title: "AUREON UPS questions and answers | AEC"
url: https://www.aecups.com/us/faq/aureon/
description: "8 questions about the AEC AUREON: choosing the model, runtime, installation, monitoring and service, each with its answer and the page it comes from."
language: en-US
---

Questions and answers

# AUREON: questions and answers

8 questions about the AEC AUREON, from its series page and its 8 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

[AUREON](https://www.aecups.com/us/products/aureon/) [All questions](https://www.aecups.com/us/faq/)

## Choosing, sizing and ordering 2 questions

#### What sizes does AUREON come in?

10 to 30 kVA, in 8 models of the 2026 catalog for the US, from the AUR-10 (10 kVA) to the AUR30-80X9A (30 kVA). The datasheet on this page gives every one.

Answered on [AUREON](https://www.aecups.com/us/products/aureon/)

#### What supply does AUREON need?

208 V, three-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on [AUREON](https://www.aecups.com/us/products/aureon/)

## Runtime and batteries 1 question

#### What batteries does AUREON use?

VRLA batteries. The battery bus is 240 V DC on every model.

Answered on [AUREON](https://www.aecups.com/us/products/aureon/)

## Installation, size and connections 3 questions

#### What is the output current of each AUREON model?

At full load, from the rating and the voltage:

| Model | Output current | Worked out as |
| --- | --- | --- |
| [AUR-10](https://www.aecups.com/us/products/aureon/aur-10/) | 27.8 A per phase | 10 kVA ÷ (√3 × 208 V) |
| [AUR-20](https://www.aecups.com/us/products/aureon/aur-20/) | 55.5 A per phase | 20 kVA ÷ (√3 × 208 V) |
| [AUR-30](https://www.aecups.com/us/products/aureon/aur-30/) | 83.3 A per phase | 30 kVA ÷ (√3 × 208 V) |
| [AUR10-40X9A](https://www.aecups.com/us/products/aureon/aur10-40x9a/) | 27.8 A per phase | 10 kVA ÷ (√3 × 208 V) |
| [AUR10-80X9A](https://www.aecups.com/us/products/aureon/aur10-80x9a/) | 27.8 A per phase | 10 kVA ÷ (√3 × 208 V) |
| [AUR20-60X9A](https://www.aecups.com/us/products/aureon/aur20-60x9a/) | 55.5 A per phase | 20 kVA ÷ (√3 × 208 V) |
| [AUR20-80X9A](https://www.aecups.com/us/products/aureon/aur20-80x9a/) | 55.5 A per phase | 20 kVA ÷ (√3 × 208 V) |
| [AUR30-80X9A](https://www.aecups.com/us/products/aureon/aur30-80x9a/) | 83.3 A per phase | 30 kVA ÷ (√3 × 208 V) |

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

#### How much heat does each AUREON model give off?

At full load, model by model:

| Model | Heat | BTU/h | Efficiency |
| --- | --- | --- | --- |
| [AUR-10](https://www.aecups.com/us/products/aureon/aur-10/) | 661 W | 2,260 | 93.8% |
| [AUR-20](https://www.aecups.com/us/products/aureon/aur-20/) | 1.3 kW | 4,510 | 93.8% |
| [AUR-30](https://www.aecups.com/us/products/aureon/aur-30/) | 2.0 kW | 6,770 | 93.8% |
| [AUR10-40X9A](https://www.aecups.com/us/products/aureon/aur10-40x9a/) | 661 W | 2,260 | 93.8% |
| [AUR10-80X9A](https://www.aecups.com/us/products/aureon/aur10-80x9a/) | 661 W | 2,260 | 93.8% |
| [AUR20-60X9A](https://www.aecups.com/us/products/aureon/aur20-60x9a/) | 1.3 kW | 4,510 | 93.8% |
| [AUR20-80X9A](https://www.aecups.com/us/products/aureon/aur20-80x9a/) | 1.3 kW | 4,510 | 93.8% |
| [AUR30-80X9A](https://www.aecups.com/us/products/aureon/aur30-80x9a/) | 2.0 kW | 6,770 | 93.8% |

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

#### Which AUREON models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

| Model | Upright through the door | Narrow side, height |
| --- | --- | --- |
| [AUR-10](https://www.aecups.com/us/products/aureon/aur-10/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |
| [AUR-20](https://www.aecups.com/us/products/aureon/aur-20/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |
| [AUR-30](https://www.aecups.com/us/products/aureon/aur-30/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |
| [AUR10-40X9A](https://www.aecups.com/us/products/aureon/aur10-40x9a/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |
| [AUR10-80X9A](https://www.aecups.com/us/products/aureon/aur10-80x9a/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |
| [AUR20-60X9A](https://www.aecups.com/us/products/aureon/aur20-60x9a/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |
| [AUR20-80X9A](https://www.aecups.com/us/products/aureon/aur20-80x9a/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |
| [AUR30-80X9A](https://www.aecups.com/us/products/aureon/aur30-80x9a/) | Yes | 14.9 in (378 mm) across, 49.2 in (1,250 mm) high |

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

## Communication and monitoring 1 question

#### How is AUREON monitored over the network?

With the AEC SNMP-L network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on [AUREON](https://www.aecups.com/us/products/aureon/)

## Warranty, service and maintenance 1 question

#### What warranty does AUREON have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on [AUREON](https://www.aecups.com/us/products/aureon/)

## By series

## Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.

[Ask an engineer](https://www.aecups.com/us/contacts/#form) [Blog and guides](https://www.aecups.com/us/blog/)