title: "ETHERNO UPS questions and answers | AEC"
url: https://www.aecups.com/us/faq/etherno/
description: "8 questions about the AEC ETHERNO: choosing the model, runtime, installation, monitoring and service, each with its answer and the page it comes from."
language: en-US
---

Questions and answers

# ETHERNO: questions and answers

8 questions about the AEC ETHERNO, from its series page and its 9 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

[ETHERNO](https://www.aecups.com/us/products/etherno/) [All questions](https://www.aecups.com/us/faq/)

## Runtime and batteries 2 questions

#### How long does each ETHERNO model run on battery?

At the start of battery life, model by model:

| Model | 100 % load | 50 % load | 10 % load |
| --- | --- | --- | --- |
| [ETH10-1X50A-LI](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) | 14 min (10 kW) | 27 min (5.0 kW) | 2 h 13 min (1.0 kW) |
| [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) | 27 min (10 kW) | 55 min (5.0 kW) | 4 h 25 min (1.0 kW) |
| [ETH10-3X50A-LI](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) | 41 min (10 kW) | 82 min (5.0 kW) | 6 h 38 min (1.0 kW) |
| [ETH20-2X50A-LI](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) | 14 min (20 kW) | 27 min (10 kW) | 2 h 13 min (2.0 kW) |
| [ETH20-3X50A-LI](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) | 20 min (20 kW) | 41 min (10 kW) | 3 h 19 min (2.0 kW) |
| [ETH30-3X50A-LI](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/) | 14 min (30 kW) | 27 min (15 kW) | 2 h 13 min (3.0 kW) |

From the catalog runtime table at the start of battery life.

Runtime falls faster than the load rises: the chart on each model's page gives the minutes at any load in between.

Each model's own page, linked in the table, gives its full answer and data.

#### How long does ETHERNO run on battery at 20 kVA?

At a full 20 kW load, the ETH20-2X50A-LI (two 50 Ah lithium modules) runs 14 min and the ETH20-3X50A-LI (three 50 Ah lithium modules) runs 20 min; at half load, 27 min and 41 min. Figures from the 2026 catalog runtime tables, with new batteries.

Answered on [ETHERNO](https://www.aecups.com/us/products/etherno/)

## Lithium batteries 1 question

#### Can the ETHERNO lithium modules be changed with the load on?

Yes. ETHERNO takes hot-swappable 50 Ah lithium modules: a module comes out and goes back in while the UPS carries the load. The catalog sets it up with one, two or three modules at 10 kVA; two or three modules at 20 kVA; three modules at 30 kVA.

Answered on [ETHERNO](https://www.aecups.com/us/products/etherno/)

## Installation, size and connections 4 questions

#### What is the output current of each ETHERNO model?

At full load, from the rating and the voltage:

| Model | Output current | Worked out as |
| --- | --- | --- |
| [ETH10-1X50A-LI](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) | 27.8 A per phase | 10 kVA ÷ (√3 × 208 V) |
| [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) | 27.8 A per phase | 10 kVA ÷ (√3 × 208 V) |
| [ETH10-3X50A-LI](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) | 27.8 A per phase | 10 kVA ÷ (√3 × 208 V) |
| [ETH20-2X50A-LI](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) | 55.5 A per phase | 20 kVA ÷ (√3 × 208 V) |
| [ETH20-3X50A-LI](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) | 55.5 A per phase | 20 kVA ÷ (√3 × 208 V) |
| [ETH30-3X50A-LI](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/) | 83.3 A per phase | 30 kVA ÷ (√3 × 208 V) |

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

#### How much heat does each ETHERNO model give off?

At full load, model by model:

| Model | Heat | BTU/h | Efficiency |
| --- | --- | --- | --- |
| [ETH10](https://www.aecups.com/us/products/etherno/eth10/) | 661 W | 2,260 | 93.8% |
| [ETH10-1X50A-LI](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) | 661 W | 2,260 | 93.8% |
| [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) | 661 W | 2,260 | 93.8% |
| [ETH10-3X50A-LI](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) | 661 W | 2,260 | 93.8% |
| [ETH20](https://www.aecups.com/us/products/etherno/eth20/) | 1.3 kW | 4,510 | 93.8% |
| [ETH20-2X50A-LI](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) | 1.3 kW | 4,510 | 93.8% |
| [ETH20-3X50A-LI](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) | 1.3 kW | 4,510 | 93.8% |
| [ETH30](https://www.aecups.com/us/products/etherno/eth30/) | 2.0 kW | 6,770 | 93.8% |
| [ETH30-3X50A-LI](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/) | 2.0 kW | 6,770 | 93.8% |

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

#### Which ETHERNO models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

| Model | Upright through the door | Narrow side, height |
| --- | --- | --- |
| [ETH10](https://www.aecups.com/us/products/etherno/eth10/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH10-1X50A-LI](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH10-3X50A-LI](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH20](https://www.aecups.com/us/products/etherno/eth20/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH20-2X50A-LI](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH20-3X50A-LI](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH30](https://www.aecups.com/us/products/etherno/eth30/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |
| [ETH30-3X50A-LI](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/) | Yes | 12.6 in (320 mm) across, 49.2 in (1,250 mm) high |

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

#### What supply does ETHERNO need?

208 V three-phase, 4-wire (3P+N), for every model from 10 to 30 kVA. Its power factor is 1.0 (kVA = kW), so the 20 kVA model delivers 20 kW.

Answered on [ETHERNO](https://www.aecups.com/us/products/etherno/)

## Warranty, service and maintenance 1 question

#### What warranty does ETHERNO have?

5 years, lithium modules included, from start-up. Register the UPS with AEC after start-up.

Answered on [ETHERNO](https://www.aecups.com/us/products/etherno/)

## By series

## Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.

[Ask an engineer](https://www.aecups.com/us/contacts/#form) [Blog and guides](https://www.aecups.com/us/blog/)