title: "FERRUS UPS questions and answers | AEC"
url: https://www.aecups.com/us/faq/ferrus/
description: "7 questions about the AEC FERRUS: choosing the model, runtime, installation, monitoring and service, each with its answer and the page it comes from."
language: en-US
---

Questions and answers

# FERRUS: questions and answers

7 questions about the AEC FERRUS, from its series page and its 3 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

[FERRUS](https://www.aecups.com/us/products/ferrus/) [All questions](https://www.aecups.com/us/faq/)

## Choosing, sizing and ordering 2 questions

#### What sizes does FERRUS come in?

1 to 3 kVA, in 3 models of the 2026 catalog for the US, from the FER1000-2X9 (1 kVA) to the FER3000-6X9 (3 kVA). The datasheet on this page gives every one.

Answered on [FERRUS](https://www.aecups.com/us/products/ferrus/)

#### What supply does FERRUS need?

110/120 V, 50–60 Hz, single-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on [FERRUS](https://www.aecups.com/us/products/ferrus/)

## Runtime and batteries 1 question

#### What batteries does FERRUS use?

Internal VRLA batteries. The battery bus runs from 24 V DC to 72 V DC, by model.

Answered on [FERRUS](https://www.aecups.com/us/products/ferrus/)

## Installation, size and connections 2 questions

#### What is the output current of each FERRUS model?

At full load, from the rating and the voltage:

| Model | Output current | Worked out as |
| --- | --- | --- |
| [FER1000-2X9](https://www.aecups.com/us/products/ferrus/fer1000-2x9/) | 8.3 A at 120 V | 1.0 kVA ÷ 120 V |
| [FER2000-4X9](https://www.aecups.com/us/products/ferrus/fer2000-4x9/) | 16.7 A at 120 V | 2.0 kVA ÷ 120 V |
| [FER3000-6X9](https://www.aecups.com/us/products/ferrus/fer3000-6x9/) | 25.0 A at 120 V | 3.0 kVA ÷ 120 V |

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

#### How much heat does each FERRUS model give off?

At full load, model by model:

| Model | Heat | BTU/h | Efficiency |
| --- | --- | --- | --- |
| [FER1000-2X9](https://www.aecups.com/us/products/ferrus/fer1000-2x9/) | 78 W | 260 | 92.8% |
| [FER2000-4X9](https://www.aecups.com/us/products/ferrus/fer2000-4x9/) | 155 W | 530 | 92.8% |
| [FER3000-6X9](https://www.aecups.com/us/products/ferrus/fer3000-6x9/) | 233 W | 790 | 92.8% |

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

## Communication and monitoring 1 question

#### How is FERRUS monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on [FERRUS](https://www.aecups.com/us/products/ferrus/)

## Warranty, service and maintenance 1 question

#### What warranty does FERRUS have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on [FERRUS](https://www.aecups.com/us/products/ferrus/)

## By series

## Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.

[Ask an engineer](https://www.aecups.com/us/contacts/#form) [Blog and guides](https://www.aecups.com/us/blog/)