5,
    "80": 19,
    "90": 16,
    "100": 14,
    "12.5": 185,
    "37.5": 50,
    "62.5": 30
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "RADIB100-3X20",
   "series": "RADIANT-IB",
   "description": "60kVA (frame+3PM+240pcs)",
   "url": "https://www.aecups.com/us/products/radiant-ib/radib100-3x20/",
   "kva": 60,
   "kw": 60,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 240,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2086,
   "net_weight_kg": 946.2,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 145,
    "20": 65,
    "25": 50,
    "30": 38,
    "40": 30,
    "50": 21.5,
    "60": 16,
    "70": 14,
    "75": 13.5,
    "80": 12,
    "90": 10,
    "100": 8,
    "3.3": 480,
    "6.7": 220,
    "8.3": 185,
    "13.3": 110,
    "16.7": 85,
    "23.3": 55,
    "26.7": 45,
    "33.3": 32,
    "41.7": 30,
    "46.7": 24,
    "53.3": 19,
    "66.7": 14,
    "83.3": 12,
    "93.3": 10
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "RADIB100-4X20",
   "series": "RADIANT-IB",
   "description": "80kVA (frame+4PM+240pcs)",
   "url": "https://www.aecups.com/us/products/radiant-ib/radib100-4x20/",
   "kva": 80,
   "kw": 80,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 240,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2130,
   "net_weight_kg": 966.2,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "5": 220,
    "10": 110,
    "15": 65,
    "20": 45,
    "25": 32,
    "30": 30,
    "35": 24,
    "40": 19,
    "45": 16,
    "50": 14,
    "60": 12,
    "70": 10,
    "75": 8,
    "80": 8,
    "90": 7,
    "100": 6,
    "2.5": 480,
    "6.3": 185,
    "7.5": 145,
    "12.5": 85,
    "17.5": 55,
    "18.8": 50,
    "22.5": 38,
    "31.3": 30,
    "37.5": 21.5,
    "52.5": 14,
    "56.3": 13.5,
    "62.5": 12,
    "67.5": 10,
    "87.5": 8,
    "93.8": 7
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "RADIB100-5X20",
   "series": "RADIANT-IB",
   "description": "100kVA (frame+5PM+240pcs)",
   "url": "https://www.aecups.com/us/products/radiant-ib/radib100-5x20/",
   "kva": 100,
   "kw": 100,
   "power_factor": "1.0",
   "supply": "208 V three-phase, 4-wire (3P+N)",
   "voltage": "208V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 94,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 240,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2174,
   "net_weight_kg": 986.1,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "2": 480,
    "4": 220,
    "5": 185,
    "6": 145,
    "8": 110,
    "10": 85,
    "12": 65,
    "14": 55,
    "15": 50,
    "16": 45,
    "18": 38,
    "20": 32,
    "24": 30,
    "25": 30,
    "28": 24,
    "30": 21.5,
    "32": 19,
    "36": 16,
    "40": 14,
    "42": 14,
    "45": 13.5,
    "48": 12,
    "50": 12,
    "54": 10,
    "56": 10,
    "60": 8,
    "64": 8,
    "70": 8,
    "72": 7,
    "75": 7,
    "80": 6,
    "90": 4,
    "100": 3
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "CIRIB150-1X30",
   "series": "CIRRO-IB",
   "description": "30kVA (frame+1PM+240pcs)",
   "url": "https://www.aecups.com/us/products/cirro-ib/cirib150-1x30/",
   "kva": 30,
   "kw": 30,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2191.8,
   "net_weight_kg": 994.2,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 300,
    "20": 130,
    "25": 107.5,
    "30": 85,
    "40": 55,
    "50": 45,
    "60": 35,
    "70": 28,
    "75": 25,
    "80": 22,
    "90": 17,
    "100": 14
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "CIRIB150-2X30",
   "series": "CIRRO-IB",
   "description": "60kVA (frame+2PM+240pcs)",
   "url": "https://www.aecups.com/us/products/cirro-ib/cirib150-2x30/",
   "kva": 60,
   "kw": 60,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2243.8,
   "net_weight_kg": 1017.8,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "5": 300,
    "10": 130,
    "15": 85,
    "20": 55,
    "25": 45,
    "30": 35,
    "35": 28,
    "40": 22,
    "45": 17,
    "50": 14,
    "60": 14,
    "70": 12,
    "75": 10.5,
    "80": 9,
    "90": 7,
    "100": 6,
    "12.5": 107.5,
    "37.5": 25,
    "62.5": 14
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "CIRIB150-3X30",
   "series": "CIRRO-IB",
   "description": "90kVA (frame+3PM+240pcs)",
   "url": "https://www.aecups.com/us/products/cirro-ib/cirib150-3x30/",
   "kva": 90,
   "kw": 90,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2295.8,
   "net_weight_kg": 1041.4,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "10": 85,
    "20": 35,
    "25": 25,
    "30": 17,
    "40": 14,
    "50": 10.5,
    "60": 7,
    "70": 6,
    "75": 6,
    "80": 6,
    "90": 4,
    "100": 3,
    "3.3": 300,
    "6.7": 130,
    "8.3": 107.5,
    "13.3": 55,
    "16.7": 45,
    "23.3": 28,
    "26.7": 22,
    "33.3": 14,
    "41.7": 14,
    "46.7": 12,
    "53.3": 9,
    "66.7": 6,
    "83.3": 6,
    "93.3": 4
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "CIRIB150-4X30",
   "series": "CIRRO-IB",
   "description": "120kVA (frame+4PM+240pcs)",
   "url": "https://www.aecups.com/us/products/cirro-ib/cirib150-4x30/",
   "kva": 120,
   "kw": 120,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2347.8,
   "net_weight_kg": 1065,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "5": 130,
    "10": 55,
    "15": 35,
    "20": 22,
    "25": 14,
    "30": 14,
    "35": 12,
    "40": 9,
    "45": 7,
    "50": 6,
    "60": 6,
    "70": 4,
    "75": 3,
    "80": 3,
    "90": 3,
    "100": 2,
    "2.5": 300,
    "6.3": 107.5,
    "7.5": 85,
    "12.5": 45,
    "17.5": 28,
    "18.8": 25,
    "22.5": 17,
    "31.3": 14,
    "37.5": 10.5,
    "52.5": 6,
    "56.3": 6,
    "62.5": 6,
    "67.5": 4,
    "87.5": 3,
    "93.8": 2.5
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "CIRIB150-5X30",
   "series": "CIRRO-IB",
   "description": "150kVA (frame+5PM+240pcs)",
   "url": "https://www.aecups.com/us/products/cirro-ib/cirib150-5x30/",
   "kva": 150,
   "kw": 150,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "Internal Tray System",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 2399.8,
   "net_weight_kg": 1088.6,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": {
    "2": 300,
    "4": 130,
    "5": 107.5,
    "6": 85,
    "8": 55,
    "10": 45,
    "12": 35,
    "14": 28,
    "15": 25,
    "16": 22,
    "18": 17,
    "20": 14,
    "24": 14,
    "25": 14,
    "28": 12,
    "30": 10.5,
    "32": 9,
    "36": 7,
    "40": 6,
    "42": 6,
    "45": 6,
    "48": 6,
    "50": 6,
    "54": 4,
    "56": 4,
    "60": 3,
    "64": 3,
    "70": 3,
    "72": 3,
    "75": 2.5,
    "80": 2
   },
   "runtime_basis": "catalog table, new batteries"
  },
  {
   "sku": "CIR360-1X60",
   "series": "CIRRO",
   "description": "60kVA (frame + 1 PM)",
   "url": "https://www.aecups.com/us/products/cirro/cir360-1x60/",
   "kva": 60,
   "kw": 60,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 636.4,
   "net_weight_kg": 288.7,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR360-2X60",
   "series": "CIRRO",
   "description": "120kVA (frame + 2 PM)",
   "url": "https://www.aecups.com/us/products/cirro/cir360-2x60/",
   "kva": 120,
   "kw": 120,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 726.8,
   "net_weight_kg": 329.7,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR360-3X60",
   "series": "CIRRO",
   "description": "180kVA (frame + 3 PM)",
   "url": "https://www.aecups.com/us/products/cirro/cir360-3x60/",
   "kva": 180,
   "kw": 180,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 817.2,
   "net_weight_kg": 370.7,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR360-4X60",
   "series": "CIRRO",
   "description": "240kVA (frame + 4 PM)",
   "url": "https://www.aecups.com/us/products/cirro/cir360-4x60/",
   "kva": 240,
   "kw": 240,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 907.6,
   "net_weight_kg": 411.7,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR360-5X60",
   "series": "CIRRO",
   "description": "300kVA (frame + 5 PM)",
   "url": "https://www.aecups.com/us/products/cirro/cir360-5x60/",
   "kva": 300,
   "kw": 300,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 998,
   "net_weight_kg": 452.7,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR360-6X60",
   "series": "CIRRO",
   "description": "360kVA (frame + 6 PM)",
   "url": "https://www.aecups.com/us/products/cirro/cir360-6x60/",
   "kva": 360,
   "kw": 360,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 96,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 23.6,
   "depth_in": 39.3,
   "height_in": 78.7,
   "width_mm": 599,
   "depth_mm": 998,
   "height_mm": 1999,
   "net_weight_lb": 1088.4,
   "net_weight_kg": 493.7,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR600-1X100",
   "series": "CIRRO",
   "description": "100kVA (600 frame + 1 PM) — 4 breakers",
   "url": "https://www.aecups.com/us/products/cirro/cir600-1x100/",
   "kva": 100,
   "kw": 100,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 31.5,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 800,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 996.5,
   "net_weight_kg": 452,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR600-2X100",
   "series": "CIRRO",
   "description": "200kVA (600 frame + 2 PM) — 4 breakers",
   "url": "https://www.aecups.com/us/products/cirro/cir600-2x100/",
   "kva": 200,
   "kw": 200,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 31.5,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 800,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 1100.1,
   "net_weight_kg": 499,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR600-4X100",
   "series": "CIRRO",
   "description": "400kVA (600 frame + 4 PM) — 4 breakers",
   "url": "https://www.aecups.com/us/products/cirro/cir600-4x100/",
   "kva": 400,
   "kw": 400,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 31.5,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 800,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 1307.3,
   "net_weight_kg": 593,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR600-5X100",
   "series": "CIRRO",
   "description": "500kVA (600 frame + 5 PM) — 4 breakers",
   "url": "https://www.aecups.com/us/products/cirro/cir600-5x100/",
   "kva": 500,
   "kw": 500,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 31.5,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 800,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 1410.9,
   "net_weight_kg": 640,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR600-6X100",
   "series": "CIRRO",
   "description": "600kVA (600 frame + 6 PM) — 4 breakers",
   "url": "https://www.aecups.com/us/products/cirro/cir600-6x100/",
   "kva": 600,
   "kw": 600,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 31.5,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 800,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 1514.5,
   "net_weight_kg": 687,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR800-7X100",
   "series": "CIRRO",
   "description": "700kVA (800 frame + 7 PM) — 4 breakers",
   "url": "https://www.aecups.com/us/products/cirro/cir800-7x100/",
   "kva": 700,
   "kw": 700,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 31.5,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 800,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 1798.8,
   "net_weight_kg": 815.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR800-8X100",
   "series": "CIRRO",
   "description": "800kVA (800 frame + 8 PM) — 4 breakers",
   "url": "https://www.aecups.com/us/products/cirro/cir800-8x100/",
   "kva": 800,
   "kw": 800,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 31.5,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 800,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 1902.4,
   "net_weight_kg": 862.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1200-9X100",
   "series": "CIRRO",
   "description": "900kVA (1200 frame + 9 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1200-9x100/",
   "kva": 900,
   "kw": 900,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 47.2,
   "depth_in": 43.3,
   "height_in": 78.7,
   "width_mm": 1199,
   "depth_mm": 1100,
   "height_mm": 1999,
   "net_weight_lb": 2308.1,
   "net_weight_kg": 1046.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1200-10X100",
   "series": "CIRRO",
   "description": "1000kVA (1200 frame + 10 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1200-10x100/",
   "kva": 1000,
   "kw": 1000,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 47.2,
   "depth_in": 43.3,
   "height_in": 78.7,
   "width_mm": 1199,
   "depth_mm": 1100,
   "height_mm": 1999,
   "net_weight_lb": 2411.7,
   "net_weight_kg": 1093.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1200-11X100",
   "series": "CIRRO",
   "description": "1100kVA (1200 frame + 11 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1200-11x100/",
   "kva": 1100,
   "kw": 1100,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 47.2,
   "depth_in": 43.3,
   "height_in": 78.7,
   "width_mm": 1199,
   "depth_mm": 1100,
   "height_mm": 1999,
   "net_weight_lb": 2515.3,
   "net_weight_kg": 1140.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1200-12X100",
   "series": "CIRRO",
   "description": "1200kVA (1200 frame + 12 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1200-12x100/",
   "kva": 1200,
   "kw": 1200,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 47.2,
   "depth_in": 43.3,
   "height_in": 78.7,
   "width_mm": 1199,
   "depth_mm": 1100,
   "height_mm": 1999,
   "net_weight_lb": 2618.9,
   "net_weight_kg": 1187.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1600-13X100",
   "series": "CIRRO",
   "description": "1300kVA (1600 frame + 13 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1600-13x100/",
   "kva": 1300,
   "kw": 1300,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 63,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 1600,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 3485.3,
   "net_weight_kg": 1580.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1600-14X100",
   "series": "CIRRO",
   "description": "1400kVA (1600 frame + 14 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1600-14x100/",
   "kva": 1400,
   "kw": 1400,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 63,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 1600,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 3588.9,
   "net_weight_kg": 1627.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1600-15X100",
   "series": "CIRRO",
   "description": "1500kVA (1600 frame + 15 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1600-15x100/",
   "kva": 1500,
   "kw": 1500,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 63,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 1600,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 3692.5,
   "net_weight_kg": 1674.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "CIR1600-16X100",
   "series": "CIRRO",
   "description": "1600kVA (1600 frame + 16 PM) — no breakers, external switchgear",
   "url": "https://www.aecups.com/us/products/cirro/cir1600-16x100/",
   "kva": 1600,
   "kw": 1600,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 4-wire (3P+N)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+X",
   "form_factor": "Modular",
   "efficiency_max_pct": 97,
   "battery": "VRLA (sealed lead-acid)",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 480,
   "width_in": 63,
   "depth_in": 39.4,
   "height_in": 78.7,
   "width_mm": 1600,
   "depth_mm": 1001,
   "height_mm": 1999,
   "net_weight_lb": 3796.1,
   "net_weight_kg": 1721.9,
   "warranty": "3 years on UPS · 2 years on VRLA batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF-100",
   "series": "INFINITE",
   "description": "100kVA (frame100+1 + 1 PM)",
   "url": "https://www.aecups.com/us/products/infinite/inf-100/",
   "kva": 100,
   "kw": 100,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External VRLA bank or L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": 23.62,
   "depth_in": 39.37,
   "height_in": 81.42,
   "width_mm": 600,
   "depth_mm": 1000,
   "height_mm": 2068,
   "net_weight_lb": 452.2,
   "net_weight_kg": 205.1,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF-200",
   "series": "INFINITE",
   "description": "200kVA (frame200+1 + 2 PM)",
   "url": "https://www.aecups.com/us/products/infinite/inf-200/",
   "kva": 200,
   "kw": 200,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External VRLA bank or L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": 23.62,
   "depth_in": 39.37,
   "height_in": 81.42,
   "width_mm": 600,
   "depth_mm": 1000,
   "height_mm": 2068,
   "net_weight_lb": 591.3,
   "net_weight_kg": 268.2,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF-400",
   "series": "INFINITE",
   "description": "400kVA",
   "url": "https://www.aecups.com/us/products/infinite/inf-400/",
   "kva": 400,
   "kw": 400,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External VRLA bank or L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": 23.62,
   "depth_in": 39.37,
   "height_in": 81.42,
   "width_mm": 600,
   "depth_mm": 1000,
   "height_mm": 2068,
   "net_weight_lb": 1182.5,
   "net_weight_kg": 536.4,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF-600",
   "series": "INFINITE",
   "description": "600kVA",
   "url": "https://www.aecups.com/us/products/infinite/inf-600/",
   "kva": 600,
   "kw": 600,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External VRLA bank or L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": 23.62,
   "depth_in": 39.37,
   "height_in": 81.42,
   "width_mm": 600,
   "depth_mm": 1000,
   "height_mm": 2068,
   "net_weight_lb": 1773.8,
   "net_weight_kg": 804.6,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF-100+1",
   "series": "INFINITE",
   "description": "100kVA N+1 (frame + 2 PM)",
   "url": "https://www.aecups.com/us/products/infinite/inf-100-1/",
   "kva": 100,
   "kw": 100,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+1",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External VRLA bank or L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": 23.62,
   "depth_in": 39.37,
   "height_in": 81.42,
   "width_mm": 600,
   "depth_mm": 1000,
   "height_mm": 2068,
   "net_weight_lb": 571.3,
   "net_weight_kg": 259.1,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF-100+1+L6-CAB-20x50LI",
   "series": "INFINITE",
   "description": "100kVA N+1 + 1x L6 20x50",
   "url": "https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/",
   "kva": 100,
   "kw": 100,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+1",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "External L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": null,
   "depth_in": null,
   "height_in": null,
   "width_mm": null,
   "depth_mm": null,
   "height_mm": null,
   "net_weight_lb": 2742.8,
   "net_weight_kg": 1244.1,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": {
    "10": 300,
    "20": 150,
    "25": 120,
    "30": 100,
    "40": 75,
    "50": 60,
    "60": 50,
    "70": 43,
    "75": 40,
    "80": 38,
    "90": 33,
    "100": 30
   },
   "runtime_basis": "50 Ah L6 modules' rating, 10 kW for 15 minutes each, start of battery life"
  },
  {
   "sku": "INF-100+L6-CAB-10x50LI",
   "series": "INFINITE",
   "description": "100kVA + 1x L6 10x50",
   "url": "https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/",
   "kva": 100,
   "kw": 100,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "External L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": null,
   "depth_in": null,
   "height_in": null,
   "width_mm": null,
   "depth_mm": null,
   "height_mm": null,
   "net_weight_lb": 1808,
   "net_weight_kg": 820.1,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": {
    "10": 150,
    "20": 75,
    "25": 60,
    "30": 50,
    "40": 38,
    "50": 30,
    "60": 25,
    "70": 21,
    "75": 20,
    "80": 19,
    "90": 17,
    "100": 15
   },
   "runtime_basis": "50 Ah L6 modules' rating, 10 kW for 15 minutes each, start of battery life"
  },
  {
   "sku": "INF-100+L6-CAB-20x50LI",
   "series": "INFINITE",
   "description": "100kVA + 1x L6 20x50",
   "url": "https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/",
   "kva": 100,
   "kw": 100,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "External L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": null,
   "depth_in": null,
   "height_in": null,
   "width_mm": null,
   "depth_mm": null,
   "height_mm": null,
   "net_weight_lb": 2623.8,
   "net_weight_kg": 1190.1,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": {
    "10": 300,
    "20": 150,
    "25": 120,
    "30": 100,
    "40": 75,
    "50": 60,
    "60": 50,
    "70": 43,
    "75": 40,
    "80": 38,
    "90": 33,
    "100": 30
   },
   "runtime_basis": "50 Ah L6 modules' rating, 10 kW for 15 minutes each, start of battery life"
  },
  {
   "sku": "INF-200+1",
   "series": "INFINITE",
   "description": "200kVA N+1 (frame + 3 PM)",
   "url": "https://www.aecups.com/us/products/infinite/inf-200-1/",
   "kva": 200,
   "kw": 200,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+1",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External VRLA bank or L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": 23.62,
   "depth_in": 39.37,
   "height_in": 81.42,
   "width_mm": 600,
   "depth_mm": 1000,
   "height_mm": 2068,
   "net_weight_lb": 710.4,
   "net_weight_kg": 322.2,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF-200+1+L6-CAB-20x50LI",
   "series": "INFINITE",
   "description": "200kVA N+1 + 1x L6 20x50",
   "url": "https://www.aecups.com/us/products/infinite/inf-200-1-l6-cab-20x50li/",
   "kva": 200,
   "kw": 200,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular N+1",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "External L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": null,
   "depth_in": null,
   "height_in": null,
   "width_mm": null,
   "depth_mm": null,
   "height_mm": null,
   "net_weight_lb": 2881.9,
   "net_weight_kg": 1307.2,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": {
    "10": 150,
    "20": 75,
    "25": 60,
    "30": 50,
    "40": 38,
    "50": 30,
    "60": 25,
    "70": 21,
    "75": 20,
    "80": 19,
    "90": 17,
    "100": 15
   },
   "runtime_basis": "50 Ah L6 modules' rating, 10 kW for 15 minutes each, start of battery life"
  },
  {
   "sku": "INF-200+L6-CAB-20x50LI",
   "series": "INFINITE",
   "description": "200kVA + 1x L6 20x50",
   "url": "https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/",
   "kva": 200,
   "kw": 200,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "External L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": null,
   "depth_in": null,
   "height_in": null,
   "width_mm": null,
   "depth_mm": null,
   "height_mm": null,
   "net_weight_lb": 2762.9,
   "net_weight_kg": 1253.2,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": {
    "10": 150,
    "20": 75,
    "25": 60,
    "30": 50,
    "40": 38,
    "50": 30,
    "60": 25,
    "70": 21,
    "75": 20,
    "80": 19,
    "90": 17,
    "100": 15
   },
   "runtime_basis": "50 Ah L6 modules' rating, 10 kW for 15 minutes each, start of battery life"
  },
  {
   "sku": "INF-400+2xL6-CAB-20x50LI",
   "series": "INFINITE",
   "description": "400kVA + 2x L6 20x50",
   "url": "https://www.aecups.com/us/products/infinite/inf-400-2xl6-cab-20x50li/",
   "kva": 400,
   "kw": 400,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "External L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": null,
   "depth_in": null,
   "height_in": null,
   "width_mm": null,
   "depth_mm": null,
   "height_mm": null,
   "net_weight_lb": 5525.7,
   "net_weight_kg": 2506.4,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": {
    "10": 150,
    "20": 75,
    "25": 60,
    "30": 50,
    "40": 38,
    "50": 30,
    "60": 25,
    "70": 21,
    "75": 20,
    "80": 19,
    "90": 17,
    "100": 15
   },
   "runtime_basis": "50 Ah L6 modules' rating, 10 kW for 15 minutes each, start of battery life"
  },
  {
   "sku": "INF-600+3xL6-CAB-20x50LI",
   "series": "INFINITE",
   "description": "600kVA + 3x L6 20x50",
   "url": "https://www.aecups.com/us/products/infinite/inf-600-3xl6-cab-20x50li/",
   "kva": 600,
   "kw": 600,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.3,
   "battery": "Lithium LiFePO4",
   "battery_configuration": "External L6 lithium cabinets",
   "battery_dc_bus_v": 480,
   "width_in": null,
   "depth_in": null,
   "height_in": null,
   "width_mm": null,
   "depth_mm": null,
   "height_mm": null,
   "net_weight_lb": 8597.2,
   "net_weight_kg": 3899.6,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": {
    "10": 150,
    "20": 75,
    "25": 60,
    "30": 50,
    "40": 38,
    "50": 30,
    "60": 25,
    "70": 21,
    "75": 20,
    "80": 19,
    "90": 17,
    "100": 15
   },
   "runtime_basis": "50 Ah L6 modules' rating, 10 kW for 15 minutes each, start of battery life"
  },
  {
   "sku": "INF15-750",
   "series": "INFINITE 1.5MW",
   "description": "750kVA (frame1500 + 6 PM)",
   "url": "https://www.aecups.com/us/products/infinite-1-5mw/inf15-750/",
   "kva": 750,
   "kw": 750,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.5,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 600,
   "width_in": 70.87,
   "depth_in": 39.37,
   "height_in": 78.74,
   "width_mm": 1800,
   "depth_mm": 1000,
   "height_mm": 2000,
   "net_weight_lb": 5456.4,
   "net_weight_kg": 2475,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF15-750+1",
   "series": "INFINITE 1.5MW",
   "description": "750kVA N+1 (frame1500 + 7 PM)",
   "url": "https://www.aecups.com/us/products/infinite-1-5mw/inf15-750-1/",
   "kva": 750,
   "kw": 750,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.5,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 600,
   "width_in": 70.87,
   "depth_in": 39.37,
   "height_in": 78.74,
   "width_mm": 1800,
   "depth_mm": 1000,
   "height_mm": 2000,
   "net_weight_lb": 5575.5,
   "net_weight_kg": 2529,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF15-1000",
   "series": "INFINITE 1.5MW",
   "description": "1000kVA (frame1500 + 8 PM)",
   "url": "https://www.aecups.com/us/products/infinite-1-5mw/inf15-1000/",
   "kva": 1000,
   "kw": 1000,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.5,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 600,
   "width_in": 70.87,
   "depth_in": 39.37,
   "height_in": 78.74,
   "width_mm": 1800,
   "depth_mm": 1000,
   "height_mm": 2000,
   "net_weight_lb": 5694.5,
   "net_weight_kg": 2583,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF15-1000+1",
   "series": "INFINITE 1.5MW",
   "description": "1000kVA N+1 (frame1500 + 9 PM)",
   "url": "https://www.aecups.com/us/products/infinite-1-5mw/inf15-1000-1/",
   "kva": 1000,
   "kw": 1000,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.5,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 600,
   "width_in": 70.87,
   "depth_in": 39.37,
   "height_in": 78.74,
   "width_mm": 1800,
   "depth_mm": 1000,
   "height_mm": 2000,
   "net_weight_lb": 5813.6,
   "net_weight_kg": 2637,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF15-1250",
   "series": "INFINITE 1.5MW",
   "description": "1250kVA (frame1500 + 10 PM)",
   "url": "https://www.aecups.com/us/products/infinite-1-5mw/inf15-1250/",
   "kva": 1250,
   "kw": 1250,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.5,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 600,
   "width_in": 70.87,
   "depth_in": 39.37,
   "height_in": 78.74,
   "width_mm": 1800,
   "depth_mm": 1000,
   "height_mm": 2000,
   "net_weight_lb": 5932.6,
   "net_weight_kg": 2691,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF15-1250+1",
   "series": "INFINITE 1.5MW",
   "description": "1250kVA N+1 (frame1500 + 11 PM)",
   "url": "https://www.aecups.com/us/products/infinite-1-5mw/inf15-1250-1/",
   "kva": 1250,
   "kw": 1250,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.5,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 600,
   "width_in": 70.87,
   "depth_in": 39.37,
   "height_in": 78.74,
   "width_mm": 1800,
   "depth_mm": 1000,
   "height_mm": 2000,
   "net_weight_lb": 6051.7,
   "net_weight_kg": 2745,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  },
  {
   "sku": "INF15-1500",
   "series": "INFINITE 1.5MW",
   "description": "1500kVA (frame1500 + 12 PM)",
   "url": "https://www.aecups.com/us/products/infinite-1-5mw/inf15-1500/",
   "kva": 1500,
   "kw": 1500,
   "power_factor": "1.0",
   "supply": "480 V three-phase, 3-wire (delta)",
   "voltage": "480V",
   "phase": "3Ph",
   "topology": "Online double conversion, modular",
   "form_factor": "Modular",
   "efficiency_max_pct": 97.5,
   "battery": "VRLA or lithium LiFePO4",
   "battery_configuration": "External battery bank",
   "battery_dc_bus_v": 600,
   "width_in": 70.87,
   "depth_in": 39.37,
   "height_in": 78.74,
   "width_mm": 1800,
   "depth_mm": 1000,
   "height_mm": 2000,
   "net_weight_lb": 6170.7,
   "net_weight_kg": 2799,
   "warranty": "3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries",
   "runtime_min_at_load_pct": null,
   "runtime_basis": null
  }
 ]
}