## Choosing, sizing and ordering 2 questions

#### What sizes does RADIANT-IB come in?

20 to 100 kVA, in 5 models of the 2026 catalog for the US, from the RADIB100-1X20 (20 kVA) to the RADIB100-5X20 (100 kVA). The datasheet on this page gives every one.

Answered on [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/)

#### What supply does RADIANT-IB need?

208/120 V three-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/)

## Runtime and batteries 1 question

#### What batteries does RADIANT-IB use?

Internal hot-swappable VRLA, up to 240 × 12 V 9 Ah blocks. The battery bus is 240 V DC on every model.

Answered on [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/)

## Installation, size and connections 3 questions

#### What is the output current of each RADIANT-IB model?

At full load, from the rating and the voltage:

| Model | Output current | Worked out as |
| --- | --- | --- |
| [RADIB100-1X20](https://www.aecups.com/us/products/radiant-ib/radib100-1x20/) | 55.5 A per phase | 20 kVA ÷ (√3 × 208 V) |
| [RADIB100-2X20](https://www.aecups.com/us/products/radiant-ib/radib100-2x20/) | 111.0 A per phase | 40 kVA ÷ (√3 × 208 V) |
| [RADIB100-3X20](https://www.aecups.com/us/products/radiant-ib/radib100-3x20/) | 166.5 A per phase | 60 kVA ÷ (√3 × 208 V) |
| [RADIB100-4X20](https://www.aecups.com/us/products/radiant-ib/radib100-4x20/) | 222.1 A per phase | 80 kVA ÷ (√3 × 208 V) |
| [RADIB100-5X20](https://www.aecups.com/us/products/radiant-ib/radib100-5x20/) | 277.6 A per phase | 100 kVA ÷ (√3 × 208 V) |

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

#### How much heat does each RADIANT-IB model give off?

At full load, model by model:

| Model | Heat | BTU/h | Efficiency |
| --- | --- | --- | --- |
| [RADIB100-1X20](https://www.aecups.com/us/products/radiant-ib/radib100-1x20/) | 1.3 kW | 4,510 | 93.8% |
| [RADIB100-2X20](https://www.aecups.com/us/products/radiant-ib/radib100-2x20/) | 2.6 kW | 9,020 | 93.8% |
| [RADIB100-3X20](https://www.aecups.com/us/products/radiant-ib/radib100-3x20/) | 4.0 kW | 13,530 | 93.8% |
| [RADIB100-4X20](https://www.aecups.com/us/products/radiant-ib/radib100-4x20/) | 5.3 kW | 18,040 | 93.8% |
| [RADIB100-5X20](https://www.aecups.com/us/products/radiant-ib/radib100-5x20/) | 6.6 kW | 22,550 | 93.8% |

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

#### Which RADIANT-IB models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

| Model | Upright through the door | Narrow side, height |
| --- | --- | --- |
| [RADIB100-1X20](https://www.aecups.com/us/products/radiant-ib/radib100-1x20/) | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| [RADIB100-2X20](https://www.aecups.com/us/products/radiant-ib/radib100-2x20/) | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| [RADIB100-3X20](https://www.aecups.com/us/products/radiant-ib/radib100-3x20/) | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| [RADIB100-4X20](https://www.aecups.com/us/products/radiant-ib/radib100-4x20/) | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| [RADIB100-5X20](https://www.aecups.com/us/products/radiant-ib/radib100-5x20/) | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

## Communication and monitoring 1 question

#### How is RADIANT-IB monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/)

## Warranty, service and maintenance 1 question

#### What warranty does RADIANT-IB have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/)