Questions and answers

# INFINITE: questions and answers

9 questions about the AEC INFINITE, from its series page and its 13 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

[INFINITE](https://www.aecups.com/us/products/infinite/) [All questions](https://www.aecups.com/us/faq/)

## Choosing, sizing and ordering 2 questions

#### Which AEC UPS reach 500 kVA at 480 V?

CIRRO, 60–1,600 kVA on 4-wire supplies, and INFINITE, 100–600 kVA on 3-wire supplies. INFINITE 1.5MW starts at 750 kVA.

Answered on [INFINITE](https://www.aecups.com/us/products/infinite/)

#### How is INFINITE built up to 600 kVA?

100 to 600 kVA: one 100 or 200 kVA frame, or up to three 200 kVA frames in parallel; above 600 kVA, INFINITE 1.5MW. The power modules are 100 kVA; one module more than the load needs gives N+1 redundancy.

Answered on [INFINITE](https://www.aecups.com/us/products/infinite/)

## Runtime and batteries 2 questions

#### How long does each INFINITE model run on battery?

At the start of battery life, model by model:

| Model | 100 % load | 50 % load | 10 % load |
| --- | --- | --- | --- |
| [INF-100+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/) | 30 min (100 kW) | 60 min (50 kW) | 5 h 0 min (10 kW) |
| [INF-100+L6-CAB-10x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) | 15 min (100 kW) | 30 min (50 kW) | 2 h 30 min (10 kW) |
| [INF-100+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/) | 30 min (100 kW) | 60 min (50 kW) | 5 h 0 min (10 kW) |
| [INF-200+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-1-l6-cab-20x50li/) | 15 min (200 kW) | 30 min (100 kW) | 2 h 30 min (20 kW) |
| [INF-200+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/) | 15 min (200 kW) | 30 min (100 kW) | 2 h 30 min (20 kW) |
| [INF-400+2xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-400-2xl6-cab-20x50li/) | 15 min (400 kW) | 30 min (200 kW) | 2 h 30 min (40 kW) |
| [INF-600+3xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-600-3xl6-cab-20x50li/) | 15 min (600 kW) | 30 min (300 kW) | 2 h 30 min (60 kW) |

From the rating of its 50 Ah lithium modules, 10 kW for 15 minutes each, at the start of battery life.

These minutes divide the modules' energy by the load; a battery gives less in a fast discharge, so take the light-load figures as an upper bound. The chart on each model's page gives the minutes at any load in between.

Each model's own page, linked in the table, gives its full answer and data.

#### What batteries does INFINITE use?

External, lead-acid (30–50 blocks) or AEC L6 lithium cabinets. With L6 lithium the catalog lists 7 set-ups, from the INF-100+1+L6-CAB-20x50LI to the INF-600+3xL6-CAB-20x50LI.

Answered on [INFINITE](https://www.aecups.com/us/products/infinite/)

## Installation, size and connections 4 questions

#### What is the output current of each INFINITE model?

At full load, from the rating and the voltage:

| Model | Output current | Worked out as |
| --- | --- | --- |
| [INF-100](https://www.aecups.com/us/products/infinite/inf-100/) | 120.3 A per phase | 100 kVA ÷ (√3 × 480 V) |
| [INF-100+1](https://www.aecups.com/us/products/infinite/inf-100-1/) | 120.3 A per phase | 100 kVA ÷ (√3 × 480 V) |
| [INF-100+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/) | 120.3 A per phase | 100 kVA ÷ (√3 × 480 V) |
| [INF-100+L6-CAB-10x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) | 120.3 A per phase | 100 kVA ÷ (√3 × 480 V) |
| [INF-100+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/) | 120.3 A per phase | 100 kVA ÷ (√3 × 480 V) |
| [INF-200](https://www.aecups.com/us/products/infinite/inf-200/) | 240.6 A per phase | 200 kVA ÷ (√3 × 480 V) |
| [INF-200+1](https://www.aecups.com/us/products/infinite/inf-200-1/) | 240.6 A per phase | 200 kVA ÷ (√3 × 480 V) |
| [INF-200+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-1-l6-cab-20x50li/) | 240.6 A per phase | 200 kVA ÷ (√3 × 480 V) |
| [INF-200+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/) | 240.6 A per phase | 200 kVA ÷ (√3 × 480 V) |
| [INF-400](https://www.aecups.com/us/products/infinite/inf-400/) | 481.1 A per phase | 400 kVA ÷ (√3 × 480 V) |
| [INF-400+2xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-400-2xl6-cab-20x50li/) | 481.1 A per phase | 400 kVA ÷ (√3 × 480 V) |
| [INF-600](https://www.aecups.com/us/products/infinite/inf-600/) | 721.7 A per phase | 600 kVA ÷ (√3 × 480 V) |
| [INF-600+3xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-600-3xl6-cab-20x50li/) | 721.7 A per phase | 600 kVA ÷ (√3 × 480 V) |

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

#### How much heat does each INFINITE model give off?

At full load, model by model:

| Model | Heat | BTU/h | Efficiency |
| --- | --- | --- | --- |
| [INF-100](https://www.aecups.com/us/products/infinite/inf-100/) | 2.8 kW | 9,470 | 97.3% |
| [INF-100+1](https://www.aecups.com/us/products/infinite/inf-100-1/) | 2.8 kW | 9,470 | 97.3% |
| [INF-100+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/) | 2.8 kW | 9,470 | 97.3% |
| [INF-100+L6-CAB-10x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) | 2.8 kW | 9,470 | 97.3% |
| [INF-100+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/) | 2.8 kW | 9,470 | 97.3% |
| [INF-200](https://www.aecups.com/us/products/infinite/inf-200/) | 5.5 kW | 18,940 | 97.3% |
| [INF-200+1](https://www.aecups.com/us/products/infinite/inf-200-1/) | 5.5 kW | 18,940 | 97.3% |
| [INF-200+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-1-l6-cab-20x50li/) | 5.5 kW | 18,940 | 97.3% |
| [INF-200+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/) | 5.5 kW | 18,940 | 97.3% |
| [INF-400](https://www.aecups.com/us/products/infinite/inf-400/) | 11 kW | 37,870 | 97.3% |
| [INF-400+2xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-400-2xl6-cab-20x50li/) | 11 kW | 37,870 | 97.3% |
| [INF-600](https://www.aecups.com/us/products/infinite/inf-600/) | 17 kW | 56,810 | 97.3% |
| [INF-600+3xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-600-3xl6-cab-20x50li/) | 17 kW | 56,810 | 97.3% |

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

#### Which INFINITE models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

| Model | Upright through the door | Narrow side, height |
| --- | --- | --- |
| [INF-100](https://www.aecups.com/us/products/infinite/inf-100/) | No: needs an opening taller than 81.4 in | 81.4 in (2,068 mm) high |
| [INF-100+1](https://www.aecups.com/us/products/infinite/inf-100-1/) | No: needs an opening taller than 81.4 in | 81.4 in (2,068 mm) high |
| [INF-200](https://www.aecups.com/us/products/infinite/inf-200/) | No: needs an opening taller than 81.4 in | 81.4 in (2,068 mm) high |
| [INF-200+1](https://www.aecups.com/us/products/infinite/inf-200-1/) | No: needs an opening taller than 81.4 in | 81.4 in (2,068 mm) high |
| [INF-400](https://www.aecups.com/us/products/infinite/inf-400/) | No: needs an opening taller than 81.4 in | 81.4 in (2,068 mm) high |
| [INF-600](https://www.aecups.com/us/products/infinite/inf-600/) | No: needs an opening taller than 81.4 in | 81.4 in (2,068 mm) high |

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

#### What does silicon carbide (SiC) change in INFINITE?

INFINITE's power modules use silicon carbide (SiC) semiconductors, where AEC's other three-phase series use 3-level IGBTs. The 2026 catalog gives INFINITE up to 97.3% efficiency: less loss, so less heat for the room's cooling to remove.

Answered on [INFINITE](https://www.aecups.com/us/products/infinite/)

## Warranty, service and maintenance 1 question

#### What warranty does INFINITE have?

3 years on UPS, 5 if registered; 5 years on lithium cabinets including batteries. To get the 5 years, register the UPS with its serial number and invoice.

Answered on [INFINITE](https://www.aecups.com/us/products/infinite/)

## By series

## Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.

[Ask an engineer](https://www.aecups.com/us/contacts/#form) [Blog and guides](https://www.aecups.com/us/blog/)